Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.9 CrAdmitted-Finance | ₹4.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹7.5 CrAdmitted-Finance CITIZEN INDUSTRIES PLOT NO 57 PHASE II GIDC ESTATE NARODA AHMEDABAD GUJARAT 382330 UDYAM GJ 01 0027986 24AAVPM5024D1ZS R M 29AAVPM5024D1ZI M MII STATUS AS VERIFIED | AHMADABAD | GUJARAT | 382330 | ₹7.5 Cr | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Citizen Industries L2 | CGMP Projects Pvt. Ltd L1 |
|---|---|---|---|---|---|
| 1.00SINGLE STAGE PACKED BED VERTICAL WET SCRUBBER. | |||||
| 1.00Supply, Installation, Testing and Commissioning of Single stage, Vertical Wet Scrubber with integrated liquid tank. - Airflow : As mentioned below for individual Scrubbers - Temperature: 70 Deg C (max.). - Pressure drop 100 mm WG (approx.). - Material: PP+FRP with Isophthalic resin. - Scrubber Sink height not less than 750mm. Complete makeup water connection, 5" Float valve, 12mm x 1000 mm Glass water level indicator, drain & over flow pipe connections with required valves. - Scrubber recirculation pump with Mechanical seal coupled with suitable IP-55, 3 Phase, 50 Hz, motor with rain protection of PP+FRP guard. Inlet flange connection with valve and 'Y' Strainer with brass filter. Outlet flange connection with non return (NRV) valve with gaskets & bolt nuts. - Scrubber Inlet collar with 15 Deg inclination towards down at shell inside. - 12mm Perforated sheet with 35mm hole diameter and total open area is not less than 66% of perforated sheet area. - Single stage packing material consists of 50mm PP pal rings filled upto 750 mm Height. - One Set of liquid spray nozzle system with equal space matrix not less than 300mm. - Circular 3 pass PVC mist eliminator secured with 6 number mounting bolts mounted on lugs / circular ring. - Acylic/ White PP dosing tank 500 mm Diameter x 500 mm Height with lead & handle and supported with galvanised MS support stand and with12mm Pipe connection to the scrubber with control valve for manual dosing. - MS Ladder with 5mm Thick maintenace platform, finished with Chlorinated rubber paint and attached to the scrubber shell near the view port / window. - 5mm Thick acrylic Inspection and maintenance door /window between packing material & mist eleminator zone. - 0-500mm U-Tube manometer acorss inlet & outlet collars with transparent connecting tubes. - Mounting Bolt & Nuts with Anti Vibration Pads. | |||||
| 1.00Location: 99B 1F | |||||
| 1.00 | Cluster EEC (cluster ) : 1 Capacity - not less than 500 CFM & Diameter 450 mm
Type of Scrubber - Packed Bed Vertical Scrubber .
Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin
Packing Ht. - 750 mm
Packing Type - PP Pall Ring of 2" Dia.
PP Vertical Pump ( Coupled Drive )
Pump Motor - Matching Capacity of TEFC 2900 RPM | 1 | No. | 3,62,530 ₹3.6 L | 3,41,318 ₹3.4 L |
| 1.00Location: 99B 2F | |||||
| 1.01 | Cluster EEC : 1 Capacity - not less than 5,027 CFM & Diameter 1200 mm
Type of Scrubber - Packed Bed Vertical Scrubber .
Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin
Packing Ht. - 750 mm
Packing Type - PP Pall Ring of 2" Dia.
PP Vertical Pump ( Coupled Drive )
Pump Motor - Matching Capacity of TEFC 2900 RPM | 1 | No. | 6,52,740 ₹6.5 L | 5,67,422 ₹5.7 L |
| 1.01 | Cluster EEC : 2 Capacity - not less than 11,831 CFM & Diameter 1800 mm
Type of Scrubber - Packed Bed Vertical Scrubber .
Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin
Packing Ht. - 750 mm
Packing Type - PP Pall Ring of 2" Dia.
PP Vertical Pump ( Coupled Drive )
Pump Motor - Matching Capacity of TEFC 2900 RPM | 1 | No. | 8,88,320 ₹8.9 L | 7,65,938 ₹7.7 L |
| 1.01 | Cluster EEC : 3 Capacity - not less than 12,200 CFM & Diameter 1800 mm
Type of Scrubber - Packed Bed Vertical Scrubber .
Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin
Packing Ht. - 750 mm
Packing Type - PP Pall Ring of 2" Dia.
PP Vertical Pump ( Coupled Drive )
Pump Motor - Matching Capacity of TEFC 2900 RPM | 1 | No. | 8,88,320 ₹8.9 L | 7,65,938 ₹7.7 L |
| 1.01 | Cluster EEC : 4 Capacity - not less than 2,866 CFM & Diameter 900 mm
Type of Scrubber - Packed Bed Vertical Scrubber .
Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin
Packing Ht. - 750 mm
Packing Type - PP Pall Ring of 2" Dia.
PP Vertical Pump ( Coupled Drive )
Pump Motor - Matching Capacity of TEFC 2900 RPM | 1 | No. | 4,96,230 ₹5.0 L | 4,54,547 ₹4.5 L |
| 1.01 | Cluster EEC : 5 Capacity - not less than 9,670 CFM & Diameter 1350 mm
Type of Scrubber - Packed Bed Vertical Scrubber .
Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin
Packing Ht. - 750 mm
Packing Type - PP Pall Ring of 2" Dia.
PP Vertical Pump ( Coupled Drive )
Pump Motor - Matching Capacity of TEFC 2900 RPM | 1 | No. | 7,59,120 ₹7.6 L | 6,59,603 ₹6.6 L |
Updated dates
Tender Value
₹6.2 Cr
EMD Value
₹12.3 L
Closing Date
16 Mar 2026, 3:00 pmClosed
Executive Engineer
Assistant Executive Engineer-in-charge, AC Division, Works Department, IIT Delhi, Hauz Khas, New Delhi 110016
Providing Exhaust-Scrubber System for 99B and 99C Labs IIT Delhi
2026_IIT_898042_1
IITD/WORKS (SP- 5250)/2026
Open Tender
Civil Works
180 days
IIT Delhi Hauz Khas
Please refer Tender documents.
15 documents required · 15 mandatory
₹0
₹12.3 L
20 Apr 2026
12 Feb 2026
17 Mar 2026
12 Feb 2026
16 Mar 2026
12 Feb 2026
SINGLE STAGE PACKED BED VERTICAL WET SCRUBBER.
Supply, Installation, Testing and Commissioning of Single stage, Vertical Wet Scrubber with integrated liquid tank. - Airflow : As mentioned below for individual Scrubbers - Temperature: 70 Deg C (max.). - Pressure drop 100 mm WG (approx.). - Material: PP+FRP with Isophthalic resin. - Scrubber Sink height not less than 750mm. Complete makeup water connection, 5" Float valve, 12mm x 1000 mm Glass water level indicator, drain & over flow pipe connections with required valves. - Scrubber recirculation pump with Mechanical seal coupled with suitable IP-55, 3 Phase, 50 Hz, motor with rain protection of PP+FRP guard. Inlet flange connection with valve and 'Y' Strainer with brass filter. Outlet flange connection with non return (NRV) valve with gaskets & bolt nuts. - Scrubber Inlet collar with 15 Deg inclination towards down at shell inside. - 12mm Perforated sheet with 35mm hole diameter and total open area is not less than 66% of perforated sheet area. - Single stage packing material consists of 50mm PP pal rings filled upto 750 mm Height. - One Set of liquid spray nozzle system with equal space matrix not less than 300mm. - Circular 3 pass PVC mist eliminator secured with 6 number mounting bolts mounted on lugs / circular ring. - Acylic/ White PP dosing tank 500 mm Diameter x 500 mm Height with lead & handle and supported with galvanised MS support stand and with12mm Pipe connection to the scrubber with control valve for manual dosing. - MS Ladder with 5mm Thick maintenace platform, finished with Chlorinated rubber paint and attached to the scrubber shell near the view port / window. - 5mm Thick acrylic Inspection and maintenance door /window between packing material & mist eleminator zone. - 0-500mm U-Tube manometer acorss inlet & outlet collars with transparent connecting tubes. - Mounting Bolt & Nuts with Anti Vibration Pads.
Location: 99B 1F
Cluster EEC (cluster ) : 1 Capacity - not less than 500 CFM & Diameter 450 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Location: 99B 2F
Cluster EEC : 1 Capacity - not less than 5,027 CFM & Diameter 1200 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 2 Capacity - not less than 11,831 CFM & Diameter 1800 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 3 Capacity - not less than 12,200 CFM & Diameter 1800 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 4 Capacity - not less than 2,866 CFM & Diameter 900 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 5 Capacity - not less than 9,670 CFM & Diameter 1350 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 6 Capacity - not less than 4,087 CFM & Diameter 1050 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 1 Capacity - not less than 4,356 CFM & Diameter 1050 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 2 Capacity - not less than 1,876 CFM & Diameter 900 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 3 to 6 Capacity - not less than 5,280 CFM & Diameter 1200 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC : 7 Capacity - not less than 4,400 CFM & Diameter 1050 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
EXHAUST CENTRIFUGAL BLOWER
Supply, Installation , Testing & Commissioning of Medium Pressure Direct / Belt Driven PP Centrifugal Blower for the following capacity with Motor suitable for 3 Phase, 415 Volts, TEFC B5, IP 55, Protection Class F, 50 Hz, 2P/4P, Flange / Foot mounted and compatible for VFD Operations. Blower make as per NIT. Outlet Velocity less than 15 m/s
99B 1F (For respective cluster as above)
500 CFM | SP 125 mm WG | SISW | 1.1 Kw
99B 2F (For respective cluster as above)
5027 CFM | SP 125 mm WG | SISW | 5.5 Kw.
11831 CFM | SP 125 mm WG | SISW | 15 Kw.
12199 CFM | SP 125 mm WG | SISW | 15 Kw.
2866 CFM | SP 125 mm WG | SISW | 3.75 Kw.
9669 CFM | SP 125 mm WG | SISW | 11 Kw.
4086 CFM | SP 125 mm WG | SISW | 5.5 Kw.
99B 3F (For respective cluster as above)
4356 CFM | SP 125 mm WG | SISW | 5.5 Kw.
1876 CFM | SP 125 mm WG | SISW | 2.2 Kw
5280 CFM | SP 125 mm WG | SISW | 5.5 Kw.
4400 CFM | SP 125 mm WG | SISW | 5.5 Kw.
Supply and Installation of 4PP + 3FRP Weather cowl and MS Stack support for the following blower sizes. Inclusive of Blower inlet & outlet flexible connections and excluding duct between blower & cowl. (For respective cluster as above)
For SISW | 500 CFM
For SISW | 5027 CFM
For SISW | 11831 CFM
For SISW | 12199 CFM
For SISW | 2866 CFM
For SISW | 9669 CFM
For SISW | 4086 CFM
For SISW | 4356 CFM
For SISW | 1876 CFM
For SISW | 5280 CFM
For SISW | 4400 CFM
Fabrication, supplying, installation, testing & commissioning of following Variable Frequency Drive electrical control panel of cubicle construction, floor/wall mounted type of suitable size, fabricated out of 2 mm thick CRCA sheet, with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley of suitable size, interconnection, having switchgears and accessories (broadly as per following), mounting and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for operation on 415 V, 3 Phase, 50 Hz a.c supply with enclosure protection class IP 42 including connection to blower-motors of Exhaust Blower etc. complete as required. The drive panel shall run and control speed of motor automatically as per requirement taking pressure sense from main duct water through static pressure sensor. The panel shall consist of 3 phase indicating lamps, other indicating lamps with NO & NC, illuminated push buttons, etc., Digital voltmeter, ammeter, CTs, SPP, control MCB and all other accessories as to be required for complete automation with manual provision.
Not less than 0.75 kW Capacity
Not less than 1.1 kW Capacity
Not less than 2.2 kW Capacity
Not less than 3.75 kW Capacity
Not less than 5.5 kW Capacity
Not less than 11 kW Capacity
Not less than 15 kW Capacity
BLOCK 99 C | 2F - 3F - 4F | WING 1, 2 & 3.
SINGLE STAGE PACKED BED VERTICAL WET SCRUBBER.
Supply, Installation, Testing and Commissioning of Single stage, Vertical Wet Scrubber with integrated liquid tank. - Airflow : As mentioned below for individual Scrubbers - Temperature: 70 Deg C (max.). - Pressure drop 100 mm WG (approx.). - Material: PP+FRP with Isophthalic resin. - Scrubber Sink height not less than 750mm. Complete makeup water connection, 5" Float valve, 12mm x 1000 mm Glass water level indicator, drain & over flow pipe connections with required valves. - Scrubber recirculation pump with Mechanical seal coupled with suitable IP-55, 3 Phase, 50 Hz, motor with rain protection of PP+FRP guard. Inlet flange connection with valve and 'Y' Strainer with brass filter. Outlet flange connection with non return (NRV) valve with gaskets & bolt nuts. - Scrubber Inlet collar with 15 Deg inclination towards down at shell inside. - 12mm Perforated sheet with 35mm hole diameter and total open area is not less than 66% of perforated sheet area. - Single stage packing material consists of 50mm PP pal rings filled upto 750 mm Height. - One Set of liquid spray nozzle system with equal space matrix not less than 300mm. - Circular 3 pass PVC mist eliminator secured with 6 number mounting bolts mounted on lugs / circular ring. - Acylic/ White PP dosing tank 500 mm Diameter x 500 mm Height with lead & handle and supported with galvanised MS support stand and with12mm Pipe connection to the scrubber with control valve for manual dosing. - MS Ladder with 5mm Thick maintenace platform, finished with Chlorinated rubber paint and attached to the scrubber shell near the view port / window. - 5mm Thick acrylic Inspection and maintenance door /window between packing material & mist eleminator zone. - 0-500mm U-Tube manometer acorss inlet & outlet collars with transparent connecting tubes. - Mounting Bolt & Nuts with Anti Vibration Pads.
Cluster EEC ( SF cluster ) : 1 Capacity - Not less than 3,498 CFM & Diameter 900 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC ( 3F cluster ) : 1 Capacity - Not less than 3,960 CFM & Diameter 900 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC ( 4F cluster ) : 1 Capacity - Not less than 2,110 CFM & Diameter 600 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC ( 4F cluster ) : 2 Capacity - Not less than 1,568 CFM & Diameter 600 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
Cluster EEC ( 4F cluster ) : 3 Capacity - Not less than 1,606 CFM & Diameter 600 mm Type of Scrubber - Packed Bed Vertical Scrubber . Thickness - 5mm PP + 3mm FRP Using Isophthalic Resin Packing Ht. - 750 mm Packing Type - PP Pall Ring of 2" Dia. PP Vertical Pump ( Coupled Drive ) Pump Motor - Matching Capacity of TEFC 2900 RPM
EXHAUST CENTRIFUGAL BLOWER
Supply, Installation , Testing & Commissioning of Medium Pressure Direct / Belt Driven PP Centrifugal Blower for the following capacity with Motor suitable for 3 Phase, 415 Volts, TEFC B5, IP 55, Protection Class F, 50 Hz, 2P/4P, Flange / Foot mounted and compatible for VFD Operations. Blower make as per NIT.
99C 2F (For respective cluster)
3498 CFM | SP 175 mm WG | SISW | INLET SIZE 400 | 3.75 Kw.
99C 3F (For respective cluster)
3960 CFM | SP 175 mm WG | SISW | INLET SIZE 400 | 3.75 Kw.
99C 4F (For respective cluster)
2110 CFM | SP 75 mm WG | SISW | INLET SIZE 315 | 1.5 Kw
1568 CFM | SP 75 mm WG | SISW | INLET SIZE 315 | 1.5 Kw
1600 CFM | SP 75 mm WG | SISW | INLET SIZE 315 | 1.5 Kw
Supply and Installation of 4PP + 3FRP Weather cowl and MS Stack support for the following blower sizes. Inclusive of Blower inlet & outlet flexible connections and excluding duct between blower & cowl.
For SISW |Outlet size 400 mm
For SISW |Oulet size 315 mm
Ducting for Lab Exhaust- Designing, Supply and installation of PP FRP duct of 3mm PP + 3 mm FRP Using Isophthalic Resin. Duct area complete with connecting fittings, necessary flanges, bends, entry branches, tapers, inspection door, gaskets for flanges, bolt & nuts, washers, support angle, hanger threaded rods with anchor bolts for fixing, guide vanes,adjustable splitters, pressure testing, air balancing etc.. complete confirming to IS Standards. Rate is inclusive of enamel painting for exposed surfaces. Mode of measurement shall be in sqm, measured as circumference x running length, extra will not be paid for accessories such as flanges, entry doors, inspection doors, gaskets etc. Also making ducts/pipes/cable tray openings and closing the same. Up to 750 mm Dia
Ducting for Lab Exhaust- Designing, Supply and installation of PP FRP duct of 4mm PP + 3 mm FRP Using Isophthalic Resin. Duct area complete with connecting fittings, necessary flanges, bends, entry branches, tapers, inspection door, gaskets for flanges, bolt & nuts, washers, support angle, hanger threaded rods with anchor bolts for fixing, guide vanes,adjustable splitters, pressure testing, air balancing etc.. complete confirming to IS Standards. Rate is inclusive of enamel painting for exposed surfaces. Mode of measurement shall be in sqm, measured as circumference x running length, extra will not be paid for accessories such as flanges, entry doors, inspection doors, gaskets etc. Also making ducts/pipes/cable tray openings and closing the same. Above 750 mm Dia & Below 1000 mm Dia
SS Ducting : Designing, Supply and installation of SS 304 seamless duct of 18 SWG. Duct area complete with connecting fittings, necessary flanges, bends, entry branches, tapers, inspection door, gaskets for flanges, bolt & nuts, washers, support angle, hanger threaded rods with anchor bolts for fixing, guide vanes,adjustable splitters, pressure testing, air balancing etc.. complete confirming to IS Standards. Mode of measurement shall be in sqm, measured as circumference x running length, extra will not be paid for accessories such as flanges, entry doors, inspection doors, gaskets etc. Also making ducts/pipes/cable tray openings and closing the same.
Supply & fixing of PP Moulded 250/300 mm dia, Single leaf butterfly damper for Fume Hoods & BSC & Canopy
Supply & fixing of PP Moulded 100 mm dia, Single leaf butterfly damper for Spot Extractor & Chemical storage.50mm for Base Cabinets
Supply & fixing of 5PP+3FRP Volume Control Manual Dampers.@ manifolds.
Supply & fixing of 40 / 50 mm Flexible connection for Fume Hood Base Cabinet.. Number considered 1No as 2.5 Rmt.
Supply & fixing of 100 mm Flexible connection for Spot Extractors & Chemcial storage Cabinets. Number considered 1No as 1.5 Rmt.
Fresh air bleed manual damper
Supply & fixing of 1200 X 600 mm Ht., UPVC Multivane fresh air bleed control manual damper.
CONSTANT AIR VOLUME ( CAV ) BOX / CONSTANT VOLUME AIR REGULATOR.
Supply of Plastic type (fire retardant) non exposed spring loaded, silicone regulating membrane mechanical type CAV Box. The cconstant volume regulator type CVR is a control element which works independently of the pressure without an external power supply. It can be regarded as a self-actuating duct damper, as it delivers a required volume of air regardless of changes in system pressure.
0 - 300 CFM | Dia 100 - 200 mm
300 - 700 CFM | Dia 250 - 300 mm
Supply and fixing of low leakage Motorized fire and smoke dampers made out of GI materials coated with Corrosion resistant epoxy Powder coating with Actuator shall be with 90min fire rating, automatically modulate based on supply voltage of 0 V to 10 V. Damper to be multi function for smoke and fire complete with actuator ready for hook up with fire alarm control panel. Approve Make as per NIT.
Supply, installation, Testing & commissioning of motorized actuators, sensors, controls and all accessories as per specification for above Motorised fire damper.
Duct Static Pressure Sensor @ Exhaust duct
Supply, Installation, Testing & Commissioning of Static pressure sensor with all the mounting accessories included. The maximum pr limit shall be 0-500Pa all other mounting accessories complete as required.
Supply, Laying, Termination of ISI Certified 4 Core 1.5 sq.mm ATSC, PVC insulated, armored, Tinned Copper, twisted, shielded, PE insulated, Cable with proper ferrules, lugs and other necessary accessories. The spec shall meet the system manufacturer specifications
Supplying, laying, termination of following size ISI marked power cable of pvc insulated pvc shated XLPE armored copper cable 1.1 kV grade etc. complete as required.
4 core x 10 sqmm
Manual Air Balancing using third party agency For 99 C Building
Manual Air Balancing using third party agency For 99 B Building
Comprehensive maintenance including routine, preventive and breakdown maintenance of the complete exhaust ventilation system of both buildings 99B & C for proper operation of the system, repairing and replacement of spare parts as and when required etc. as required. (during DLP free of cost)
Comprehensive maintenance including routine, preventive and breakdown maintenance of the complete exhaust ventilation system of both buildings 99B & C for proper operation of the system, repairing and replacement of spare parts as and when required etc. as required. (after DLP) N.B. - 1 job means for 12 months
1st year
2nd year
3rd year
4th year
5th year
Civil Work
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge : In cement mortar
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : -Of area 3 sq. metres and below
Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : Of area beyond 3 sq. metres
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge.
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand)
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases for columns
Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level. .: Thermo-Mechanically Treated bars of grade Fe-500D or more.
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources)
Steel reinforcement for R.C.C. work ready to use “cut and bend” rebars of approved make from factory/workshop to construction site including placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
15 mm cement plaster on rough side of single or half brick wall of mix: 1:4 (1 cement: 4 coarse sand)
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and fixing mild steel round holding down bolts with nuts and washer plates complete
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum)sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge. :Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames/ opening (cut outs) having area less than 0.30 sqm.The calcium silicate ceiling tile shall have NRC value of 0.50 (Minimum), light reflection > 85%, non- combustible as per B.S. 476 part IV, 100% humidity resistance and also having thermal conductivity <0.043 w/mK.
Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 mm dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge 10 x 80 mm
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer’s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with :
12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) :2011 (Board with BIS certification marks)
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm)
Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour : 13.41.1 New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre
Painting with synthetic enamel paint of approved brand andmanufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
Providing and fixing double scaffolding system (cup lock type) on the exterior side, up to seven story height made with 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after .The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineer-in-charge .The elevational area of the scaffolding shall be measured for payment purpose .The payment will be made once irrespective of duration of scaffolding. Note: - This item to be used for maintenance work judicially, necessary deduction for scaffolding in the existing item to be done.
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design : In 75x75 mm deep chase
Providing and applying white cement based putty of average thickness 1 mm, of approvedbrand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
Making core cutting for fixing pipe/duct in RCC slab/wall/beam up to 150 mm dia for duct fitting as per detailed drawing and as directed by engineer in charge.
Filling and finishing the holes of varies sizes and shades with GP-2 cementitious polymer compound around Duct/ pipes etc. mixed with water in ratio prescribed by manufacturer to form consistent workable enough for pushing it in the holes upto full depth of wall using appropriate tools and finishing smooth all complete as per directions of the Engineer-in-charge.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
techsummary_943960.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.84 MB
BOQ_943960.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid