Assistant Engineer, Katwa Electrical Sub Division
Katwa, Purba Bardhaman PIN-713130
Installation of RAC and allied Electrical work at Eye OT,Surgical OT and Pediatric ward at Katwa SD Hospital in the District of Purba Bardhaman.
2024_WBPWD_763241_1
WBPWD/AE-KESD/NIQ-17/2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
14 days
Katwa
Please refer Tender documents.
5 documents required · 5 mandatory
₹7,450
27 Jan 2025
8 Oct 2024
21 Oct 2024
8 Oct 2024
19 Oct 2024
9 Oct 2024
Amount
Supplying and fixing double door Horizontal TPN MCB Distribution boardLegrand/ Siemens) with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment 6way(Legrand/ Siemens) Enclosure (8GB32202RC06) with 1 no. 415V 80 A. FP Isolator and 18 nos 240 V 6-32 A. SP MCB as required.(D-10/14)(D-5/6)(D-6/7)
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (RR Kabel/KEI/Havells/Polycab) in 20mm size PVC rigid conduit 'FR'(Precision MMS make) incl. necy. fittings as required (E-14/1a)
2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC (For 2 nos AC machine )
Supplying and fixing PVC Rigid Conduit 'FR' [Precision MMS Make] on wall, ceiling with saddles and other accessories as requiredand mending good damages to building works(E-16/7b)
25mm size(for 4x(10 sqmm) + 2x (6 sqmm)wire
Supplying and Drawing 1.1 KV single core stranded'FR' PVC insulated & unsheathed single core stranded copper wire(RR Kabel/KEI/Havells/Polycab)of the following sizes in the Rigid Pipe)(E-9/1)
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC( Exiting VTPN to PBDB )
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes
i)2.5 Sqmm
ii)4 sqmm
iii)6 sqmm
iv)10 sqnm
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket, on S&F 2 Module PVC Modular type switch board (all Mk. Legrand Myrus / Anchor Roma / Schneider / Cabtree) after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. (E19/16)
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Anchor/Legrand/North West) & necy. Connections. (E-17/5b)
Supply & Fixing 240 V, 25 A, Modular type starter with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate (all Mk. Legrand Myrus / Anchor Roma / Schneider / Cabtree) flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (E19/17)
S&F timer box made of 16 SWG MS Sheet, Powder Coated Painted (Siemens Grey) consisting with 1 no. 230 V. 32 A. DP MCB, 1 no. 32 A. 3 pole Power contactor, 1 no. toggle switch, 1 no. analog timer clock, Inditating lamps, 2 nos. connectors etc. (Mk. L&T / Siemens / ABB) incl. suitable size of interconnecting wire (power line by 6 sq.mm. wire, control circuit by 1.5 sq.mm., indicating circuit by 1.5 sq.mm. Mk. Havell's / Gloster / Polycab) as reqd. as per GS. [For AC]
Supply ,Installation ,Testing & Commissioning of Split type AC machine having colling capacity range (6.6KW-7.0KW),With variable speed rotary compressor ,refrigerant gas R32/R410 BBE star rating-3(EER range 3.5 to 3.99),Air flow range CFM(780-850), P2 capcitor, Indoor and outdoor PCB should be in metal enclosure both condencer and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391(Part-i &Part-II)with all amendments(Make:-Mitsubishi Electric/O General/ Hitachi)(2 nos For OT & 2 Nos for Peadiatric Ward)
Supply, installation, testing & commissioning of copper refrigeration pipe line for liquid and Suction line including vaccumiazation and Nitrogen of testing of following nominal size of soft/ hard drawn copper refrigerent piping for Split AC system, complete with fittings with adjustable ring type hanger supports, jointing/ brazing including accessories, insulated with XLPE class - O tubular insulation/ with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 9mm. thickness for suction and liquid lines, all accessories as per specification etc. as required & as per direction of EIC with proper mending good damages to original finish. Mk. of Cu pipe - Rajco/ Ryoku/ Mandev/ Nippon Mk. of Nitrile Rubber Insulation - Aeroflex/ K-flex/ Accroflex/ Armacell. (a) 15.88 mm (5/8) O.D. (Thickness : 1mm) (Insulation : 9 mm) & (b) 6.4 mm O.D (1/4). (Thickness : 0.8mm) (Insulation : 9 mm)
S/L of 4 core 2.5 sq.mm 1.1 KV grade unsheathed FR Cu cable with gas line as per direction of EIC for Indoor to Outdoor Communication for Split type AC m/c.(Make:- Polycab/ Havells/ KEI/RR Kabel)
S/L of 3core 4 sq.mm 1.1 KV grade unsheathed "FR" Cu cable with gas line as per direction of EIC for Indoor to Outdoor Communication for Split type AC m/c.(Make:- Polycab/ Havells/ KEI/RR Kabel)
Supply & layingSoft Drawn braided hose PVC Pipe 19mm dia for water drain with proper supports & brackets as per direction EIC. (Make: Suprime/Oriplast as per approved by EIC)
Rates to be quoted will be inclusive of all the taxes incl. GST. No other additional charges will be applicable in addition to the quoted rates.
K.C. BYSACK AND SONS (BID ID -5700254)
TAPAN ELECTRICS (BID ID -5696679)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .