Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹24,100
Closing Date
17 Jul 2023, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
creation of 63 KVA Substation alongwith 11 KV line for PHC Tikri under District Capex Health Sector
2023_PDD_218691_1
ED/Udh/16 of 2023-24 dt. 26-06-2023
Open Tender
Electrical Works
Turn-key
90 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division UdhampurJPDCL
₹24,100
4 Aug 2023
26 Jun 2023
19 Jul 2023
27 Jun 2023
17 Jul 2023
27 Jun 2023
26 Jun 2023 - 3 Jul 2023
Survey, Transportation, Carriage, Testing and Commissioning for erection of 11 KV line on 9 mtr long PCC poles, 30 mm sq. ACSR condcutor for creation of 63 KVA Substation at PHC Tikri.
9 mtr. Long PCC Pole (PCC-WL-300Kg)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
Shackle Insulator
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Al. Jointing Sleeves
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Transportation, Carriage, Testing and Commissioning for Creation of 63 KVA Substation at PHC Tikri.
11/0.433kV, 3-phase Distribution Transformers 63 KVA with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² 1.1 kv Grade, PVC insulated Aluminium stranded conductor FRLS type
9 Mtr. Long ST Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber.
11 KV polymeric composite Pin insulator, 12kv, 5 kn, lightening impulse 75 KV Positive and 80 KV Negative, creepage distance 320mm
LT Distribution Box for 63 KVA DTR with MCCB for incomer and SFU's for outgoing Circuits.
Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
Danger plates with clamps
GI Barbed wire for Anti Climbing
3-phase 4 wire LT Prodigy Meter with box
Cement Bottoming 1:2:4 mix as per REC Strandards 0.5 cum per pole
Painting of 9 mtr long ST poles with one coat of Red oxide and two coats of aluminium paint
THAPPA ELECTRICAL CONSTRUCTION AND SUPPLIERS
VEENA CONSTRUCTION CO.
HITECH ENTERPRISES
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .