Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹21.5 LAccepted-AOC | L-1 | Accepted-AOC Being L-1 bidder | |
| 2 | L-2₹32.1 L+₹7.2 L (29.1%)Rejected-Finance | L-2 | Rejected-Finance Being other than lowest | |
| 3 | L-3₹32.2 L+₹7.4 L (29.6%)Rejected-Finance | L-3 | Rejected-Finance Being other than lowest | |
| 4 | L-4₹34.3 L+₹9.4 L (37.8%)Rejected-Finance 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L-4 | Rejected-Finance Being other than lowest | |
| 5 | L-5₹38.3 L+₹13.4 L (53.8%)Rejected-Finance | L-5 | Rejected-Finance Being other than lowest |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
26 Jul 2021, 6:00 pmClosed
GE Jammu
GE Jammu c/o 56 APO Pin-180003
REPAIR AND MAINT OF UG CABLES, ACSR CONDUCTOR, POLES, LT DISTRIBUTION SYSTEM, SECURITY/STREET LIGHTS, SOLAR LIGHTS AND CONNECTED WORKS AT DAMANA UNDER GE JAMMU
2021_MES_455576_1
GEJC-23/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AoR of GE Jammu
Please refer Tender Documents
9 documents required · 9 mandatory
₹500
GE Jammu
₹70,000
Yes
3 Sept 2021
29 Jun 2021
28 Jul 2021
29 Jun 2021
26 Jul 2021
13 Jul 2021
Amount
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep in any type of soil getting out and levelling of bottom surface to required level for poles/stay assembly/cable complete all as specified and directed.
M&L for road cutting, PCC hard standing as per site requirement including excavation for laying of GI pipe and making good the disturbed surfaces all as per existing surface complete all as specified and directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exc 25m thick complete all as specified and directed.
Removing excavated material from site to a distance not exc 50mtr away and depositing where directed not exc 1.5mtr from the starting point complete all as specified and directed.
M&L in replacement of GI Pipe light grade 80 mm bore for cable protection as a guard pipe complete all as specified and directed.
M&L in replacment of GI Pipe light grade 50 mm bore for cable protection as a guard pipe complete all as specified and directed.
M&L sub class 'B' bricks well burnt laid with length perpendicular to the axis of the cable in trenches for protection to cable complete all as specified and directed.
Supplying & Laying in trenches Clear Sand for cushioning under ground cable 8 cm below and 15 cm above complete in level complete all as specified and directed.
M&L for PCC 1:3:6 (using 40 mm graded crushed stone aggregate) type C-2 for foundation of pole, stay including frame work where required complete all as specified and directed.
M&L for PCC (1:2:4) type B-I coping with 20 mm graded crushed stone aggregate for poles complete all as specified and directed.
Taking out/down unserviceable, defective cable any type/size including disconnecting all the electrical connections all as required at site complete all as specified and directed.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sq mm, 2 core complete all as specified and directed by Engr-in-Charge. Note: - Wherever cable fixing/connection, suitable thimble should be used as per site situation.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sq mm, 2 core complete all as specified and directed by Engr-in-Charge. Note: Wherever cable fixing/connection, suitable thimble should be used as per site situation.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge. Note: Wherever cable fixing/connection, suitable thimble should be used as per site situation.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge. Note: Wherever cable fixing/connection, suitable thimble should be used as per site situation.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge. Note: Wherever cable fixing/connection, suitable thimble should be used as per site situation.
M&L in replacement of ACSR conductor any size / any type drawn on fixed to insulator on the pole complete as with permissible sags for OH conductor all as specified and directed.
M&L in replacement of Galvanised steel wire 4.0 mm dia for continuous earth wire and cradles hexagonal / rectangular shall be provided and securely fastened to each pole and connected with earth ordinarily and cradle guarding where required complete all as specified and directed.
M&L in replacement of stay assembly complete with all accessories as shown in electrical plate No 1, including loop type insulator and stay clamps, Diameter of stay rod 20 mm complete all as specified and directed. Note: - Excavation and concrete work shall be measured and paid separately.
Supply, erecting and fixing in replacement for Pre stressed concrete pole 9.0 meter long 102mm X 172 mm at Top and 102 mm and 279 mm at bottom class 10 complying with requirement of IS-1678-1978 including painting of poles with two coats of synthetic enamel paint in black and white strip each 30 cm wide each upto 1.5 mtr high from coping over a coat of primer including numbering of poles complete all as specified and directed by Engr-in-Charge.
M&L in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections i.e M.S. channel or angle sections etc. including new nuts, bolts, washers as required dia / length in size, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat of red oxide, one under coat and one finishing coat of silver paint (1st quality) as required complete all as specified and directed.
M&L in replacement of Insulator Shackle type, porcelain, vitreous, white, brown or green, shall be in one piece and shall have a groove on the side and a hole for a cotter pin and two galvanised bolts 12 mm dia and nuts with or without a pair of straps in size 31 x 3 mm as indicated size height 75 mm and dia 90 mm, for working pressure 1100 volts complete all as specified and directed.
M&L in replacement of Insulator Pin type, porcelain, vitreous, white, brown or green including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade, shall be in one piece and have a top groove and shall be threaded to take galvanised mild steel pin complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 240 sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 185 / 120 sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 70/95 sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 25 / 35 / 50 sqmm complete all as specified and directed.
M&L for steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screw as specified type 410 SP-31 (9.00 meters long) including two coats of silver paint over a coat of red oxide primer complete with strip of black and white strips 30 cm of width upto 1.5mtr height from top of coping in as specified and directed including taking out old unserviceable pole any type complete all as specified and directed. Notes:- Excavation and Earth work, concrete work shall be measured and paid separately.
M&L for steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screw as specified type 410 SP-55 (11.00 meters long) including two coats of silver paint over a coat of red oxide primer complete with strip of black and white strips 30 cm of width upto 1.5mtr height from top of coping in as specified and directed including taking out old unserviceable pole any type complete all as specified and directed. Notes:- Excavation and Earth work, concrete work shall be measured and paid separately.
S&F in replacement of insulating rubber matting sheet of size 2m x 1m x 10 mm thick. confirming to ISI electric shock proof of 1100 volt grade complete all as specified and directed.
S&F in replacement of insulating rubber matting sheet of size 2m x 1m x 19 mm thick. confirming to ISI electric shock proof of 11000 volt grade complete all as specified and directed.
Supply, installation, testing and commissioning, replacement of LT panel of suitable size for 3 Phase 415 volt, outdoor weather proof vermin proof duly powder coated double door with back and front opening made out from 3.0 mm thick CRCA sheet with angle iron base frame of size 50 x 50 x 6 mm cubical type complete with aluminium bus bar 600 Amp 4 way with proper color coding complete with PVC insulator, with IP-54 as per IS 13947 protection, fault rating 50 KA/1 sec, complete with following items including :-
Supply, installation, testing and commissioning, replacement of LT panel of suitable size for 3 Phase 415 volt, outdoor weather proof vermin proof duly powder coated double door with back and front opening made out from 3.0 mm thick CRCA sheet with angle iron base frame of size 50 x 50 x 6 mm cubical type complete with aluminium bus bar 800 Amp 4 way with proper color coding complete with PVC insulator, with IP-54 as per IS-13947 protection, fault rating 50 KA/1 sec, complete with following items including :-
M&L for replacement of old burnt out aluminium bus bar and connected link bar with proper colour coding with insulation tape of current rating 630/400 Amps including replacement of old rusted nut and bolts, washers complete all as specified and directed by Engr-in-Charge.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge.
M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 Sq mm, 3.5 core complete all as specified and directed by Engr-in-Charge.
S&F in replacement unsv indicators LED set of three pieces as per existing size and sample complete all as specified and directed by Engr-in-Charge.
S&F in replacement Ampere meter analog type 0-600 Amp CT type with suitable set of size 96 sqmm square type flush panel mounted complete all as specified and directed by Engr-in-Charge.
S&F in replacement of Volt meter analog type 0-500 Volt 96 sqmm square type flush panel mounted complete all as specified and directed by Engr-in-Charge.
M&L for replacement of MCCB 4 Pole, current rating 630 Amp, thermal setting adjustable 70%-100% rapturing capacity 50 kA at 415V, 50Hz complete all as specified and directed by Engr-in-Charge.
M&L in replacement of MCCB 4 Pole, current rating 400 Amp, thermal setting adjustable 70%-100% rapturing breaking capacity 50kA at 415V, 50Hz complete all as specified and directed by Engr-in-Charge.
M&L for in replacement of MCCB 4 Pole, current rating 250 Amp, thermal setting adjustable 70%-100% breaking capacity 36 kA at 415V, 50 Hz complete all as specified and directed by Engr-in-Charge.
M&L for in replacement of MCCB 4 Pole, current rating 200 Amp, thermal setting adjustable 70%-100% breaking capacity 25kA at 415V, 50Hz complete all as specified and directed by Engr-in-Charge.
M&L in replacement of MCCB 4 Pole, current rating 160 Amp, thermal setting adjustable 70%-100% breaking capacity 25kA at 415V, 50Hz complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 100 Amp, 415 volts 3 phase, four pole complete all as specified and directed by Engr-in-Charge.
Supply, fixing, connecting and commissioning and testing in replacement of Company Make (automatic and manual operation) power factor improvement panel of capacity 75 KVAR for 150/160KVA Trasformer including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof (IP-54/IP-42) suitable for 1100 V / 440 V grade 3 phase 50 HZ AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four No's angle iron legs made out of 40 x 40 x 6mm 60 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles, lugs duly painted with L&T grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, all as specified and directed by Engr-in-Charge. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolte, L&T, legrand) will be accepted & factory inspection will be done by GE/AGE at original manufacturer plant onlyand all other electric incoming and outgoing connections with PVC insulated multi stranded flexible copper cable of suitable size and PVC flexible conduit medium quality as required and comprising of the following :-
Incoming Feeder: - (A) Incomer MCCB 125 Amp, Three Pole, Termal based release with adjustable O/L, Adj S/C Setting Class II Front Face, 36KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.Make:- Abb /Schneider/ L&T - 1 No (B) Metering Section- Digital Ammeter (0-150)Amps, digital Volt Meter (0-500) Volts , RYB Indicating Lamps ,1 Set Control fuses, CTs. 3 (C) Insulated Busbar of Aluminium of 150A Capacity for 3 phase, fixed on Insulators, Busbar should be PVC sleeved with red / Yellow / Blue Colour, Busbar support should be of smc/dmc - 1 set. (D) Multi 12 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display.
Outgoing Feeder: - (E) Accessories for 1 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 kvar with Damping resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 6 A having breaking capacity 10 KA with std. duty capacitor, on/off indicators, Start/stop Push button. Make :- Schneider/L&T/ABB (F) Accessories for 2 KVAR Capacitor Bank - 2 No's :- Capacitor Duty Contactor 2 kvar with Damping resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 16 A having breaking capacity 10 KA with std. duty capacitor on/off indicators, Start/stop Push button. Make :- Schneider/L&T/ABB (G) Accessories for 4 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 4 kvar with Damping resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 20 A having breaking capacity 10 KA with std. duty capacitor on/off indicators, Start/stop Push button. Make :- Schneider/L&T/ABB (H) Accessories for 8 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 8 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 16 A having breaking capacity 10 KA with std. duty capacitor on/off indicators, Start/stop Push button. Make :- Schneider/L&T/ABB (I) Accessories for 10 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 10 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 25 A having breaking capacity 10 KA with std. duty capacitor on/off indicators, Start/stop Push button. Make :- Schneider/L&T/ABB (J) Accessories for 15 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 15 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 32 A having breaking capacity 10 KA with std. duty capacitor on/off indicators, Start/stop Push button. Make :- Schneider/L&T/ABB (K) Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm,160cu.m/h flying leads.
(L) Automatic Power Factor controller steps Relay Micro proccessor based for switchting ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and excess temperature. The relay having volt free c/o contact, automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching programm : LIFO combi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt, 45 to 65 HZ, current measuring 10MA-5A suitable for CT x/1A and x/5A commissioning without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank Automatically. Make:Schnider/ Minitex/ C&S. (M) All accessories prewired with suitable size copper wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door openable with locking arrangement complete with foundation as required or recommended by manufacturer. Make of APFC Panel: confirming to Make Tricolite, dvepl,Legrand, L&T. Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolite, L&T, legrand) will be accepted & factory inspection will be done by GE/AGE at original manufacturer plant only.
M&L in replacement of PVC insulated and sheathed cable of size 1.5 sqmm 3 core aluminium conductor multistranded 1100 volt grade 230 volts complete all as specified and directed by Engr-in-Charge.
M&L for LT underground cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade cross-sectional area 10 Sq mm, 4 core complete all as specified and directed.
S&F fabrication street light bracket made out of GI tubing suitable for 45/60/90 watt LED light grade upto 1.2 mtr length, bend to shape suitable for security light fitting with necessary MS clamps with one coat of red oxide and two coats of aluminium paint including nut, bolt, washers etc and including taking out unserviceable bracket and removing from site of work complete all as specified and directed.
Labour for repair/maint to Old/Unserviceable LED security/Street/flood light of any capacity including taking down existing fitting from pole/Bldg for replacement of unsv driver, cable terminal block and connection wire and refixing the same in position after repair including testing complete all as specified and directed. Note: Spares shall be measured and paid seperately under respective item.
Taking down old unserviceable LED Street/Security light/flood light fitting of any type from the pole/bldg after disconnecting electric connection carefully complete all as specified and directed. Note: Repair/replacement of spares shall be measured separately.
Supply and fixing in replacement of electronic driver of cap 45 watt of existing make for LED street light fitting complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 60 watt of existing make for LED street light fitting complete all as directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 90 watt of existing make for LED street light fitting complete all as directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 120 watt of existing make for LED street light fitting complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 200 watt of existing make for LED Flood light fitting complete all as specified and directed by Engr-in-Charge.
S&F energy saving LED street light fitting 120 watt comprising a single piece, environment friendly light fittings including electrinic driver, luminarie housing is of pressure die-cast alluminum alloy LM-24 for gear and extruded aluminium lamp housing, operating voltage range is from 85 Volts to 264 Volts AC 50 Hz complete all as specified and directed.
S&F energy saving LED street light fitting 90 watt comprising a single piece, environment friendly light fittings including electrinic driver, luminarie housing is of pressure die-cast alluminum alloy LM-24 for gear and extruded aluminium lamp housing, operating voltage range is from 85 Volts to 264 Volts AC 50 Hz complete all as specified and directed.
S&F energy saving LED street light fitting 60 watt comprising a single piece, environment friendly light fittings including electrinic driver, luminarie housing is of pressure die-cast alluminum alloy LM-24 for gear and extruded aluminium lamp housing, operating voltage range is from 85 Volts to 264 Volts AC 50 Hz complete all as specified and directed.
S&F energy saving LED street light fitting 45 watt comprising a single piece, environment friendly light fittings including electrinic driver, luminarie housing is of pressure die-cast alluminum alloy LM-24 for gear and extruded aluminium lamp housing, operating voltage range is from 85 Volts to 264 Volts AC 50 Hz complete all as specified and directed.
S&F LED flood light fitting of cap 200 watt including inbuilt surge protection as per requirement LED flood light fittngs along with IP-65 protection complete all as specified and directed.
S&F in replacement distribution board with supply and fix time switches astro type (having longitude and latitude of Indian cities in memory) 250 V single phase of 20 Amp rating with contactor fitted inside steel enclosure complete all as specified and directed.
S&F in replacement of SMC Pole mounted box of size 250 x 200 x 100 mm with hinged door including clamp, nuts, bolts and washers complete all as specified and directed and including following accessories: (a) MCB SP 10 Amp, 10 kA 'C' Series mounted on din rail-1 No. (b) Connector block suitable for 3ph, 4 wire min 10 sqmm cable-1 No.
BMMJ TRADERS AND ENGINEERS
M/S SHREE KRISHANA ENERPRISES
kailu construction co
M/S S K Electricals Regd
Dn construction and co
M/s. Aggarwal Engineers
vishesh engineers
SATISH AND CO
Bidder Name
kailu construction co
M/S S K Electricals Regd
SATISH AND CO
BMMJ TRADERS AND ENGINEERS
Sarbat Construction Co
Dn construction and co
M/s. Aggarwal Engineers
M/S SHREE KRISHANA ENERPRISES
vishesh engineers
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .