27 Jun 2020
Amount
I.T.C. of 1.5 TR split AC unit i/c fixing of copper tubes covered with foam insulation in PVC flexible pipe, bending, brazing and leakage testing, laying/fixing of exisitng copper conductor cable, drain piping laying work etc. complete as required. (The AC units will be supplied by the department free of cost)
Dismantlling of the existing old/scrapped SAC/WAC from the wall complete with the frame of SAC, outdoor unit and piping i/c making good the damages and shifting & placing the same to store room in energy block etc. complete as required
Transportation of 1.5 TR split AC unit with complete with all accessories i/c loading & unloading from store at energy block, RTTC, Lucknow & SSA Gonda to site of work in main T E. building Delhamau pratapgharh etc. complete as required.
Providing & Fixing 500 MM Sweep A.C Supply padestal fan in MDF Room at main T.E. bldg at Delhamau Pratpgarh i/c ITC Complete as required. ( M/s Bajaj, Havells or SS make )
Supplying and fixing of copper refrigerent pipe with foam insulation of following size etc. complete as required.
1/2'' dia (for suction line)+foam
1/4'' dia (for discharge line)+foam
S/f 3 core 2.5 sqmm PVC insulated flexible copper cable i/c making connection etc. complete as required.
Supplying & fixing of following size pipe for condensed water drainage on surface with sadling at required distance with proper support etc. as reqd.
25 mm. dia C- PVC heavy duty pipe
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
a) 2 x1.5 sqmm + 1 x 1.5sqmm earth wire
b) 2 x 4 sqmm + 1 x 4 sqmm earth wire
c) 4 x 4 sqmm + 2 x 4 sqmm earth wire
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
a) Single pole
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
a) 4 way (4 + 12), Double door
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 X 25 sq. mm (28mm)
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Providing and 125 Amp. capacity TP&N disconnector fuseswitch unit inside the existing panel board with ISI marked HRCfuses including drilling holes in cubicle panel, makingconnections, etc. as required
Supplying & fixing of Prefabricated stand base frame made out of 14 swg MS sheet suitable for wall/floor mounting of condenser unit i/c cutting, welding, grouting with dash fastner, enamel painting, cutting the floor/wall and making good the same etc. complete as required.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .