| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.8 LAccepted-AOC | ₹16.8 L Quoted ₹18.8 L | L1 | Accepted-AOC BEING L1 |
| 2 | L2₹20.6 LRejected-Finance | ₹20.6 L | L2 | Rejected-Finance OTHER THAN L1 |
| 3 | L3₹22.2 LRejected-Finance 146 B SICOP BIRPUR INDUSTRIAL AREA BARI BRAHMANA JAMMU 181133 J K | BARI BRAHMANA | JAMMU | JAMMU AND KASHMIR | 181133 | ₹22.2 L | L3 | Rejected-Finance OTHER THAN L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical No in WLR of QE Sep 25 of HQ CENC letter dt 31 Jan 26 |
| Sl No | Description | Qty | Unit | ASIA ENTERPRISES L2 | M/S JIWAN SINGH L1 | jaima electricals L3 |
|---|---|---|---|---|---|---|
| 1.00 | Centrifuging (filteration/dehydration) of transformer oil including checking initial and after filteration Dielectric Strength of oil for transformers, Isolation transformers and voltage stabilizers located in various places of technical and domestic area with suitable machine having filteration, heating and pumping facility to improve the dielectric strength/insulation value of oil.
Note :- (i) Di electric strength of oil after filteration/dehydration shall not be less than 55 kv.
(ii) Oil for toping up shall be measured and paid separately under relevant item of this schedule
(iii) The contractor will take shut down orders in writing atleast two days in advance from Engr-in-charge before commencement of work.
(iv) The dielectric strength of oil shall be tested before and after filtration and necessary test results shall be submitted to the Engr-in-charge.(b) Filtration /dehydration of transformer oil shall be carried out at the location where transformer is installed under the AOR of GE (North) Akhnoor and necessary filter/dehydration plant having pressure gauge, hour meter, temperaturature gauge to be brought at site by contractor including electric supply arrangement to run the dehydration equipment and rate deemed to be included in the quoted rate. | 6,435 | Litre | 20 ₹1.3 L | 30 ₹1.9 L | 12 ₹77,220 |
| 2.00 | M & L for topping up/replacement of transformer oil with new transformer oil suitable for working voltage 11000 volts grade including necessary dehydration to achieve dielectric strength min 62 KV at 2.5 mm gap complete all as specified and directed.
Note :- New transformer oil to be bought in company sealed ISI marked container with test certificate. | 600 | Litre | 165 ₹99,000 | 140 ₹84,000 | 110 ₹66,000 |
| 3.00 | M & L for replacement of silica gel grains in the breather assembly of transformer complete all as specified and directed. | 20 | Kilogram | 500 ₹10,000 | 300 ₹6,000 | 300 ₹6,000 |
| 4.00 | M & L for replacement of breather assembly made with polycarbonate base and clear acylic glass of size min 50mm dia, min 120 mm long or suitable size as per site requirement for transformer complete all as specified and directed. | 10 | Each | 3,000 ₹30,000 | 1,000 ₹10,000 | 1,500 ₹15,000 |
| 5.00 | M & L for replacement of transformer temperature gauge dial type having temp range 0 to minimum 120 degree celcius complete all as specified and directed. | 5 | Each | 600 ₹3,000 | 1,500 ₹7,500 | 800 ₹4,000 |
| 6.00 | M&L for openning of top cover at situ or at wksp by unscrewing all nuts, bolts & washers, draining out transformer oil upto required level and keeping in clean container for replacement of HT/LT bushings, cleanning/repair and refixing complete with new cork sheet gasket, existing/new nuts, bolts & washers for transformer indoor/outdoor type, refilling of oil all as specified and directed for transformer capacity upto100 KVA to 200 KVA, 11/0.433 KV volts grade.. (Note:- HT/LT bushings, Studs, Brass stud, Nuts, bolts & washers required shall be measured and paid separately under relevant items of the schedule) | 4 | Each Job | 2,000 ₹8,000 | 2,000 ₹8,000 | 2,500 ₹10,000 |
| 7.00 | All as per items No-06 here-in-before but for transformer capacity 250-400 KVA. | 3 | Each Job | 2,000 ₹6,000 | 2,500 ₹7,500 | 2,500 ₹7,500 |
| 8.00 | All as per items No-06 here-in-before but for transformer capacity 500-630 KVA. | 4 | Each Job | 2,000 ₹8,000 | 3,000 ₹12,000 | 2,500 ₹10,000 |
| 9.00 | M&L for replacement of transformer porcelain bushing outdoor/indoor type in situ/wksp suitable for 11 KV grade complete with brass studs, rubber bush, washers, nuts, checknuts and cork sheet gasket for the rating of 100 KVA to 200 KVA, 11/0.415 KV transformer complete all as specified and directed. | 3 | Each | 1,500 ₹4,500 | 650 ₹1,950 | 1,000 ₹3,000 |
| 10.00 | All as per items No-9 here-in-before but for transformer capacity 250-500 KVA. | 3 | Each Job | 2,000 ₹6,000 | 750 ₹2,250 | 1,000 ₹3,000 |
Updated dates
Tender Value
₹29.9 L
EMD Value
₹60,000
Closing Date
23 Jan 2026, 6:00 pmClosed
Anurag Anand DCWE
HQ 135 WKS ENGRS PIN 914135 C/O 56 APO
COMPREHENSIVE REPAIR/ MAINT OF DISTRIBUTION TRANSFARMER EARTHINGS, PAINTING WORK, GOD, LIGHTENIG ARRESTERS, DEHYDRATION OF TRANSFORMER OIL AND CONNECTED WORKS UNDER GE (N) AKHNOOR.
2025_MES_746000_1
CWE/JA-32/2025-26
Open Tender
Electrical and Maintenance Works
180 days
AKHNOOR
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
GE NORTH AKHNOOR
₹60,000
Yes
27 Mar 2026
24 Dec 2025
26 Jan 2026
24 Dec 2025
23 Jan 2026
9 Jan 2026
M & L for topping up/replacement of transformer oil with new transformer oil suitable for working voltage 11000 volts grade including necessary dehydration to achieve dielectric strength min 62 KV at 2.5 mm gap complete all as specified and directed. Note :- New transformer oil to be bought in company sealed ISI marked container with test certificate.
M & L for replacement of silica gel grains in the breather assembly of transformer complete all as specified and directed.
M & L for replacement of breather assembly made with polycarbonate base and clear acylic glass of size min 50mm dia, min 120 mm long or suitable size as per site requirement for transformer complete all as specified and directed.
M & L for replacement of transformer temperature gauge dial type having temp range 0 to minimum 120 degree celcius complete all as specified and directed.
M&L for openning of top cover at situ or at wksp by unscrewing all nuts, bolts & washers, draining out transformer oil upto required level and keeping in clean container for replacement of HT/LT bushings, cleanning/repair and refixing complete with new cork sheet gasket, existing/new nuts, bolts & washers for transformer indoor/outdoor type, refilling of oil all as specified and directed for transformer capacity upto100 KVA to 200 KVA, 11/0.433 KV volts grade.. (Note:- HT/LT bushings, Studs, Brass stud, Nuts, bolts & washers required shall be measured and paid separately under relevant items of the schedule)
All as per items No-06 here-in-before but for transformer capacity 250-400 KVA.
All as per items No-06 here-in-before but for transformer capacity 500-630 KVA.
M&L for replacement of transformer porcelain bushing outdoor/indoor type in situ/wksp suitable for 11 KV grade complete with brass studs, rubber bush, washers, nuts, checknuts and cork sheet gasket for the rating of 100 KVA to 200 KVA, 11/0.415 KV transformer complete all as specified and directed.
All as per items No-9 here-in-before but for transformer capacity 250-500 KVA.
M&L for replacement of transformer LT porcelain bushing indoor/outdoor type in situ/wksp suitable for 1100 volts grade complete with rubber bush, washers, nuts, checknuts and cork sheet gasket for the rating of 100 KVA, to 200 KVA 11/0.433 KV transformer complete all as specified and directed. Note: Brass Stud shall be measured and paid separately under relavant item
All as per item No-11here-in-before but for transformer capacity 250-400 KVA,
All as per item No-11 here-in-before but for transformer capacity 500-630 KVA,
M&L for replacement of brass stud suitable for LT 1100 volts grade with con & rubber washer, double Brass nuts & brass washer at both end of stud for Tfr cap 100 KVA to 200 KVA.
All as per item Ser No-14 here-in-before but for transformer capacity 250-500 KVA
Taking out manually defective transformer of capacity 100 KVA to 200 KVA from its position by dismantling LT/HT cables, earthing and earthing strip upto road n. exc 3 KM and transportation by vehicle to workshop n. exc 30 KM and reinstallation at original position after repair or Shiting of transformer from present location to original location including connection of all HT/LT cabes, earthing and earthing strip and testing all as specified and directed. (Note: Rate deemed to included for disconnecting and reconnecting of necessary HT/LT cable/ACSR, earthing connection before and after installation)
All as per items No-16 here-in-before but for transformer capacity 250 to 400 KVA.
All as per items No-16 here-in-before but for transformer capacity 500 to 630 KVA.
M & L for lifting the transformer core carefully after dismantling terminal connections from core to HT/LT bushings, tap changer assy, drainout all oil and keeping in clean container and keeping the heating chamber for necessary value of insulation resistance, dismantling defective HT & LT coils from core for rewinding, and reassembling complete with HT/LT coils to core, required necessary numax paper insulation, insulating press board, precompressed board size of 6mm/3mm/1.5mm/1mm, varnishing, heating to achive insulation level not less than 1000 megaohms at both HT & LT side, core at transformer chamber, tap changer assy, terminal connection, top cover with new cork sheet gusket, required existing/new nuts, bolts & washers, filling transformer oil, testing after repair complete all as specified and directed for the 63 to 200 KVA, 11/0.415 KV transformer. Note:- (i) Opening of top cover, Rewinding of HT/LT coils, transformer oil, nuts, bolts & washers, HT/LT busings, required shall be measured and paid separately under relavant items of the schedule. (ii) Test result shall be kept in record duly signed by all concerned (iii) Testing record will be prepared by contractor.
All as per items No-19 here-in-before but for transformer capacity 250-315 KVA.
All as per items No-19 here-in-before but for transformer capacity 400-630 KVA.
M&L for rewinding of HT coils suitable for 11000 volts grade with new DPC/super enamelled copper wire having Class-F insulation as per existing size and turns for capacity of transformer 63KVA to 630KVA including dismantling and taking down old unserviceable copper wire complete all as specified and directed.
M&L for rewinding of LT coils suitable for 1100 volts grade with new DPC /super enamelled copper strip having Class-F insulation as per existing size and turns for capacity of transformer 63KVA to 630 KVA including dismantling and taking down old unserviceable copper wire complete all as specified and directed.
M&L for replacement of Tap changer assy having 7 position of transformer including dismantling and taking out old unserviceable one and dismantling all winding terminal connections and reconnecting after replecement complete upto transformer cap 630 KVA 11/0.433 KV.
M&L for painting of transformer outer surface installed at various electric sub station/ pump housed, in situ/wksp with one coat of synthetic enamel paint using sprayer for transformer capacity 100KVA to 400 KVA after preparation of old painted surface including writing M/C No. (Note : (i) During process of painting, transformer will be under shut down for the period and the rate deemed to be included for running the sprayer machine with own arrangement by contractor. (ii) After completion of painting HT/LT outdoor bushing, cable termination joint, Oil inspection glass and name plates to be made clean using volatile cleanner)
Supply and fixing copper fuse wire 60 Amp capacity complete all as specified and directed.
S&F in repair HT lightening arrester expulsion type with all fittings discharging capacity 65 KA 11000 volts grade complete all as directed. Make :- Alstom/Oblum/Crompton Greaves.
Construction in replacement of transformer platform size 3mx2mx1m from ground incl XPM jalli fabricated with angle size 50x50x6mm and two coat of aluminum paint over one coat of red oxide incl steps plinth protection and all other relevant works complete all as specified.
Note:- Deduction for Schedule of credit (Sch 'A' Part-II) to be made of ₹ 202385.00 from the total quoted amount of BOQ while accepting the bid. Details of schedule of credit is given in tender documents.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
BOQ_835316.xls
BOQ • 1.31 MB
TENDER.pdf
Tender Documents • 0.88 MB
Download all tender documents and submit your bid