Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹66.8 LAccepted-AOC OPP FCI GODOWN MAKUM ROAD DIST TINSUKIA ASSAM PIN 786125 | TINSUKIA | ASSAM | 786125 | L1 | Accepted-AOC Lowest and Reasonable | |
| 2 | L2₹72.9 L+₹6.0 L (8.96%)Rejected-Finance NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L2 | Rejected-Finance Other than Reasonable |
Tender Value
Refer Docs
EMD Value
₹1.3 L
Closing Date
21 Jun 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) JORHAT
HQ CWE (AF) JORHAT, ROWRIAH, ASSAM-785005
AUGUMENTATION OF ELECTRIC SUPPLY TO OPS AND TECH BUILDING AT AF STN MOHANBARI UNDER GE (AF) MOHANBARI
2021_MES_432415_3
83914/E8
Open Tender
Civil Works
Item Rate
240 days
GE (AF) MOHANBARI
Please refer tender documents
5 documents required · 5 mandatory
₹1,000
Yes
GE (AF) MOHANBARI
₹1.3 L
Yes
18 Aug 2021
1 Jun 2021
26 Jun 2021
1 Jun 2021
21 Jun 2021
8 Jun 2021
60 days
Amount
Supply, installation, testing and commissioning including transportation at site trasformer step down outdoor type copper wound of capacity 400 KVA, 11 KV on HT side and / 433 volts on LT side at no load, 3 phase 4 wire 50Hz AC supply oil immersed, naturally cooled with external cooling tubes delta connected on HT side and star connected on LT side, corresponding to vector group DY-II with neutral brought out separately for earthing off load tap changing arrangements on HT side to vary secondary voltage (+) or (-)7.5% in steps of (+) or (-) 2.5%, oil filled conforming to IS complete on stone masonry platform as per manufacturer recommendations complete with standard fittings conforming to IS-1180 (Level III) and with ECB Closses or latest IS complete all as specified and as directed. (NOTE:-Rate quoted shall be inclusive of making standard platform for transformer)
Supply, installation, testing and commissioning including transportation at site trasformer step down outdoor type copper wound of capacity 250 KVA, 11 KV on HT side and / 433 volts on LT side at no load, 3 phase 4 wire 50Hz AC supply oil immersed, naturally cooled with external cooling tubes delta connected on HT side and star connected on LT side, corresponding to vector group DY-II with neutral brought out separately for earthing off load tap changing arrangements on HT side to vary secondary voltage (+) or (-)7.5% in steps of (+) or (-) 2.5%, oil filled conforming to IS complete on stone masonry platform as per manufacturer recommendations complete with standard fittings conforming to IS-1180 (Level III) and with ECB Closses or latest IS complete all as specified and as directed. (NOTE:-Rate quoted shall be inclusive of making standard platform for transformer)
Supply and fix for voltage stablizer for automatic operation, three phase naturally oil cooled, inddor type & designed for input variation between 300 Volts to 460 Volts with output voltage stablized at 415 with accuracy + 2.5% and speed of correction 8 Volts per second and capacity of 250 KVA complete all as specified and as directed.
Supply and fix for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and as directed.
Supply and fix for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed.
Supply and fix for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and as directed.
Supply and laying for HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 3 Core 95 Sqmm complete all as specified and as directed.
Supply, laying and testing for cable LT XLPE insulated, screened, PVC bedded, galvanished steel strip or wire armoured, electric cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 Sqmm 3.5 core all as specified and as directed.
Supply, laying and testing cable LT XLPE insulated, screened, PVC bedded, galvanished steel strip or wire armoured, electric cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core all as specified and directed.
Supply, laying and testing cable LT XLPE insulated, screened, PVC bedded, galvanished steel strip or wire armoured, electric cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core complete all as specified and as directed.
Supply, laying & testing cable LT XLPE insulated, screened, PVC bedded, galvanished steel strip or wire armoured, electric cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 185 Sqmm 3.5 core all as specified and directed.
Supply, laying and testing cable LT XLPE insulated, screened, PVC bedded, galvanished steel strip or wire armoured, electric cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 240 Sqmm 3.5 core complete all as specified and as directed.
Material and labour for danger notice plate of size 1.6mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skul and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT 11KV, 25x20 cm size complete all as specified and as directed.
Supplying, installation, testing and commissioning of RMU (1LBS + 3 VCB) extendible HT 11 KV outdoor type 21KA for 3 sec, rated voltage -12KV, operation voltage 11 KV, rated lightening withstand voltage -75KV, rated frequency 50Hz, 630 amp copper bus bar, SF6 insulated compact switch gear, welded stainless steel enclosure with minimum 2.5 mm thickness, totally enclosed Ring Main Unit IP-67 protection for SF6 Tank and IP 55 protection for outdoor enclosure with self powered microprocessor based complete numerical over current & earth fault relay with specification/ equipment with power backup 24 volts DC complete with all accessories comprising of following (1 LBS + 3VCB) + M configuration and makes as specified in ps:- (a) Fixed motorised Vacuum circuit breaker (VCB) - 3 Nos , FR1 – VI 13, 12kV, 630A, 21 KA, fixed type 1 Ring Switch, 3 Vacuum Circuit Breaker ( Stainless Steel Tank) unit insulated in SF6 media as per latest IEC 62271-200 shall be comprising of the following for each set:- (i) Assembly of VCB interrupter complete with epoxy support insulator and self aligning isolating contacts with rating 11 KV, 630 Amp, 21 KA for 3 sec, 50 Hz. (ii) Manual charged and manual operated independent closing/ tripping, trip free operating mechanism and breaker closed/ open spring charged/ discharge indication. (iii) Mechanical operation counter- 01 No (iv) One bus bar chamber including a set of 3 phase 630 Amps copper bus bar. (v) Strip heater 230 volts AC single phase 80 watt. (vi) 3 0/C + 1 E/F self powered numerical protection relay with low and high set for over current and earth fault. Relay should have facility to display the maximum loaded phase current also. Relay shall record minimum 5 fault record with time stamping. (vii) One No potential transformer (PT) three phase, dry type(resin cast) draw out type 11 KV/110 volts, 25 VA burden, accuracy class 0.5 with HT & LT HRC fuses for primary and secondary complete as per conforming to IS-3156-01. (viii) Current transformer chamber comprising of 3 Nos single phase resin cast CTs of 100-50/5 and accuracy class 0.5 for metering and class 5P 10 for protection, burden 2.5 VA in VCB feeder- set of 3. (ix) Digital SCADA compatible (for future integration) intelligent panel meter indicating line/ phase current, line/ phase voltage, power factor, KVAR, KVA, frequency etc with accuracy class 0.5 – 1 No. (b) Fixed motorised load break switches (LBS)- 01 (one) Nos
Material and labour for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less then 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel and connected to main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm, reinforced with 8 mm dia TMT bars @ 15 cm c/c both ways and one handle for lifting made out of 10mm dia MS bar, funnel, wire mesh, 20 mm bore galvanized steel tubing (medium grade) for watering, filling charcoal or coke and salt in alternate layers, 40mm bore galvanized steel tubing light grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown on electrical plate No.3 of SSR Part-I . (Note: GI earth strip and protection pipe upto 7.5metres shall be deemed to be included in quoted rate)
Supply, installation, testing and commissioning of maintenance free chemical earthing system complete with 03 (three) Nos copper bonded rods 17.2mm dia 3000 mm long electrode burried at suitable distance apart directly in ground to bore holes of 120 mm dia vertically to a depth not less than 3.6 metres deep below ground level with top edge of earth electrode at a depth not less than 100 mm below normal ground level provision of clamps or brazed or both for each copper bonded rods made of copper and copper strip of size 20 mm X 3 mm for interconnection of three Nos copper bonded rods and laying atleast 500 mm below in the ground and further connected to test point terminal block including back filling of bore holes with advanced earth enhenching compound 96 Kg (minimum) for artificial treatment to soil so as to achieve earth resistance below 01 Ohm as specified in Para 19.140 of SSR Part-I (2009) including three coats of white wash on plastered / PCC surface (exposed surface) and testing. NOTE :- (i) The unit rate also inclusive of excavation, earth work in any type of strata, Pit of PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab of 450 mm x 450 mm x 50 mm reinforced with 8 mm dia TMT bars @ 150 mm C/C both ways and one handle for lifting made out of 12 mm dia MS round bar complete in addition to item No.1(a) to (e) of preamble (notes) under sub-heading earthing specified in SSR Part-II. (ii) All joints are with nuts and bolts as well as brazing. (iii) If the desired earth resistance is not achieve during testing as per IS, the complete earthing shall be carried out by the contractor at his own cost and no exta claim shall be admissible.
Supply and fix for 32x6 mm size galvanised iron or steel strips earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc. complete all as specified and as directed.
Supply and fix for cable route indicator made out of cast iron suitable size supported on angle iron embeded in PCC (1:4:8) type D2 with engraved size of cable and direction of route complete all as specified and as directed.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc. for taking out pipe line for repairs/ laying cables etc. and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick with soils complete all as specified and as directed.
Removing of excavated material (soil) to distance not exceeding 50metre and deposited where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed.
Material and labour for dry river sand as in sand cushioning in trenches/ ducts for protection of underground cable (below, above and around the UG cable laid in trenches) of 23 cm spread thickness ( 8 cm in depth before laying the cable and 15 cm in depth after laying the cable) and consolidated (punned) up to 18 cm thickness complete all as specified and as directed. Note : - Thickness after punning shall be measured for payment
Supply and fix for 80 mm bore GI tubing light grade in trenches or on pole for cable protection complete all as specified and as directed.
Supply and fix for 50 mm bore GI tubing light grade in trenches or on pole for cable protection complete all as specified and as directed.
Supply and fix for 40 mm bore GI tubing light grade in trenches or on pole for cable protection complete all as specified and as directed.
Supply and laying for un-reinforced precast concrete cable cover, class HVP type 2 with peak size 450mm x 180mm x 40mm complete all as specified and as directed.
Material and labour for sub class 'B', old size bricks for cable protection cover, common burnt clay building bricks, laid dry and flat abutting each other with width equal to length of brick and gap between adjacent bricks not exc.10mm complete all as specified and as directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed..
PURBANCHAL BUILDERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .