Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance GAYATRI HOUSE OPP GOYAL INTERCITY ROW HOUSE DRIVE IN ROAD THALTEJ AHMEDABAD GUJARAT 380054 | AHMADABAD | GUJARAT | 380054 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Rejected-Technical B 814 8TH FLOOR B G TOWER OPP DELHI GATE SHAHIBAUG ROAD AHMEDABAD 380004 | AHMADABAD | GUJARAT | 380004 | Rejected-Technical Not Elegible |
| 5 | Rejected-Technical | Rejected-Technical Not Eligible |
Tender Value
₹48.2 L
Closing Date
2 Mar 2021, 11:00 amClosed
Chief Engineer
Office of the Chief Engineer, ESTATE ( EM), Head Office, 1st Floor, Old Building,
Supply erection testing and commissioning of 33 kV Vacuum Circuit Breaker (VCB) as RMU in the proposed 33 kV indoor Sub-station at IIT Kharagpur considering 33 kV double feeder line source from the WBSEDCL, Hijli 132 kV Sub-station.
2021_IITKG_613852_1
IIT/E/EM/T/30/2020-21
Open Tender
Electrical Works
Item Rate
120 days
IIT Kharagpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
Exempted
ESTATE ( EaM), Head Office, 1st Floor, Old Buildin
16 Mar 2021
3 Feb 2021
3 Mar 2021
3 Feb 2021
2 Mar 2021
3 Feb 2021
18 Feb 2021
Amount
Supply, erection, testing and commissioning of Four panel (2-in + 1-Out + 1-Bus PT), indoor, motorized 36 kV vacuum circuit breaker along with other equipment/accessories with RMU facilities of the following feature: a) The panel unit should have 33kV, 3 pole, 50 Hz, 1600 Amps, 750 MVA, symmetrical breaking capacity 25 KA for 3 sec, single phase motor operated along with manual spring charging system. b) The DC supply for control circuit should be through 110 Volt DC of the existing sub-station. c) All the panels should have Intelligent multifunctional meters with RS 485 communication port facilities. d) The RMU should have horizontal draw out type PT unit having 33 kV/110 Volt, 3phase, 4 wire, 50hz, bus-bar connected resin cast PT. e) The C.Ts should be dual core type with ratio 400-200/5+5 amp for metering and protection with the relevant class as per IS. for each panel f) The panels should have microprocessor based E/F & O/C IDMT Relays. g) One no earthing Trolley (For details please see ANX IV attached herewith) Make: ABB / Siemens and equivalent approved by the Site in-charge. Warranty: Two years from the date of successful commissioning at site.
Calcutta Power Construction Co.
GAYATRI PRIVATE LIMITED
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .