Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 CrAccepted-AOC | ₹1.8 Cr | L1 | Accepted-AOC Reasonable |
| 2 | L2₹2.5 Cr+₹62.0 L (33.7%)Rejected-Finance | ₹2.5 Cr+₹62.0 L (33.7%) | L2 | Rejected-Finance Rates on higher side |
| 3 | Rejected-Technical | - | - | Rejected-Technical Criteria not fulfilled being two class below |
Tender Value
₹1.9 Cr
EMD Value
₹2.7 L
Closing Date
9 Dec 2019, 6:00 pmClosed
CWE AF PANAGARH
HQ CWE AF PANAGARH MILITARY ENGINEER SERVICES AIR FORCE STATION ARJAN SINGH PO BIRUDIAH DIST BURDWAN WEST BENGAL PIN 713148
PROVISION OF REFUELING SECTION AND ALLIED WORKS AT AIRFORCE STATION PANAGARH.
2019_MES_257742_2
82269/PAN/E8
Open Tender
Miscellaneous Works
Lump-sum
365 days
CWE AF PANAGARH
Please refer tender documents
8 documents required · 8 mandatory
₹1,000
GE (AF) PANAGARH
₹2.7 L
Yes
26 Feb 2020
13 Sept 2019
11 Dec 2019
13 Sept 2019
9 Dec 2019
17 Oct 2019
13 Sept 2019 - 5 Oct 2019
Amount
Sch 'A' Part-I (Building and Construction work)
SCHEDULE 'A' PART-I (BUILDING WORK) Construction of Adm-cum-Laboratory Building, Single Storey, RCC Framed Structure complete all as specified and as shown on drawings.
SCHEDULE 'A' PART-I (BUILDING WORK) Construction of Garages including Repair Bay for specialized vehicle Building, Single Storey, RCC Framed Structure complete all as specified and as shown on drawings.
Total Amount of Sch 'A' Part-I(A)(CONSTRUCTION OF SHED) Prepriced amount B/F from Sl page No.
Total Amount of Sch 'A' Part-II (INTERNAL WATER SUPPLY) Prepriced amount B/F from Sl page No. ( 22 )
Total Amount of Sch 'A' Part-III (INTERNAL ELECTRIFICATION) Prepriced amount B/F from Sl page No. No. ( 25 )
Total Amount of Sch 'A' Part-IV (SEWAGE DISPOSAL) Prepriced amount B/F from Sl page No. No. ( 29 )
Total Amount of Sch 'A' Part-V (AREA DRAINAGE) Prepriced amount B/F from Sl page No. No. ( 31)
Total Amount of Sch 'A' Part-VI (ROAD /PATH/CULVERT/ HARDSTANDING) Prepriced amount B/F from Sl page No. No. (35)
Total Amount of Sch 'A' Part-VII (FLAME PROOF WIRING) Prepriced amount B/F from Sl page No.No. ( 36 )
Total Amount of Sch 'A' Part-VIII (COMPOUND WALL, FENCING & GATE) Prepriced amount B/F from Sl page No. No. ( 39 )
Total Amount of Sch 'A' Part-IX (EXTERNAL WATER SUPPLY) Prepriced amount B/F from Sl page No. No. ( 41 )
Total Amount of Sch 'A' Part-X(EXTERNAL ELECTRIFICATION WORKS) Prepriced amount B/F from Sl page No. No. (43)
Total Amount of Sch 'A' Part-XI(LIGHTNING PROTECTION) Prepriced amount B/F from Sl page No. No. (44)
Sch 'A' Part-V (Misc Items) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.5 signifies this fact only.
S&F Building security LED luminaire 45 watt including lamp, aluminium pressure die-cast housing, with heat resistant toughened glass cover, IP 65 protection, suitable for mounting on 40mm or 50mm dia. G.I. pipe(medium grade) bracket arms with 2 Nos 40 x 6mm MS flat iron clamps with necessary bolts, nuts and washers, including making necessary electric connection to the luminaire with flexible cord copper 3 core of size 23/ 0.0076 complete all as specified and directed by Engineer-in-Charge (Make: Bajaj Cat No, BRTFG 45W LED or its equivalent model in Crompton Greaves/Wipro/Havells/C&S Electric).
Supply and fix LED tube light fitting 18 watt on wall/surface complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size all as specified and directed by Engineer-in-Charge. (Make : Crompton Greaves Model Slim Ray 18-Watt LED Tube Light (Cool Day Light)/Philips Slimline 18-Watt LED Batten/Havells 18W LED E-Lite Tube Light Cat Part No LHEXBLP7IN1W018 / equivalent model in Bajaj//Wipro)
M&L fluorescent tube light fitting, flameproof type, 2x20 watt LED, die -cast aluminium housingfor gas/vapour group IIA & IIB & zone 1 & 2, IP 65 protected complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor with suitable size all as specified and as directed by the Engineer-in-Charge. (Make : Crompton Greaves/Philips/GE/ Bajaj/Wipro)
S&F thermo-plastic junction box of size 200 mm x 160 mm x 98 mm ,IP 6 ,with locking arrangement and necessary mounting arrangement on pole with M.S. clamps, bolts, nuts and washers of suitable size, including one No SP MCB of suitable capacity and PVC connector for cable termination complete all as specified and as directed (Make: Hensel/ Legrand/Sintex/ABB/Schneider)
S&F junction box/terminal box made of polycarbonate material of size 139mm x 119mm x 70mm, IP 66, suitable for fixing test points complete all as specified and directed by Engineer-in-Charge. (Make: Hensel/Legrand/Sintex/ABB/Schneider)
S&F Gong bell, single phase, 220/250 Volts, 15cm size complete all as specified and directed by Engineer-in-Charge.
S&F Fire extinguisher Carbon di-oxide type (portable), in 4.5 Kg capacity steel cylinder, IS :15683- 2006 marked (amended upto date) complete all as specified and directed by Engineer-in-Charge.
S&F Fire extinguisher Mechanical Foam type (portable), 9.00 litres capacity in steel cylinder , IS :15683- 2006 marked(amended upto date) complete all as specified and directed by Engineer-in-Charge.
S&F Fire extinguisher Dry Chemical Powder type (portable), 4.0 Kg capacity in steel cylinder , IS :15683- 2006 marked(amended upto date) complete all as specified and directed by Engineer-in-Charge.
S&F Fire Buckets with stand , size 3.5 ft (H) x 3 ft(W), having 02 Nos bucket holding capacity, fabricated from 18-20 gauge M.S. sheet, painted outside in Fire Red colour and inside in white colour and marked with the word 'FIRE' in bold black letters.on the outside of the bucket of 9 litres capacity complete all as specified and directed by Engineer-in-Charge.
Supply, installation, testing and commissioning LT distribution panel board (CPRI tested), outdoor, cubical type, floor mounted, factory made out of 40mmx40mmx6mm angle iron frame and 3.15mm CRCA steel sheet side covers with front and back hinged doors with neoprene rubber gasket to make it weather, dust and vermin proof,with proper locking arrangement, epoxy powder coated inside & outside,with danger notice plate, earthing strip point and bottom detachable gland plates complete with suitable size Zinc chromium plated bolts, nuts, washers etc having control unit diagram with PVC insulated colour codes sleeves, mounted on porcelain insulators solid copper conductor 1.5 sq. mm cable for easy identification including incoming/outgoing cable holes at bottom and bottom 'C' channel with 200 Amp capacity Aluminium bus-bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system , including wiring with suitable size of copper cable complete with the following incoming and outgoing switchgears and accessories all as specified and directed by the Engineer-in-Charge. (Note: LT panel board shall be mounted on PCC 1:2:4, type B-1 (using 20mm graded stone aggregate) foundation block of suitable size up to 40cm above ground level as directed. The cost of the PCC block shall be deemed to be included in the unit rate quoted for the item ) :- (A) INCOMING :- (a) MCCB, 4 Pole, 100 Amp, 415 volts, AC, 50 Hz, 25 kA breaking capacity - 01 No.
Supply , Installation , commissioning and testing hi-wall split air conditioner(outdoor & indoor unit), electric driven, single phase, AC, 220 volts complete with cordless remote control unit, acaro bacterium, anti-dust, anti-fungal, IR control with smart phone, LED display, self diagnosis, silver ion and with in-built air ioniser and plasma filter for better indoor quality with R410A refrigerant minimum 3 star rating and EER 3.2 of capacity 2.0TR complete all as specified and directed by the Engineer-in-Charge. (Notes: Cost of angle iron bracket for mounting outdoor unit shall be deemed to be included in the unit rate)
Supply, installation, commissioning & testing of water cooler, partiallly stainless steel, electric driven, single phase having 40 litres storage capacity and 40 litres/hour nominal cooling capacity complete all as specified and directed by Engineer-in-Charge. (Make: Voltas/Blue Star/Carrier/Usha)
Supply and fixing voltage stabilizer for automatic operation, single phase naturally aircooled, indoor type and designed for input variation between 170 V to 250 V with out-put voltage stabilized at 230 V with accuracy of + 2.5 % and of capacity 2 KVA (not less than 8 Amps) complete all as specified and as directed.
Supply and fixing voltage stabilizer for automatic operation, single phase naturally aircooled, indoor type and designed for input variation between 170 V to 250 V with out-put voltage stabilized at 230 V with accuracy of + 2.5 % and of capacity 5 KVA complete all as specified and as directed.
Supply and fixing flame proof DB TPN 4 Way 415 volt, 63 Amps for bowser shed with following items: (a) MCCB 63 Amps 4 Pole - 01 Nos. (b) MCB SPN 32 Amps - 03 Nos. (c) MCB SP 16 Amps - 06 Nos.
Supply & fixing /hanging ceiling fan, 1200 mm sweep size, 230 volts, AC, 50 Hz, single phase including provisioning of cord flexible copper 3 core of size 23/ 0.0076 of required length not exceeding 1.5 metre from ceiling rose or connector to ceiling fan for giving electric connection complete all as specified and directed by Engineer-in-Charge.
Supply & fixing exhaust fan with louver shutter, turbo force, 300 mm sweep size or dia., 1400 RPM, BEE 4 star rated suitable for operation on 240 volts, AC, 50 Hz, single phase electric supply with necessary bolts (6 inches long, 6 mm dia.) with nuts and washers for fixing the fan in wall including making necessary electric connection from ceiling rose to the fan with flexible cord copper 3 core of size 23/ 0.0076 complete all as specified and directed.(Make: Havells, Model:Turbo Force or its equivalent in Crompton Greaves/Khaitan/Bajaj)
S&F MCB, Triple Pole & Neutral, 40 Amp, 240 volts, AC, 50 Hz, 10 kA breaking capacity with 40 Amps MCB SPN attached all as specified and directed by Engineer-in-Charge.
S&F MCB, Single Pole, 6-32 Amp, 240 volts, AC, 50 Hz, 10 kA breaking capacity (C-curve characteristics) all as specified and directed by Engineer-in-Charge.
M&L for Earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground, earth pit not less than 2.25 meters deep below ground level with top edge of the plate not less than 1.5 m below normal ground level , connected to GI Wire 4mm dia as earthing lead by means of bolts, nuts,check nuts and washers complete all as shown in Electrical Plate No 3 of MES Schedule Part-I and connected to earthing test point, including excavation & earthwork in any type of soil, PCC 1:2:4, type B-1 pit/chamber, 50 mm thick pre-cast RCC 1:2:4, type B-1 cover reinforced with hard drawn steel wire fabric weighing not less than 4 kg/sqm, GI sheet funnel with 20 mm bore GI watering pipe (medium grade),15 mm bore GI protection pipe (light grade) , wire mesh and testing on completion all as specified and as directed.(Note: GI wire earthing lead along with protection pipe upto 7.5 m length shall be deemed to be included in the cost of the item)
S&F MCB distribution board, tripple pole and neutral, 63 Amps, 16 kA, vertical type, 4 way, double door, made out of 18SWG CRCA steel sheet, phosphatised powder coated with copper bus bar, Earth stud, Din Rail, terminal blocks for incoming and outgoing circuits, duly pre-wired , 415 volts with 200 Amps rated bus bar, wall mounting type with 63 Amps 4 pole MCCB complete all as specified and directed by Engineer-in-Charge. (Make: Havells LOAD LINE MCB DB Cat No DHDPTVODRW04 or its equivalent model in other makes specified in the tender).
M & L earthing complete with galvanised steel earth plate electrode of size 60 cm x 60 cm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 metre deep below GL with top edge of the earth plate not less than 1.5 metre below normal GL surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanised steel earth lead strip 32mm x 6mm upto 7.5m length by means of bolts, nuts , check nuts and washers of galvanised iron or steel and protected by light grade 40 mm bore GI pipe connected to main switch board or main control board and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh , 80 mm thick RCC 1:2:4, type B-1(using 20 mm graded stone aggregate) pit cover and PCC chamber/ pit with PCC 1:3:6 type C-1 (using 20 mm grade stone aggregate) including excavation and earth work in any type of soil, returning , filling in soil and disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in Electrical Plate No 3 of MES Schedule Part-I (Note: PCC chamber shall be constructed at least 0.5 mtr away from the earth pit and not just on the earth pit itself and extra cost of additional length of water pipe and fitting shall be deemed to be included in the unit rate).
Supply & Fixing LED street light fitting , 72 watt, complete with all accessories comprising of pressure die-cast aluminium housing , heat resistant toughened glass with frame & plastic cover of highly transparent, clear acrylic material fixed to canopy by spring loaded hooks, IP 66 protection, fixed on pole on GI pipe bracket arm with pole fixing attachment complete all as specified and as directed. (Note:GI pipe bracket arm with pole fixing attachment payable seperately)
M&L earthing complete with copper earth plate electrode 30cmx30cmx3.15mm thick buried directly in ground vertically at a depth not less than 2.25m below normal ground level with top level of earth plate at depth not less than 1.5m below normal ground level surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using copper strip 25mm x 3 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel and protected by GI pipe light grade 50mm bore connected to main switch board or main control board and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, 80 mm thick pre-cast RCC 1:2:4, type B-1 cover reinforced with hard drawn steel wire fabric weighing not less than 4 kg/sq. m in lieu of CI cover, PCC1:3:6 type C2 pit/chamber including all necessary excavation and earth work, disposal of surplus soil to a distance not exceeding 50m all as specified and as shown in Electrical Plate No. 5 of MES Schedule Part-I. (Notes: (i) The unit rate shall deemed to include for Test point, copper strip from top of the earth plate and GI protection pipe up to 7.5m above ground level. In case GI protection pipe required is less than 7.5m, no price adjustment shall be made. (ii) PCC pit shall be provided at least 500 mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fittings, junctions, elbow etc shall be deemed to be included in the unit rate.
FRIENDS CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .