Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.1 CrAdmitted-Finance | ₹3.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹3.1 Cr+₹2.8 L (0.90%)Admitted-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | ₹3.1 Cr+₹2.8 L (0.90%) | L2 | Admitted-Finance |
| 3 | L3₹3.2 Cr+₹9.7 L (3.13%)Admitted-Finance | ₹3.2 Cr+₹9.7 L (3.13%) | L3 | Admitted-Finance |
| 4 | L4₹3.2 Cr+₹11.0 L (3.55%)Admitted-Finance C 9 53 IIND FLOOR SECTOR 08 ROHINI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | ₹3.2 Cr+₹11.0 L (3.55%) | L4 | Admitted-Finance |
| 5 | L5₹3.8 Cr+₹66.6 L (21.6%)Admitted-Finance 51 212D 3E K V NAGAR NEAR ADARSH NAGAR KHERIA MOD AGRA UP 282001 | AGRA | UTTAR PRADESH | 282001 | ₹3.8 Cr+₹66.6 L (21.6%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Parveen Builders L7 | M/s Dhapola Elevator and Engineering L6 | AMIT ASSOCIATES L3 | L G BUILDERS L4 | Commercial Traders L2 | Sethi Brothers L5 | Arihant Enterprises L1 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supplying, installing, testing and commissioning of 100 KVA 3-Ph Input / 3-Ph Output True Online, Modular type, Medical grade, having suitable output isolation transformer, double conversion PWM IGBT-based UPS System, suitable for critical applications requiring high availability. The UPS shall be based on DSP-controlled three-level inverter topology and operate in tower installation mode. The system shall support parallel scalability up to 6 units in N+1 configuration. Input voltage shall be 400V AC, 3-phase, 4-wire with a wide operating range of 340V to 477V and frequency range from 40Hz to 70Hz complete all as specified, directed and comprising of the following specifications :-
(a) The output shall be 415V AC, 3-phase, delivering rated power of 100 kW at unity power factor. The inverter shall offer a crest factor of minimum 2.5:1 with THDv<2.0% on linear loads and voltage regulation within ±1%. Inverter overload capability shall include <105% continuous, <110% for 60 minutes, <125% for 10 minutes, <150% for 1 minute, and >150% for 200ms. Transfer from mains to battery shall be seamless (0 ms), while inverter-to-bypass transfer shall be synchronous ≤0 ms and asynchronous ≤20 ms. | 4 | Each Job | 21,99,999 ₹87,99,996 | 19,35,500 ₹77,42,000 | 18,13,900 ₹72,55,600 | 18,20,000 ₹72,80,000 | 19,00,000 ₹76,00,000 | 19,18,000 ₹76,72,000 | 14,35,680 ₹57,42,720 Lowest |
| 1.01(b) Efficiency shall be up to 96% in double conversion mode and 99% in ECO mode. The UPS shall support battery bus voltage from 360 V to 600 VDC or as per OEM recommendations, and suitable battery charger. Compatible battery types include SMF VRLA, Tubular, and Li-ion. Noise level shall not exceed 65 dB at 1 meter. (c) UPS Operating temperature range shall be 0°C to 40°C, and storage temperature -25°C to +55°C (without battery), -15°C to +40°C (with battery). Relative humidity shall be 5% to 95% non-condensing. System shall operate without derating up to 1000 m altitude; above that, derate by 1% per 100 m. (d) The system shall feature a graphical LCD display capable of storing up to 256 events. Data must be transferred to CMS via SNMP or RS232/ RS485/ Modbus (serial/TCP/IP) or as per OEM recommendations. UPS shall be integrated with the existing 'OT Building Management System' through a field controller via Bacnet/ DNP3.0 protocols. The contractor shall coordinate with the existing BMS vendor and provide field controller(s) required for integration. UPS graphics and alarms shall be provided in the BMS. All integration costs shall be deemed included in the quoted rate of the contractor. (e) UPS enclosure shall be IP20/IP21 rated with rear cable entry, forced-air cooling, and powder-coated black texture finish. | ||||||||||
| 1.02(f) UPS must comply with IEC 62040-1 (safety), IEC 62040-2 (EMC). It shall also meet ISO 9001:2015 for quality and ISO 14001 for environmental management. Vendor must provide full spare and service support for at least 10 years from the date of product discontinuation. (g) The contractor shall submit a Manufacturer’s Authorization Form (MAF) from the OEM of the UPS, covering all warranties, along with the technical bid. (h) Make & Model of the UPS : Schneider- Easy UPS 3M, Vertiv- Liebert EXM2-100KVA, ABB DPA 500-100KVA | ||||||||||
| 2.00 | Supplying, installing, testing and commissioning of 30 KVA 3-Ph Input / 3-Ph Output True Online, Modular type, Medical grade, having suitable output isolation transformer, Double Conversion IGBT-based UPS System, suitable for OT & Lighting Application. UPS shall be based on DSP-controlled Three-Level Inverter technology (VFI-SS-III topology) with Cold Start and Soft Start feature. The system shall support battery backup testing without switching OFF Input Breaker. UPS must operate on generator supply with provision for separate mains and bypass input, and comply with IEC 62040-3 standards. System must offer inverter output at unity power factor with <2% THD (linear load) and <5.5% (non-linear load), pure sinewave output and capability to handle 110% load for 60 mins, 125% for 10 mins, and 150% for 1 min. UPS efficiency shall be >96% at 100% linear load. Transfer time from AC to Battery shall be zero, complete all as specified, directed and comprising of the following specifications :-
(a) UPS shall support SMF VRLA battery bank with flexible DC bus (384–480V), batteries ranging 65AH–200AH. It must support operation with up to 2 battery failures without shutdown, and provide battery protection via circuit breaker with fuse, DC undervoltage trip, and EPO. Charger shall support minimum 10% AH rating and charge battery to 90% within 10 hours. Note : If, OEM is not manufacturing 30 KVA UPS system, the contractor shall provide the next standard one with higher capacity without any extra cost. | 19 | Each Job | 7,00,000 ₹1,33,00,000 | 9,45,800 ₹1,79,70,200 | 6,15,950 ₹1,17,03,050 Lowest | 6,18,000 ₹1,17,42,000 | 6,70,000 ₹1,27,30,000 | 8,99,000 ₹1,70,81,000 | 6,80,950 ₹1,29,38,050 |
| 2.01(b) The system must include intuitive LCD display with UPS status, I/O voltage, battery level, breaker status, and fault logs (upto 500 events). Alarm conditions must include Mains Fail, Rectifier Fail, Inverter Fail, Low Battery, Over Temp, Fan Fail, etc. UPS must include REPO (EPO) switch and support SNMP, Modbus (serial/TCP/IP). UPS shall be integrated with the existing 'OT Building Management System' through a field controller via Bacnet/ DNP3.0 protocols. The contractor shall coordinate with the existing BMS vendor and provide field controller(s) required for integration. UPS graphics and alarms shall be provided in the BMS. All integration costs shall be deemed included in the quoted rate of the contractor. (c) System shall have automatic bypass on overload / fault conditions and facility for bypass enable / disable. Cabinet shall be IP20 rated with bottom cable entry. UPS must operate in 0–40°C without derating, support 20–90% RH non-condensing, and have noise level <65 dBA at 1m. (d) UPS shall comply with IEC 62040-1, IEC 62040-2, ISO 9001:2015, ISO 14001:2015, ISO 45001:2018. Surge protection per IEC 62040-2. Input, Output and Earth cabling by client using ISI-marked multi-strand flexible copper cable. The earth resistance shall be monitored and displayed continuously using smart earth resistance monitoring system. Warranty: 1 Year. OEM must provide service and spare support for 10 years after product discontinuation. (e) The contractor shall submit a Manufacturer’s Authorization Form (MAF) from the OEM of the UPS, covering all warranties, along with the technical bid. (f) Make & Model of the UPS : Schneider Easy UPS 3-Phase Modular-30KVA, Vertiv Liebert APM2 Series-30KVA, ABB Conceptpower DPA-30 KVA | ||||||||||
| 3.00 | Supplying, installing, testing and commissioning of UPS vendor-approved 200Ah / 12V SMF Batteries, 1 set consisting of minimum 40 blocks per 100 KVA UPS, suitable for providing 30 minutes backup time @0.89F. Batteries shall be sealed maintenance-free (SMF) type, conforming to the latest relevant standards. Each battery shall be factory-fresh, date-coded, and rated for high cyclic life and deep discharge recovery characteristics. The manufacturing months/ year shall be clearly embossed on the battery. Stickers are not allowed.
The installation shall be carried out using open-type, powder-coated mild steel (MS) battery racks for floor mounting installation with proper tiered arrangement of batteries, along with battery-to-battery and battery-to-UPS interconnections using appropriately rated Nyvin (Flame Retardant) copper cables with insulated lugs and sleeves. Cable length and sizing shall be as per UPS OEM recommendations.
All batteries must be sourced from UPS OEM-approved makes only. Manufacturer’s test certificate, warranty certificate for 2 years, and batch test report shall be submitted at the time of delivery. Batteries must be RoHS compliant. Batteries replaced under warranty condition shall have manufacturing date within 6 months from the date of replacement.
Approved Make: Amaron (Quanta), Exide, HBL.
Notes :
(a) The UPS and batteries should be from same OEM for better compatibility, integration and service support.
(b) The battery system shall be designed with highest level of protection built into the battery system against potential safety risk i.e. over voltage and short circuit. Compatibility certificate with offered model of battery and UPS shall be submitted by the contractor before commencement of work.
(c) Whole scheme i.e. battery sizing and quantity calculation for minimum 30 minute backup duly approved from NIT/IIT shall be submitted by the contractor before commencement of work. Any change i.e. in size and in quantites of batteries and UPS, if any required to obtain desired result shall be done by the contractor without any extra cost and expenditure in this regard shall be deemed included in quoted rates. | 4 | Each Set | 15,00,000 ₹60,00,000 | 9,78,500 ₹39,14,000 | 11,15,500 ₹44,62,000 | 11,00,000 ₹44,00,000 | 9,02,000 ₹36,08,000 | 8,80,000 ₹35,20,000 Lowest | 10,15,250 ₹40,61,000 |
| 4.00 | Supplying, installing, testing and commissioning of UPS vendor-approved 65Ah / 12V SMF Batteries, 1 set consisting of minimum 38 blocks per 30 KVA UPS, suitable for providing 30 minutes backup time @0.89F. Batteries shall be sealed maintenance-free (SMF) type, conforming to the latest relevant standards. Each battery shall be factory-fresh, date-coded, and rated for high cyclic life and deep discharge recovery characteristics. The manufacturing months/ year shall be clearly embossed on the battery. Stickers are not allowed.
The installation shall be carried out using open-type, powder-coated mild steel (MS) battery racks for floor mounting installation with proper tiered arrangement of batteries, along with battery-to-battery and battery-to-UPS interconnections using appropriately rated Nyvin (Flame Retardant) copper cables with insulated lugs and sleeves. Cable length and sizing shall be as per UPS OEM recommendations.
All batteries must be sourced from UPS OEM-approved makes only. Manufacturer’s test certificate, warranty certificate for 2 years, and batch test report shall be submitted at the time of delivery. Batteries must be RoHS compliant. Batteries replaced under warranty condition shall have manufacturing date within 6 months from the date of replacement.
Approved Make: Amaron (Quanta), Exide, HBL.
Notes :
(a) The UPS and batteries should be from same OEM for better compatibility, integration and service support.
(b) The battery system shall be designed with highest level of protection built into the battery system against potential safety risk i.e. over voltage and short circuit. Compatibility certificate with offered model of battery and UPS shall be submitted by the contractor before commencement of work.
(c) Whole scheme i.e. battery sizing and quantity calculation for minimum 30 minute backup duly approved from NIT/IIT shall be submitted by the contractor before commencement of work. Any change i.e. in size and in quantites of batteries and UPS, if any required to obtain desired result shall be done by the contractor without any extra cost and expenditure in this regard shall be deemed included in quoted rates. | 19 | Each Set | 6,00,000 ₹1,14,00,000 | 2,76,500 ₹52,53,500 | 3,00,700 ₹57,13,300 | 3,10,000 ₹58,90,000 | 2,10,000 ₹39,90,000 Lowest | 3,50,000 ₹66,50,000 | 3,15,850 ₹60,01,150 |
| 5.00 | Supplying, installing, testing and commissioning of PVC insulated Copper Conductor (sheathed), flexible cable, 1100 volts grade of size 4 core 16 Sq mm including securing the cable on wall / cable tray with suitable fastners etc, complete all as specified and directed | 190 | RM | 1,099 ₹2,08,810 | 1,200 ₹2,28,000 | 1,358 ₹2,58,020 | 1,400 ₹2,66,000 | 1,414 ₹2,68,660 | 800 ₹1,52,000 Lowest | 1,459 ₹2,77,210 |
| 6.00 | Supplying, installing, testing and commissioning of PVC insulated Copper Conductor (sheathed), flexible cable, 1100 volts grade of size 4 core 50 Sq mm including securing the cable on wall / cable tray with suitable fastners etc, complete all as specified and directed | 60 | RM | 3,299 ₹1,97,940 | 2,560 ₹1,53,600 | 3,686 ₹2,21,160 | 3,500 ₹2,10,000 | 4,710 ₹2,82,600 | 950 ₹57,000 Lowest | 4,458 ₹2,67,480 |
| 7.00 | Material and Labour for dismantling the existing UPS alongwith connected batteries and accessories carefully from various OTs / Wards of CTVS / Main Bldg and depositing the same to MES Store yard for further disposal, complete all as specified and directed. | 23 | Each Job | 2,999 ₹68,977 | 8,000 ₹1,84,000 | 1,940 ₹44,620 | 2,000 ₹46,000 | 10,000 ₹2,30,000 | 1,500 ₹34,500 Lowest | 2,000 ₹46,000 |
Tender Value
₹3 Cr
EMD Value
₹3.8 L
Closing Date
11 Jul 2026, 6:00 pmClosed
HQ Chief Engineer Delhi Zone
HQ Chief Engineer Delhi Zone Delhi Cantt-10
SPL REPAIR TO UPS AGAINST BER INSTALLED AT AHRR UNDER GE E/M RR DELHI CANTT-10
2025_MES_729612_3
CEDZ/TOKEN-32 OF 2025
Open Tender
Civil Works
Item Rate
240 days
Delhi Cantt
As per NIT
10 documents required · 10 mandatory
₹2,000
GE EM RR Hospital
₹3.8 L
Yes
17 Aug 2026
13 Jun 2026
16 Jul 2026
13 Jun 2026
11 Jul 2026
27 Jun 2026
13 Jun 2026 - 19 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, installing, testing and commissioning of 100 KVA 3-Ph Input / 3-Ph Output True Online, Modular type, Medical grade, having suitable output isolation transformer, double conversion PWM IGBT-based UPS System, suitable for critical applications requiring high availability. The UPS shall be based on DSP-controlled three-level inverter topology and operate in tower installation mode. The system shall support parallel scalability up to 6 units in N+1 configuration. Input voltage shall be 400V AC, 3-phase, 4-wire with a wide operating range of 340V to 477V and frequency range from 40Hz to 70Hz complete all as specified, directed and comprising of the following specifications :-
(a) The output shall be 415V AC, 3-phase, delivering rated power of 100 kW at unity power factor. The inverter shall offer a crest factor of minimum 2.5:1 with THDv<2.0% on linear loads and voltage regulation within ±1%. Inverter overload capability shall include <105% continuous, <110% for 60 minutes, <125% for 10 minutes, <150% for 1 minute, and >150% for 200ms. Transfer from mains to battery shall be seamless (0 ms), while inverter-to-bypass transfer shall be synchronous ≤0 ms and asynchronous ≤20 ms. | 4 | Each Job | - | - |
| 1.01 | (b) Efficiency shall be up to 96% in double conversion mode and 99% in ECO mode. The UPS shall support battery bus voltage from 360 V to 600 VDC or as per OEM recommendations, and suitable battery charger. Compatible battery types include SMF VRLA, Tubular, and Li-ion. Noise level shall not exceed 65 dB at 1 meter.
(c) UPS Operating temperature range shall be 0°C to 40°C, and storage temperature -40°C to +70°C (without battery), -25°C to +55°C (with battery). Relative humidity shall be 5% to 95% non-condensing. System shall operate without derating up to 1000 m altitude; above that, derate by 1% per 100 m.
(d) The system shall feature a graphical LCD display capable of storing up to 256 events. Data must be transferred to CMS via SNMP or RS232/ RS485/ Modbus (serial/RCP/IP) or as per OEM recommendations.
(e) UPS enclosure shall be IP20/IP21 rated with rear cable entry, forced-air cooling, and powder-coated black texture finish. | - | - | - | - |
| 1.02 | (f) UPS must comply with IEC 62040-1 (safety), IEC 62040-2 (EMC). It shall also meet ISO 9001:2015 for quality and ISO 14001 for environmental management. Vendor must provide full spare and service support for at least 10 years from the date of product discontinuation.
(g) The contractor shall submit a Manufacturer’s Authorization Form (MAF) from the OEM of the UPS, covering all warranties, along with the technical bid.
(h) Make & Model of the UPS : Schneider- Easy UPS 3M, Vertiv- Liebert EXM2-100KVA, ABB DPA 500-100KVA | - | - | - | - |
| 2 | Supplying, installing, testing and commissioning of 30 KVA 3-Ph Input / 3-Ph Output True Online, Modular type, Medical grade, having suitable output isolation transformer, Double Conversion IGBT-based UPS System, suitable for OT & Lighting Application. UPS shall be based on DSP-controlled Three-Level Inverter technology (VFI-SS-III topology) with Cold Start and Soft Start feature. The system shall support battery backup testing without switching OFF Input Breaker. UPS must operate on generator supply with provision for separate mains and bypass input, and comply with IEC 62040-3 standards. System must offer inverter output at unity power factor with <2% THD (linear load) and <5.5% (non-linear load), pure sinewave output and capability to handle 110% load for 60 mins, 125% for 10 mins, and 150% for 1 min. UPS efficiency shall be >96% at 100% linear load. Transfer time from AC to Battery shall be zero, complete all as specified, directed and comprising of the following specifications :-
(a) UPS shall support SMF VRLA battery bank with flexible DC bus (384–480V), batteries ranging 65AH–200AH. It must support operation with up to 2 battery failures without shutdown, and provide battery protection via circuit breaker with fuse, DC undervoltage trip, and EPO. Charger shall support minimum 10% AH rating and charge battery to 90% within 10 hours. Note : If, OEM is not manufacturing 30 KVA UPS system, the contractor shall provide the next standard one with higher capacity without any extra cost. | 19 | Each Job | - | - |
| 2.01 | (b) The system must include intuitive LCD display with UPS status, I/O voltage, battery level, breaker status, and fault logs (upto 500 events). Alarm conditions must include Mains Fail, Rectifier Fail, Inverter Fail, Low Battery, Over Temp, Fan Fail, etc. UPS must include REPO (EPO) switch and support SNMP, Modbus (serial/TCP/IP).
(c) System shall have automatic bypass on overload / fault conditions and facility for bypass enable / disable. Cabinet shall be IP20 rated with bottom cable entry. UPS must operate in 0–40°C without derating, support 20–90% RH non-condensing, and have noise level <65 dBA at 1m.
(d) UPS shall comply with IEC 62040-1, IEC 62040-2, ISO 9001:2015, ISO 14001:2015, ISO 45001:2018. Surge protection per IEC 62040-2. Input, Output and Earth cabling by client using ISI-marked multi-strand flexible copper cable. The earth resistance shall be monitored and displayed continuously using smart earth resistance monitoring system. Warranty: 1 Year. OEM must provide service and spare support for 10 years after product discontinuation.
(e) The contractor shall submit a Manufacturer’s Authorization Form (MAF) from the OEM of the UPS, covering all warranties, along with the technical bid.
(f) Make & Model of the UPS : Schneider Easy UPS 3-Phase Modular-30KVA, Vertiv Liebert APM2 Series-30KVA, ABB Conceptpower DPA-30 KVA | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.19 MB
BOQ_864549.xls
BOQ • 0.90 MB
1 Common pages.pdf
Tender Documents • 0.61 MB
2. Sch B.pdf
Tender Documents • 0.46 MB
3. Min Wages.pdf
Tender Documents • 0.40 MB
4.0 Special Condition.pdf
Tender Documents • 0.53 MB
5.. Particular Specification.pdf
Tender Documents • 0.74 MB
6.0 List of material Appx A & B.pdf
Tender Documents • 0.29 MB
7.0 Appendix C.pdf
Tender Documents • 0.38 MB
8.0 List of makes Appx D.pdf
Tender Documents • 0.58 MB
8.1 List of makes Appx E.pdf
Tender Documents • 0.50 MB
9.0 Appendix F.pdf
Tender Documents • 0.34 MB
10. Appendix G &H.pdf
Tender Documents • 0.29 MB
03amdt83183.pdf
PDF • 4.29 MB
01amdt83183.pdf
PDF • 0.85 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .