Executive Engineer
Electy 400 Kv S S Div Banda
Work of SF 6 gas leakage attends on 400 KV 220 KV breakers at 400 KV sub station Banda.
2025_UPTCL_1007791_1
T-32/E.400KVS/SDIV.(B)/2024-25
Open Tender
Electrical Works
Lump-sum
Electy 400 Kv S S Div Banda
Detail Enclosed
2 documents required · 2 mandatory
₹590
Executive engineer
₹3,000
5 Mar 2025
18 Feb 2025
1 Mar 2025
18 Feb 2025
1 Mar 2025
18 Feb 2025
18 Feb 2025 - 1 Mar 2025
Amount
Description of Works
Attending the SF-6 gas leakage from 245 KV Circuit breaker (CGL make) of 400/220 KV 3I5 MVA ICT-II of R-phase pole Work includes opening of jumpers, connectors & dismentalling of 4inch IPS tube both side of breaker. Then extraction of SF-6 gas from R-phase pole in empty SF-6 gas cylinder. Then Safe dismantling of R-phase pole porcelain section, fixed & moving part assembly, of breaker after safely removing of nut bolt and gas kit of circuit breaker. After pulling out of circuit breaker fixed & moving part of breaker assembly then proper cleaning of breaker contacts , all part of chamber, replacement of defective O-ring of different size as per equipment of breaker pole (supplied by contractor in own cost) . Then complete erection of breaker moving & fix part and porcelain assembly of breaker. then creating vacuum in R-phase pole and then after filling of SF-6 gas up to required pressure then checking for leakage of gas with help of detector, checking and proper operation of circuit breaker . Then proper erection of both side of clamp & connector with 4 inch IPS pipe tube. all T&P , experiance engineer,labour, hydra should be arrange by contractor it self .
Tests for 220 kv Circuit Breakers associated & short out any defect found in wiring and with 315 MVA ICT- II:- 1. CRM 2. Open /closing time 3. PD test 4. Closing/Tripping coil Resistance 5. IR test
Attending of SF-6 gas leakage of 400 kv Banda-Rewa road-1st B-phase pole from connecting pipe line from breaker pole-2 pressure indication density meter, pressure gauge for Sf-6 gas alarm and lock out system after opening of connecting copper pipe and replacement of new O-rings ( supply by contactor). And removing all type of SF-6 gas leakage in pipe line. & rifling of SF-6 gas in to the breaker. ( all T&P arrange by contractor itself)
Attending of SF-6 gas leakage of 220 kv Banda-Banda 2nd Y,R phase pole from connecting pipe line from breaker pole-2 pressure indication density meter, pressure gauge for Sf-6 gas alarm and lock out system after opening of connecting copper pipe and replacement of new O-rings ( supply by contactor). and removing all type of SF-6 gas leakage in pipe line. & riffling of SF-6 gas in to the breaker. ( all T&P arrange by contractor itself)
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
M/S Bharat Construction (BID ID -5009162)
M/S V.K.T. SYSTEMS (BID ID -5008883)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .