Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹154.8 CrAccepted-AOC | ₹154.8 Cr | L1 | Accepted-AOC Being lowest and reasonable |
| 2 | L2₹174.7 CrRejected-Finance | ₹174.7 Cr | L2 | Rejected-Finance Not being lowest |
| 3 | L3₹204.1 CrRejected-Finance | ₹204.1 Cr | L3 | Rejected-Finance Not being lowest |
Tender Value
₹141 Cr
EMD Value
₹15 L
Closing Date
27 Aug 2021, 6:00 pmClosed
CHIEF ENGINEER (AF) SHILLONG ZONE
HQ CHIEF ENGINEER AF SHILLONG ZONE MILITARY ENGINEER SERVICES ELEPHANT FALLS CAMP PO NONGLYER SHILLONG 793009
PROVISION OF DEFICIENT OTM ACCN AND HANGAR COMPLEX AT AF STN DINJAN UNDER GE(AF) MOHANBARI
2021_MES_450567_1
88617/DIN/E8
Open Tender
Civil Works
750 days
Dinjan
As per NIT
7 documents required · 7 mandatory
₹3,000
GE (AF) Mohanbari
₹15 L
Yes
5 Oct 2021
11 Jun 2021
1 Sept 2021
11 Jun 2021
27 Aug 2021
6 Aug 2021
12 Jun 2021 - 27 Aug 2021
Amount
NOTE (Applicable for all Parts/ Items):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates.
SCHEDULE "A" Part - I (BUILDING / STRUCTURES WORK ) Details of pre priced Schedule is given in tender documents
SCHEDULE 'A' PART- II (SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART- III (INTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- IV (INTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART-V (TRANSFORMER YARD) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART-VI (HANGAR FLOOR / TARMAC AREA) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART-VII (ROAD) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART-VIII (STEEL GATE AND FENCING) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- IX (SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- X (AREA DRAINAGE) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- XI (FIRE ALARM) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- XII (FIRE FIGHTING) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- XIII (EXTERNAL WATER SUPPLY ) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XIV (EXTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XV (LIGHTENING PROTECTION) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XVI (AIR CONDITIONING) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XVII (SOLAR WATER HEATING SYSTEM) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XVIII (ELECTROSTATIC DISCHARGE/EARTHING) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART -XIX (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col 5 signifies this fact only.
Removing excavated soil to a distance not exceeding 50 m and depositing where directed at a level, not exceeding 1.5 metre above the starting point complete all as specified and as directed.
Removing excavated soil to a distance exceeding 50 m but not exceeding 250 m and depositing where directed at a level, not exceeding 1.5 metre above the starting point complete all as specified and as directed.
Removing excavated soil to a distance exceeding 250 m but not exceeding 500 m and depositing where directed at a level, not exceeding 1.5 metre above the starting point complete all as specified and as directed.
Removing excavated soil to a distance exceeding 1.5 KM but not exceeding 5.0 KM and depositing where directed at a level, not exceeding 1.5 metre above the starting point complete all as specified and as directed.
INTERNAL ELECTRIFICATION: S &F LED tube light ultra bright fittings, 1x20 Watt ,4 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block etc. with all assoceries intenallt prewired & including coneecting up with 2 core flexible copper conductor cable with sutable size & suitable for and mounting clamps with and including PVC squre box 75x75mm (2 Nos) complete in all respect all as specified and directed. (Make: HAVELLS model No. CRYSTAL1213T8DSTL20WLED865S GLASS or equivalent model of WIPRO/BAJAJ)
S &F LED tube light hanging type, 1x40 Watt, 4 feet, surface mounting & including coneecting up with 2 core flexible copper conductor cable with sutable size & suitable for and mounting clamps with and including PVC squre box 75x75mm (2 Nos) complete in all respect all as specified and directed. (Make: HAVELLS model No. STOUTPLUS1200BS40WLED8575 PCWH or equivalent model of WIPRO/BAJAJ)
S & F LED light fittings decorative 42 Watt recessed mounting type extruded metal/aluminium body, electronic LED driver, connector block ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size and mounting clamps etc. complete in all respect all as specified and directed. (Make: HAVELLS model No. PLUTONEO2X2PLR42WLED857S or equivalent model of WIPRO/BAJAJ)
S & F LED Security/Street light fittings 75 Watt wall mounting type extruded metal/aluminium body, and electronic LED driver, ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size etc. complete in all respect all as specified and directed. (Make: HAVELLS model No. ENDURAPEARLPLUSSC70WLED757 SASYTOPS or equivalent model of WIPRO/BAJAJ)
S&F Energy efficient BEE five star rated ceiling fan, 1200 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed. ( for Tech Building & Adm Building )
S&F Exhaust fan, heavy duty, of size 230 mm sweep metal body complete with and including suirable metallic louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan including making of suitable hole in wall complete all as specified and directed.
S&F modular flush Box 5 module complete, all as specified and as directed.
S&F Modular fan regulator stepped type, 120 watt, 2 module complete, all as specified and as directed.
S & F MCBs (C-Curve) SP 6 to 32A, breaking capacity 10KA complete all as specified and directed.
S & F MCBs (C-Curve) SPN 6 to 32A, breaking capacity 10KA complete all as specified and directed.
S & F MCBs (C-Curve) TPN 63A, breaking capacity 10KA complete all as specified and directed.
S & F Air circulator 450 mm sweep high speed, thermally protected motor, heavy duty gear box, 90 degree oscillation for wide coverage conforming to IS-2997-1964 complete all as specified and directed.
S & F LED highbay light 180 watt Baybrite saucer fitting complete with switch control gear unit, IP-66 protection, operating voltage 130 to 280 volts, specially designed for thermal management complete all as specified and directed. (Make: HAVELLS model No. BAYBRITESAUCERHBP180WLED757 WBTOLTG or equivalent model of CROMPTON/PHILLIPS)
S & F PVC conduit pipe medium grade with all connectedc fixing accessories, 50mm dia in recessed/concealed including cutting chases for conduits and making good to walls, floors for CCTV cable and Telephone cables complete all as specified and directed.
S & F PVC conduit pipe medium grade with all connectedc fixing accessories, 25mm dia in recessed/concealed including cutting chases for conduits and making good to walls, floors for CCTV cable and Telephone cables complete all as specified and directed.
S & F 100Amps, TPN with 100% neutral lighting compact air busbar trunking system suitable for 415V, 50Hz, IP-55 with conductor made from electrolytic grade copper with enclosure made from 0.8mm thick hot galvanised sheet steel in beam type section of 39x97 mm size with suspersion clamp, support brackets, earth bar, straight feeder, elbow, joints, wall bracket with ring complete system in compliance with IEC 61439-6 complete with all standard fittings & fixtures complete all as specified and directed.
S & F bus bar plug-in box 32 Amps TPN with MCB, 32 Amps 415 Volt 50 Hz, 10 KA, C Curve type complete all as specified and directed.
S & F end feed unit with end cover suitable for 100 Amps TPN Copper bus bar trunking system complete all as specified and directed.
S & F 40Amps, TPN with 100% neutral lighting compact air busbar trunking system suitable for 415V, 50Hz, IP-55 with conductor made from electrolytic grade copper with enclosure made from 0.45mm thick hot galvanised sheet steel in beam type section of 35x46 mm size with suspension clamp, support brackets, earth bar, straight feeder, elbow, joints, wall bracket with ring complete system in compliance with IEC 439 Part-II complete with all standard fittings & fixtures complete all as specified and directed.
S & F bus bar plug-in box 10 Amps SPN with MCB, 10 Amps 230 Volt 50 Hz, 10 KA, C Curve type with one meter copper flexible cable complete all as specified and directed.
S & F end feed unit with end cover suitable for 40 Amps TPN Copper bus bar trunking system complete all as specified and directed.
INTERNAL WATER SUPPLY. S&F 15 mm bore angle stop cock brass CP high pressure with capstan head, long shank screwed down complete all as specified and directed.
HANGER FLOOR / TARMAC AREA / ROAD /HARDSTANDING: Supplying laying and Stabilizing the approved soil 500mm thk ( to achieve mionimum K value of 5 Kg/Sqcm/cm as per E-in-C's Branch design )obtained from excavated from outside of MoD land,breaking the over size particles to required size including ramming and consolidating in layers not exceeding 200mm thick with suitable compactingplant such as 8 to 10 ton vibratory roller etc under optimum moisture content to achieve at least 98% of maximum dry density in accordance with relevant IS code of practices and finishing the surface to the required level,gradient etc complete all as specified and directed.
M&L Soling (or sub base ) of 150 mm spread thickness with broken boulders or quarried stone of grading 80 to 40 mm including interstices filled surface formed and rolled with 8 to 12 ton power roller and consolidated to required gradient and camber complete all as specified and as directed.
M&L for providing 300mm thick GSB Grade-II of table 400 morth, IRC specifications spreading in layers and excavation 15cm thick watering, ramming/rolling by tandem vibrator roller & transverse gradient (1:100) for achieved field compaction at least to 98% MDD (Maximum dry density ) of complete all as specifications as directed.
M&L for providing and laying 250mm thick GSB Grade-II of table 400 morth, IRC specifications spreading in layers and excavation 15cm thick watering, ramming/rolling by tandem vibrator roller & finishing to longitudinal gradient (1:150) & transverse gradient (1:100) for achieved field compaction at least to 98% MDD (Maximum dry density ) of complete all as specifications as directed.
M&L for 225mm thick (compacted thickness) wet mix mecadam (WMM) in three layers each layer 75mm thick each layer compacted separately with crushed stone aggregate of specified grade , rolled & consolidated as per required gradient and camber complete all as specified and as directed.
M&L for providing 150mm Thick DLC over a prepared sub grade with coarse and fine aggreagate confirming to IS. Size of aggreagte not exc 26.5mm (grading and other parameters as per table 600-1 of MORTH , IRC SP 49 specifcation ) design(minimum cement content shall not be less than 150 Kg /cum)with 7 days compressive strength as 10 n/ sqmm mixed in batching transported to site laid with sensor paver including spreading and compacted by using 8 to 10 tonnes vibrator roller incl necessary formwork finishing etc all as specified and as directed.
M&L HDPE sheet 400 micron laid in floor etc complete all as speciefied and as directed
M&L for 375mm thick Pavement Quality Concrete (PQC) work in Pavement / Dispersal / Taxi Link of minimum field flexural strength 45 Kg/Sqcm, (Lower Control Limit) (LCL) after 28 days of pavement slab using minimum 400 Kg Ordinary Portland Cement Grade 43 per cum with not exc 31.5mm graded crushed stone aggregate conforming to IS: 383 (grading and other parameters as specified in PS) and mixed with non circular synthetic fibre reinforcement @ 0.25% of weight of cement or as per manufacturers instuction, mixed in batching plant transported to site, laid in panels, spread and compacted using slip form paver , mechanically vibrated and bull nosing / rounding off the edges, spreading curing compund, finishing the surface by brooming without using extra cement etc including necessary form work etc complete all as specified and directed.
M&L for Forming 25mm wide Expansion (using high RPM diamond bit cutter) for depth of 375mm of PQC, joint filled with pre formed expandable synthetic filler board of approved makers , provision of closed cell, medium density, cross linked polyethylene foamed rod of 30mm dia, and filled with pitch free polysulphide grey set( minimum depth of sealent above backup shall be 25mm), confirmnig to BS -5212 (type FB) primimg the sides as recommended by manufactures instructions applying masking tape on edge to prevent accidental spillage of sealent and removing the mask in tape after sealant is applied , the sealant should have MAF used in internstional aipot in India complte all as specified. deep joint shall be full depth of PQC slab as specified as directed
M&L for forming dummy joint using diamond cutter with initial cut with 3mm blade soon after concrete sets for depth of 125mm. Widening the first saw cut to 8mm wide and 25mm from top primming 10mm with approved primer , applying mason tape on edges of joint to pavement accidental spillageof sea filling with polyurethane/ polysulphide based sealent MAF ( BS-512) to closed cell medium density, cress linkes polyethylene foam back up rod of 10mm dia , for complte width of the join and removing the masking tape after filling of sealent and as specified and as per the directions of the manufacturer, complete all as and as directed
M&L for forming construction joint 30mm deep ×10mm wide using diamond cutter with close cell , with medium density , cross linked polyethyelene foam back up rod of 12mm dia , applying bond breaker tape on top of back up rod for complte width of the joint, priming top 10mm with specified primer and filling with polyethane based sealent (BS5212), applying masking tape on edges of joint to to prevent accidental spillage of sealant and removing the masking tape after filling of sealant and as specified and as adierected . The rate shall include cost of 12mm dia bar
M&L polyurethine paint hangar flooring 2mm EPU system (100 micron primer, 2mm epoxy screed, 1mm self leveling EPU top coat of approved make) including cleaning the existing surface using suitable medium,fillingof dense and cracks with suitable apoxy putu for mortar followed by application of apoxy primer (incl marking of lines, arrows over painted surfaces) all as the manufacturers instructions and as directed.
M&L for preparing new concrete/ bituminous surfaces and painting lines, dashes (continous/uninterrupted) arrows, letters,etc n,exceeding 10cm width with two coats of water based road marking paint in white ,golden,yellow, orage or red colour over a coat of primer comlete all using road painting machine complete all as specified and directed.
Supply only Polyester non circular synthetic fibre, 6/12mm long with circum-circle diameter 30-35micron, designed for melting point 240-260 degree Celsius and having specific gravity 1.34 to 1.40 etc complete all as specified and directed. Make:- Reliance (Recron 3S) or equivalent as approved make as per list of make.
SECURITY FENCING AND GATE:- S&F CONSEC-ZAL Super Razor punched barb tape (SRPBT) Aluminium base helix coil with and including necessary GI fixing clips for securing complete all as specified and directed with following specifications:- (i) Dia of coil (when unstretched) - 610mm (ii) No of spirals-50 turns per coil (iii) Weight of each coil with hessian pack - 8.50 Kg (+/- 0.5) (iv) Stretch Length : 6 Spirals / RM (v) Coverage per coil - 8 RM (vi) Central core wire :- Made from 2.60 mm dia GI- H.T.S.S. wire as per IS-4454 galvanised as per IS-2629. (vi) Razor Punched Strip:- Razor punched tape is CONSEC-ZAL Steel comprising of Aluminium base with Zinc coating @ 150 gm/Sqm conforming to ASTM A-792/A-792M with additional primer treatment of Epoxy/ Polyurethane & Final Paint Top coat of Caulfield green shade (BSL 139) by Hot Dipping process. (Note:- Running length of the fencing shall be measured for payment purpose.)
SEWAGE DISPOSAL:- Construction of RCC septic tank conventional type designed to carry sewage and sullage water, excavation in ordinary soil, foundation PCC (1:4:8) type D2 (using 40mm graded stone aggregate), RCC M30 (design mix) using 20mm graded stone aggregate for RCC wall,base slab,baffle wall and roof slab incl beam etc vent shaft,manhole openings with cover connection etc complete with effective depth of 1.50m and overall depth of 3.0m for 100 users complete all as specified and as shown on drawings.
Construction of Soakage well exc. In ordinary soil , foundation in PCC (1:3:6) type C2 (using 40mm graded stone aggregate), wells of honey combed and soil in RCC M25 (design mix) using 20mm graded stone aggregate, including intercepting chamber, screen chamber brick work in CM, RCC cover slab in M25 /RR masonary/filled with brick bats, complete of size 3m dia×4.5m deep complete all as specified and as shown on drawings.
M & L for RCC precast cover slabs RCC M-25 (Design Mix) (using 20 mm graded stone aggregate) including necessary form work with plain fair faces and set in cement mortar (1:4) complete all as specified and as directed. (Note: Reinforcement shall be measured and paid separately.)
FIRE ALARM:- Supply and fix the indoor detector complying with and type certified to EN -54 Addressable type Quadband (Triple IR+ Visible ) technology (add up to cost of module to be a complete set,the type of module shall be relay type module)with self built intelligence complete all as specified and directed.
Supply, installation, commissioning and testing of RTU Logic development for Central Monitoring through wireless communication at Master Control Station which include the development logic for fire alarm which comes from Addressable fire alarm control panel complete all as specified and directed.. (Nore: The RTU panel should have reset facility, full display like main fire alarm control panel.)
Supply install testing & commissioning Of flow chart based programmable RTU along with battery backup upto one hours in case of power fail & protection through isolation Transformer & compaitable with GSM modem with the specificationn as appended below:- (a) Power: 85V-264V AC,50Hz (b) Memory: 8-GB SD card storage (c) Communication port -internet port, USB port, RS -232 port RS-485 port. (d) Ingress protction IP-55 (e) Digital input/Output-Optically Isolated. (f) Local Display, membrane key board and data storage (g) Compatibility with GSM Modem. (h) Isolation transformer for RTU protection -01 No.
Supply, installation, commissioning and testing of loop isolator certified to EN-54 and LPCB approved, Module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected complete, all specified and directed.
M&L for submain wiring with two single core HFFR/ZHFR cable with stranded copper conductor of 1.5 Sqmm size and drawn intoand including 20mm bore concealed steel conduit, medium grade with all fittings such as bend, elbow, tee, joint complete all as specified and directed. (Note : Two runs of 1.5 Sqmm cable and one run of steel conduit shall be measured as one run length.)
M&L for submain wiring with two single core HFFR/ZHFR cable with stranded copper conductor of 2.5 Sqmm size and drawn intoand including 20mm bore concealed steel conduit, medium grade with all fittings such as bend, elbow, tee, joint complete all as specified and directed. (Note : Two runs of 2.5 Sqmm cable and one run of steel conduit shall be measured as one run length.)
Supply, installation, commissioning and testing of wireless modem suitable for GSM based communication system to be mounted in RTU enclosure and shall be installed at proposed buildings (it should also be used as a GSM based autodialer, to be installed with the main control panel having minimum 10 Nos mobile connection facility and atleast memory for voice recording of minimum five monuted data) including providing one GSM Sim Card (including Rental and SMS charges for period of two years) complete all as specified and directed.
Supply, installation, commissioning and testing of MIMIC type panel box of size 600mm(L) x 600mm(H) x 200mm(W) for fire indication status through LED (Green/Red) made out of 1.6 mm thick CRCA sheet ,duly painted with two coats of powder coated paint internally & externally on of the surface complete all as specified and directed. (a) Operating Voltage-220V (b)Led Capacity-20 to 500 Led (c) Power consumption-30watt (d) Temperature-0 to 50 degree celsius. (e) Relative humidity< 95%.
Supply and fix of amplifier suitable 100 watt,230 Volts, AC ,50 HZ complete all as specified and directed. (a) Power source:AC 220V,50HZ ,DC -12V battery (b) Power consumption:100watt. (c) Channels: 5 (d) Color:Black (e) Audio input/output:- 5x MIS 0.60mV/4.7 Kohm,1 x Aux 100mV/ 4.70 Kohm.
Supply and fixing of Zone Monitor module compatible with Fire Alarm Control Panel complete all as specified and directed.
FIRE FIGHTING:- M & L for providing, testing and commissioning of 100mm bore (Nominal Bore) for heavy class MS pipe as per IS : 1239 marked with all necessary fittings like tees, elbows, flanges, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary MS structural supports & clamping arrangement including painting with two coats of compatible synthetic enamel paint over a coat of Zinc chromate primer complete, all as specified and directed.
M & L for providing, testing and commissioning of 150mm bore (Nominal Bore) for heavy class MS pipe as per IS : 1239 marked with all necessary fittings like tees, elbows, flanges, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary MS structural supports & clamping arrangement including painting with two coats of compatible synthetic enamel paint over a coat of Zinc chromate primer complete, all as specified and directed.
S & F Pressure guage 100mm dia with ball valve of pressure 25KG/Sqcm complete, all as specified and directed.
S & F fire hydrant landing valve type A (single head outlet) of 63 mm dia confirming to IS-5290 complete, all as specified and directed.
S & F fire hydrant landing valve type B (double head outlet) of 63 mm dia confirming to IS-5291 complete, all as specified and directed.
S & F hose box for keeping 2 Nos hose pipe of length 15 meter each, branch pipe, nozzle, coupling of MS sheet of thickness 2.0 mm complete, all as specified and directed.
S & F hose box for keeping 2 Nos hose pipe of length 30 meter each, branch pipe, nozzle, coupling of MS sheet of thickness 2.0 mm complete, all as specified and directed.
S & F 63mm dia 15 meter long rubberised fabric reinforced rubber lined hose including gun metal male & female instataneous coupling, hose confirming to IS 636 type II and coupling confirming to IS 903 complete, all as specified and directed.
S & F 63mm dia 30 meter long rubberised fabric reinforced rubber lined hose including gun metal male & female instataneous coupling, hose confirming to IS 636 type II and coupling confirming to IS 903 complete, all as specified and directed.
S & F hose box for hose reel of 20mm size of 30 meter length complete with coupling branch pipe and nozzel MS sheet 2 mm thickness complete, all as specified and directed.
S & F hose reel of 20mm dia and 30 meter length conforming to IS 5132 complete, all as specified and directed.
S & F branch pipe with nozzle of 20mm dia for hose reel conforming to IS 8090 complete, all as specified and directed.
Supply, commissioning and testing of first aid fire hose reel wall mounting swinging type complete with drum, bracket, 20mm dia. 30m long high pressure hose reel tubing with gunmetal shutoff nozzel confirming to IS:8090-1976. The hose reel shall be as per IS:884-1985 complete all as specified and directed.
Supply, fixing, commissionng and testing gun metal 63mm bore short branch pipe (ISI marked) of standerd length with nozzle as required complete all as specified and directed.
M&L for making fire point with shed complete all as directed and comprising of the following items :- (a) Mechanical foam Extinguisher of capacity 9.0 Ltrs complete all as per (IS :15683) - 02 Nos. (b) Wheeled Fire extingusher C02 type 25KG capacity all as per(IS:16018)- 01 No. (c) Wheeled mechanical foam extinguisher,45 Ltrs capacity trolly mounted type as per IS:16018 - 01 No.(d) Weeled dry powder type fire extinguisher of capacity 25 Kgs all as per (IS:16018)-01 No. (e) Dry powder fire extinguisher of 9 Kgs capacity all as per(IS:15683)-02 Nos.
M&L for making fire point with shed complete all as directed and comprising of the following items :- (a) Mechanical foam Extinguisher of capacity 9.0 Ltrs complete all as per (IS :15683)-02 Nos. (b) Light weight Squeeze grip type CO2 Fire extingusher 3KG capacity all as per(IS:16018)- 02 Nos. (c) Dry powder(ABC) type fire extinguisher of capacity 6.0 Kgs all as per (IS:15683)-02 Nos.
M&L for making fire point complete all as directed and comprising of the following items :- (a) Light weight Squeeze grip type CO2 Fire extingusher 4.5 Kg capacity all as per (IS:15683) - 01 No. (b) Dry powder (ABC) type fire extinguisher of capacity 9.0 Kg all as per (IS:15683) - 02 Nos.
S & F 100mm bore CI Foot valve conforming to IS 4038 complete all as specifeid and directed.
S & F 150mm bore CI Foot valve conforming to IS 4038 complete all as specifeid and directed.
M & L for construciton of brick masonry valve pit / chamber of internal dimension 120 cm x 120 cm x 120 cm depth with sub class 'B' bricks in CM (1:4) and 15 mm thick plastering in CM (1:4), PCC (1:4:8) type D2 (using 40 mm graded breoken stone aggregate) as in foundaitn lean concrete, PCC (1:2:4) type B1 ( using 20 mm graded broken stone aggregate) as in bedding and copping, MS frame with 50 x 50 x 6 mm angle iron, 3.15 mm thick MS sheet cover plate with locking arrangement hinges and two coats of synthetic enamel paint over a coat of red oxide primer including preparation of steel surface, three coats of white wash to plastered surface (exposed to view), excavation in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 m complete all as specified and directed.
Supply, installing, commissioning and testing terrace pump set, 440V, 3 phase 50HZ conforming IS-12469: 1988 with CI cassing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for 450 LPM discharge at 36 mtr with star delta starter control panel for automatic operation complete, all as specified and directed.
Design, supply ,installation, commissioning and testing of automatic foam extinguishing system having a foam tank made of stainless steel of suitable capacity as per design having induction delivery for hanger solenoid valves operation through detectors of automatic fire alaram system (smoke detectors), seamase connection,GM coupling with builts in tvrv housed in MS box with front glass Note:-(a) water from fire fighting pump of capacity 2850LPM at 70 mtr head considered in this schedule hear in before installed at near by pump house will be made available near to foam extinguishing system building through 150/200 mm MS pipe line,however contractor has to be design and give the reqd pressure and quantity of water for the above system the hanger shall have the arrangement of remotly operated oscillaiting type moinitor (with long application) these monitor shall be so located at diagonally opposite position for hanger area arrange tp permit application of water of fire fighting foam into interior of the aircraft/helicopter located in the hanger only remotly operated oscillating type monitor (with long range application ) may be inside the main hanger area at center positionon either side the monitor should be capable of discharging water with minium throw of 50 meter with minimum quantity of 200 ltrs/minute at 7kg/cm2 foam liquid concentrate shall be supplied from a central distribution system or from stationary foam liquid concentrate containers fitted with proportion devices complete all as specified and directed.
M & L for stand post type fire hydrant, conforming to IS 908: 1975, consisting of two Class- I type sluice valves with cap, road surface boxes, a duck foot bend, flange riser and an 80 mm NB CI flanged stand post column of 1.5 m height, perfectly water tight under a hydraulic pressure of 200 m head along with coating and painting complete as specified and directed.
S&F water cum foam monitors of size 63mm as per IS 8442 stand post type with material of construction beign in carbon steel/stainless with flanged inlet with jet and spray type hydro foam nozal/aluminium barrel type 63mm size suitable for operation at pressure 100 PSI complete as specified and directed.
S & F Sprinkler Pendant type (Standard response) as per IS:15106/TAC guidelines 68 degree temperature rating complete, all as specified and directed.
S & F Air release single valve (Zoloto/ZIP) of 100mm dia including. necessary support and painting with two coats of enamel paint over a coat of primer etc. complete, for wet riser termination complete, all as specified and directed.
S & F alarm valve for sprinkler system size 150mm dia ,cast iron body complete all as specified and directed.
Supply, installation, testing and commissioning of Adequate Pressure switch for Hydrant pump, jockey pump and Diesel Engine Driven pump including necessary wiring and cut off Hydrant pump, jockey pump and Diesel Engine Driven pump including necessary wiring and cut off valve up to central panel & other material as described in specifications complete all as specified and directed.
S & F heavy duty ,'C' class MS ERW pipes of 25mm bore (ERW quality conforming to IS 1239), ISI marked with screwed or welded joints, including all fitting, supported by galvanized hangers (Size and Spacing as per drawing) including anchor fasteners for fixing in ceiling testing to 15 kg/Sqcm pressure, including painting with two coat of approved enamel paint over a coat of zinc dichromate primer, making direction arrows and labelling etc.complete, all as specified and directed.
All as per item No. 19.088 here-in-before but for 50mm bore complete.
All as per item No. 19.088 here-in-before but for 80mm bore complete.
All as per item No. 19.088 here-in-before but for 100mm bore complete.
EXTERNAL WATER SUPPLY: Designing supply, installation, testing abd commissioning iron removal pressure feed type filtration plant 13500 GPH withstand to pressure 10 Kg/cm sq with catalytic and filtration media (as required size and grade/mesh to obtain potable water recommended parameters) including MS frontal pipe(duly welded) ,cocks, valves (inlet, outlet, back wash, rinse and bypass complete as per manufacture's instruction) provision of man hole, hand hole strainer including air vent system, coagulant feeder with accessories, oxidation chamber with media (MnO2) with all accessories suitable capacity with all standard fittings and fixture, pressure gauge,Compressor for compress air supply and RCC/PCC foundation as per OEM recommendation, drainage system and connected to rising and delievery system including painting and writing complete. The technical detail of oxidation chamber and multigrade filter are as given below-
Contd/-..... Item No 19.092 Oxidation Chamber Feed Flow- 60.75 cum/hr Operating pressure- 4.5 kg/sq cm Max allowable pressure drop- 1.5 Kg/sqcm vessel size in mm- 1000X 1000 mm Material of vessel- MS Frontal pipe line size- 150 mm Media Type- Maganese di oxide (MnO2) Thickness in mm-(Shell and dish ends)- 8 mm Media Quantity- 800 Kg Multigrade filter Flow rate- 60.75 cum/hr Operating pressure- 4.5 Kg/sq cm Max allowable pressure drop- 1.5 Kg/sqcm Continuous duty cycle- 48 hrs Backwash- 20 min Rinsing- 10 min Filtering media detail- Media type- Mixed Sand Depth of sand- 1600 Kg Depth of gravels support- 2000 Kg Vessels Details- Type cylinder- Vertical Dimentions I mm ( DiaXHeight)- 2000X2100 mm Free boared for back wash- 50% Materials- MS Thicness in mm (shell and dish end)- 8/10 mm
Drilling Trial Bore hole by Direct Rotary mechanical method through any kind of soil, boulders /reverse circulation method of size 150mm (6") dia and upto 150m depth, as required at site, below ground level in any kind of soil strata including hard stone/boulder complete all as specified on IS 2800 and directed.
Reaming of bore well from 150 mm dia to 525 mm dia hole in three steps from 200 mm to 350 mm, 350 mm to 450 mm and 450 mm to 525 upto 60 m depth below the ground level from the top of groung complete all as specified and directed.
Reaming of bore well from 150 mm dia to 450 mm dia hole in two steps from 200 mm to 350 mm and 350 mm to 450 mm for depth exceeding 60m but not exceeding 150m below the ground level from the top of groung complete all as specified and directed. (Note: In case additional reaming of bore well is required due to site condition beyond 150 metres below ground level, the same will be measured and paid for under Sl item No. 19.096 to 19.098. No extra claim what so ever shall be entertained by the Dept. at later stage on this account.)
M & L for electric logging of bore well complete including all tools and fixture required for same complete all as specified and directed.
S & F mild steel bail plug assembly suitable for 200 mm bore casing pipe internal threaded with strong iron hook, screwed and welded to casing pipe as per IS 2800 complete all as specified and directed.
Supply, fixing and jointing 250 mm x 200 mm mild steel reducing socket having wall thickness not less than 7.3mm, fitted to casing pipe as per IS 2800, including two coats of black bituminous paint over a coat of Red oxide Zinc chrome both externally and internally complete all as specified and as directed.
Supply, welding, lowering and fixing in position 250 mm (10”) bore, ISI marked casing pipe of wall thickness 7.3mm (minimum) ERW MS black pipe heavy duty screwed and socketed in length upto 6m, conforming to IS 4270 – 2001 including painting with two coats of black bituminous paint over a coat of red oxide zinc chrome primer both externally and internally complete all as specified and directed.
Supply, welding, lowering and fixing in position 200 mm (8”) bore, ISI marked casing pipe of wall thickness 7.3mm (minimum) ERW MS black pipe heavy duty screwed and socketed in length upto 6m, conforming to IS 4270 – 2001 including painting with two coats of black bituminous paint over a coat of red oxide zinc chrome primer both externally and internally complete all as specified and directed.
Supply assembling lowering and fixing low carbon galvanized (LCG) steel strainer pipe (slotted pipe) 200 mm nominal bore of wall thickness of 8 mm as per IS:8110:2000 and having cage type wire wound screen ‘V’ shaped profile in suitable length having slots of size 0.75 mm width including necessary end coupling complete all as specified and directed.
Supply, placing, packing and surrounding with thoroughly washed pea gravels of size 2mm to 4.5mm as approved by GE throughout annular space between bore hole and assembly pipes form bottom level up to the top of bore well complete all as specified and as directed. (Note : Measurement of pea gravel shall be taken in measuring box at site and the same shall be reordered in MB duly signed by Engineer - in - Charge before packing surrounding the tube well assembly. From the above volume, 10% (Ten percent) of volume shall be deducted and volume there after worked out for the purpose of payments.)
Development of bore well by disel engine operated air compressor of suitable capacity till sand/Mud free clear water of potable quality is obtained for a period of 72 hours minimum complete all as specified and as directed. (Note : (i) The unit rate quoted shall deemed to be inclusive of hire charges of plants & machinery required for development of bore well including their transportation charges upto the site of work, fuel & lubricant and operator etc required complete in all respect. (ii) Total development of bore well shall before a period of 72 hours excluding 2 hours rest period after every 8 hours of continuous development of bore well.)
Testing of tube well for yield after development by continuosly pumping for 16 hours to determine safe pumping yield complete all as specified and directed.
Supply, lowering, commissioning and testing of manufacturer assembled and electric driven submersible pump set mix flow type with high graded CI bowl, Stainless steel shafts, Bronze impellers etc of pump dia 200 mm capable to deliver 850 LPM clear water at 79 Meter head with electric motor 200 mm dia three phase 415 volt of cap 25 HP (18.5 KW) as per, OEM recommendations suitable for 100 mm delivery pipe complete all as specified and directed.
Supply, laying/ fixing along the column pipe or passing through pipes or laid under floor of through walls etc jointing and testing of PVC insulated submersible cable 10 Sq mm 3 core flat LT 1100 volt grade heavy duty ISI marked with copper conductor and overall served with an outer sheath of PVC complete all as specified and directed.
S&F round strand steel wire rope RHO/LHO/RHL/LHL conforming to IS: 2266/02 dia 12 mm 1770 N / Sqmm tensile and connected clamp nut bolts fixed complete all as per specified and directed.
Supply and lowering MS column pipe (medium grade) confirming to IS of size 100 mm dia bore approx 3 m length each duly both ends flanged/ drilled by welding with special provision such as MS clamps and MS flange (size shall be as per IS specifications) and should have two cuts for fixing submersible cable and connecting complete with rubber gasket and nuts bolts etc complete and painted internally and externally with two coat of non corrosive non toxic bituminous paint complete all as specified and directed.
Testing of water for all parameter chemicals and bacteriology aspects from RRL jorhat/ DRL tezpur or any GOV Approv/recommended laboratory as approved by GE.
Supply , install, testing and commissioning of LT outdoor Feeder pillar Box AC 415 V , 50 HZ 3 Phase 4 wire, totally enclosed self supporting structure / cubicle , fully compartmentalized type, weather proof, protection IP 54, suitable for outdoor use double door type, with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick CRCA steel sheet of minimum Size ( 0.9x0.9 x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm, with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , with sloping canopy at top , double hinged doors at front with suitable locking arrangement , provision of louvers at sides , duly powder coated , complete comprising of following accessories:-
Contd/-..... Item No 19.111 BUSBAR :- Aluminium bus bar 150 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- MCCB 4 pole 415 Volts of breaking capacity of 16 KA of 100 Amps with Fixed thermal and Fixed magnetic setting - 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 31/2 digital display, including CT having CTR 100/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 63 Amps with Fixed thermal and Fixed magnetic setting - 01 No (Outgoing for submersible pump). (b) MCB of 3 pole , 415volts of capacity 32 Amps with breaking capacity of 10 KA C Curve- 02 Nos. (Outgoing for 01 Pump House Building & 01 for bldg security light). (c) Digital time switches 415 V three Phase of 16 Amp rating with contactor fitted inside steel enclosure - 01 No. (d) Star-delta starter with overload protection, single phase preventor suitable for 25 HP submersible pump set - 01 No.
Supplying, laying in trenches, under floor, under road, connecting, jointing and testing 100 mm bore (Nominal) Ductile Iron pressure pipe centrifugally cast ISI marked, with socket and spigot ends confirming to IS 8329/2000 standard length, of K7 specification provided with internal cement mortar lining with seal coat of compatible epoxy based material and externally painted with metallic zinc with finishing layer of bituminous paint for potable water complete with and including EPDM rubber ring joints as per IS:5382 (1985) all as specified and directed.
All as per item No. 19.113 here-in-before but for 150mm bore complete.
Supplying, laying in trenches, under floor, under road, connecting, jointing and testing 100 mm bore (Nominal) Ductile Iron pressure pipe centrifugally cast ISI marked, with socket and spigot ends confirming to IS 8329/2000 standard length, of K9 specification provided with internal cement mortar lining with seal coat of compatible epoxy based material and externally painted with metallic zinc with finishing layer of bituminous paint for potable water complete with and including EPDM rubber ring joints as per IS:5382 (1985) all as specified and directed
M & L for ductile iron fitting as per IS:9523 such as Bends any type any radius, tapers, tee pieces, double branch, collar caps, plug etc upto 150 mm bore socket and spigot end pipe complete all as specified and directed.
M&L for construction of brick masonry valve pit chamber of internal dimension 900 x 900 x 900 mm depth with sub class 'B', old size, in CM (1:4) and 10mm thick plastering in CM (1:4) ,PCC (1:4:8) type D2 (using 40mm graded broken stone aggregate ) as in foundation lean concrete ,PCC (1:3:6) type C1 (using 20mm graded broken stone aggregate) as in bedding and copping MS frame with 50x50x6mm angle iron 5mm thick MS sheet cover plate with locking system ,hinges and two coats of synthetic enamel paint over one coat of red oxide primer including preperation of surface ,three coats of white wash on plastered suface (exposed to view) including necessary excavation in soft loose ,soil ,returning filling in and removal of surplus soil to a distance not excedding 50 m complete all as specified and directed.
M&L for construction of brick masonry valve pit chamber of internal dimension 600 x 600 x 600 mm depth with sub class 'B', old size, in CM (1:4) and 10mm thick plastering in CM (1:4) ,PCC (1:4:8) type D2 (using 40mm graded broken stone aggregate ) as in foundation lean concrete ,PCC (1:3:6) type C1 (using 20mm graded broken stone aggregate) as in bedding and copping MS frame with 50x50x6mm angle iron 5mm thick MS sheet cover plate with locking system ,hinges and two coats of synthetic enamel paint over one coat of red oxide primer including preperation of surface ,three coats of white wash on plastered suface (exposed to view ) including necessary excavation in soft loose ,soil ,returning filling in and removal of surplus soil to a distance not excedding 50 m complete all as specified and directed.
Supplying, installing, testing and commissioning silent Diesel Engine Driven generating set 415 volt ,3 phase 4 wire 0.8 PF,engine as per IS 10001/10002 and alternator as per IS 13364 complete with relay panel and switch gears for Automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms including PCC foundation complete with all standard accessories of capacity 62.5 kVA comprising and including of following- (A) DIESEL ENGINE: Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500RPM under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation. Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling and coupling guard complete with following-
Contd/-..... Item No 19.119 (a) Radiator with blower fan or heat exchangar with guard. (b) Pipe coupling for engine cooling system piping. (c ) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter complete with first filling of lube oil (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator. (n) Exhaust piping made out of STIC C class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (o) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet 30 gauge for the entire length of exhaust pipe. (p) First fill of oil, coolant and diesel during commissioning and 12 hours testing. (q) Interconnecting copper cabling of adequate capacity batteries control. (r ) Fuel pipe class (s) Self starter (t) Electric operated electronic governor. (u) Fuel injection pump.
Contd/-..... Item No 19.119 (v) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) Battery as per manufacturer recommendation. (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed -1500Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (viii) Safety control (Trip and indication). (ix) High water temperature (x) Low lube oil temperature (xi) Overspeed stop (B) ALTERNATOR- Brushless AC alternator, 3 Phase, 415 Volt, 4 wire, rated for output of 62.5 KVA ,minimum power factory 0.8, 1500 RPM , insulation class 'H' salient pole, revolving field,single bearing automatic voltage regulator and directly coupled with engine.
Contd/-..... Item No 19.119 (E) BASE PLATE: Common fabricated base frame for engine & alternator made from structural Steel channel, jerk proof on PCC (1:2:4) type B1 foundation including adequate number of anti-vibration pads in adequate quantity all as per the recommendation of the manufacturer. (F) DIESEL STORAGE TANK: Fuel tank of MS sheet of capacity not less than 12 Hrs continuous operation on full load with fuel level guage, drain plug, locking arrengements, etc including connection to Engine through fuel filter/ manual feed pump as per manufacturer recommendation. (G) ACOUSTIC ENCLOSURE:Sheet metal fabricatedcope type silent enclosure manufactured on CNC machines as per CPCB norms and power coated after seven tank process, the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distance of 1 M at 75 % load under field condition and 70DB at 3 M from Gen set when DG set is working at full load along with testing performance, laveling certification etc as laid down in GSR No.371(E) dt 17 May 2002. (H) FOUNDATION: Foundation/plinth shall be provided as per manufacturers recommendation with PCC (1:2:4) type B1. (Note:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor). (I) MISC: Tool kit operation, maint cat, spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacturers standard practice.
Boring of holes under road,pavement,hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4mpa working pressure all as directed.
Supplying, installing, testing and commissioning silent Diesel Engine Driven generating set 415 volt ,3 phase 4 wire 0.8 PF,engine as per IS 10001/10002 and alternator as per IS 13364 complete with relay panel and switch gears for Automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms including PCC foundation complete with all standard accessories of capacity 750 kVA comprising and including of following- (A) DIESEL ENGINE: Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500RPM under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation. Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling and coupling guard complete with following-
Contd/-..... Item No 19.126 (a) Radiator with blower fan or heat exchangar with guard. (b) Pipe coupling for engine cooling system piping. (c ) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter complete with first filling of lube oil (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator. (n) Exhaust piping made out of STIC C class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (o) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet 30 gauge for the entire length of exhaust pipe. (p) First fill of oil, coolant and diesel during commissioning and 12 hours testing. (q) Interconnecting copper cabling of adequate capacity batteries control. (r ) Fuel pipe class (s) Self starter
Contd/-..... Item No 19.126 (t) Electric operated electronic governor. (u) Fuel injection pump. (v) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) Battery as per manufacturer recommendation. (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed -1500Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (viii) Safety control (Trip and indication). (ix) High water temperature (x) Low lube oil temperature (xi) Overspeed stop (B) ALTERNATOR- Brushless AC alternator, 3 Phase, 415 Volt, 4 wire, rated for output of 750 KVA ,minimum power factory 0.8, 1500 RPM , insulation class 'H' salient pole, revolving field,single bearing automatic voltage regulator and directly coupled with engine.
Contd/-..... Item No 19.126 (E) BASE PLATE: Common fabricated base frame for engine & alternator made from structural Steel channel, jerk proof on PCC (1:2:4) type B1 foundation including adequate number of anti-vibration pads in adequate quantity all as per the recommendation of the manufacturer. (F) DIESEL STORAGE TANK: Fuel tank of MS sheet of capacity not less than 12 Hrs continuous operation on full load with fuel level guage, drain plug, locking arrengements, etc including connection to Engine through fuel filter/ manual feed pump as per manufacturer recommendation. (G) ACOUSTIC ENCLOSURE:Sheet metal fabricatedcope type silent enclosure manufactured on CNC machines as per CPCB norms and power coated after seven tank process, the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distance of 1 M at 75 % load under field condition and 70 DB at 3 M from Gen set when DG set is working at full load along with testing performance, laveling certification etc as laid down in GSR No.371(E) dt 17 May 2002. (H) FOUNDATION: Foundation/plinth shall be provided as per manufacturers recommendation with PCC (1:2:4) type B1. (Note:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor). (I) MISC: Tool kit operation, maint cat, spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacturers standard practice.
Supplying, installing, testing and commissioning silent Diesel Engine Driven generating set 415 volt ,3 phase 4 wire 0.8 PF,engine as per IS 10001/10002 and alternator as per IS 13364 complete with relay panel and switch gears for Automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms including PCC foundation complete with all standard accessories of capacity 1010 kVA comprising and including of following- (A) DIESEL ENGINE: Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500RPM under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation. Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling and coupling guard complete with following-
Contd/-..... Item No 19.131 (a) Radiator with blower fan or heat exchangar with guard. (b) Pipe coupling for engine cooling system piping. (c ) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter complete with first filling of lube oil (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator. (n) Exhaust piping made out of STIC C class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (o) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet 30 gauge for the entire length of exhaust pipe. (p) First fill of oil, coolant and diesel during commissioning and 12 hours testing. (q) Interconnecting copper cabling of adequate capacity batteries control. (r ) Fuel pipe class (s) Self starter
Contd/-..... Item No 19.131 (t) Electric operated electronic governor. (u) Fuel injection pump. (v) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) Battery as per manufacturer recommendation. (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed -1500Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (viii) Safety control (Trip and indication). (ix) High water temperature (x) Low lube oil temperature (xi) Overspeed stop (B) ALTERNATOR- Brushless AC alternator, 3 Phase, 415 Volt, 4 wire, rated for output of 1010 KVA ,minimum power factory 0.8, 1500 RPM , insulation class 'H' salient pole, revolving field,single bearing automatic voltage regulator and directly coupled with engine.
Contd/-..... Item No 19.131 (E) BASE PLATE: Common fabricated base frame for engine & alternator made from structural Steel channel, jerk proof on PCC (1:2:4) type B1 foundation including adequate number of anti-vibration pads in adequate quantity all as per the recommendation of the manufacturer. (F) DIESEL STORAGE TANK: Fuel tank of MS sheet of capacity not less than 12 Hrs continuous operation on full load with fuel level guage, drain plug, locking arrengements, etc including connection to Engine through fuel filter/ manual feed pump as per manufacturer recommendation. (G) ACOUSTIC ENCLOSURE:Sheet metal fabricatedcope type silent enclosure manufactured on CNC machines as per CPCB norms and power coated after seven tank process, the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distance of 1 M at 75 % load under field condition and 70DB at 3 M from Gen set when DG set is working at full load along with testing performance, laveling certification etc as laid down in GSR No.371(E) dt 17 May 2002. (H) FOUNDATION: Foundation/plinth shall be provided as per manufacturers recommendation with PCC (1:2:4) type B1. (Note:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor). (I) MISC: Tool kit operation, maint cat, spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacturers standard practice.
Supply , Installation, Testing & Commissioning of 2000 A TPN with 100% neutral ,1000V, 50 Hz , IP-55 for Indoor & IP-66 for outdoor Sandwich type Super Compact Busduct compliance with IEC 60439 part II with Busbar made from Aluminium alloy with Cu Plating + Tin Plating over the whole length of Conductor insulated by Class F ( 155 deg) PET insulation with 1.5mm thick steel housing ( Size 130x380mm) with 150KA for 1 Sec short circuit with stand capacity including junction monoblock, joint cover, Vertical/ Horizontal Elbow/ bend, Flanged End, Adopter Boxes, supports with two runs of 50x6mm Aluminium External Earth Busbar with nuts & bolts and system design in compliance with latest IEC- 61439-6, Electro-tinned Baided Jumpers with silver coated sockets and suitable for termination between Busduct & Transformer/ Panel complete with & including all fixing accessories complete all as specified and directed.
Supply, installation, testing and commissioning of floor mounted LT indoor panel board AC 415 V , 50 Hz 3 Phase 4 wire of totally enclosed self supporting structure / cubicle , fully compartmentalized type ,suitable for indoor use , with bottom cable entry with suitable cable glands structure made out of 2.00 mm thick CRCA steel sheet of Size minimum ( 2.0 x 2.8 x 0.6) m with angle iron frame work and legs of MS 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , hinged doors at front with suitable locking arrangement , provision of louvers at sides , duly powder coated , complete for accomodating and including following accessories :- (Main Panel)
Contd/-..... Item No 19.137 BUSBAR :- Electrolytic copper bus bar 3000 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- ACB microprocessor based released O/L/S/C & E/F protection & metering display manual Draw out type 4 pole 415 Volts breaking capacity 50kA of 2000 Amps - 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) ACB microprocessor based released O/L/S/C & E/F protection &metering display manual Draw out type 3 pole 415 Volts breaking capacity 50kA of 1250 Amps - 01 No (For APFC Panel) (b) MCCB of 3 pole of capacity 500 Amps with breaking capacity of 36 KA fixed thermal and fixed magnetic setting - 01 No (For Hangar No. 01 left Panel). (c) MCCB of 3 pole of capacity 400 Amps with breaking capacity of 36 KA fixed thermal and fixed magnetic setting - 01 No (For Hangar No. 01 right Panel) (d) MCCB of 3 pole of capacity 200 Amps with breaking capacity of 36 KA fixed thermal and fixed magnetic setting - 01 No (Hangar No. 02 left Panel). (e) MCCB of 3 pole of capacity 250Amps with breaking capacity of 36 KA fixed thermal and fixed magnetic setting - 01 No (Hangar No. 02 right Panel).
Contd/-..... Item No 19.137 (f) MCCB of 3 pole of capacity 160 Amps with breaking capacity of 36 KA fixed thermal and fixed magnetic setting - 02 Nos (For Ware house panel and fire fighting pump 90HP). (g) MCCB of 3 pole of capacity 125 Amps with breaking capacity of 16 KA fixed thermal and fixed magnetic setting - 01 No (For compressor panel). (h) MCCB of 3 pole of capacity 63 Amps with breaking capacity of 16 KA fixed thermal and fixed magnetic setting - 01 No (For Pump house). (j) MCCB of 3 pole of capacity 25 Amps with breaking capacity of 16 KA fixed thermal and fixed magnetic setting - 06 Nos (For MES sub stn,Road way lighting Right side & left side incl lighting and Fencing Security lighting left side & right side). (k) Digital time switches 415 V three Phase of 16 Amps rating with contactor fitted inside steel enclosure - 02 Nos.
Supply, installation, testing and commissioning of LT outdoor Feeder pillar Box AC 415 V , 50 HZ 3 Phase 4 wire, totally enclosed self supporting structure / cubicle , fully compartmentalized type , weather proof , protection IP 54 , suitable for outdoor use double door type , with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick CRCA steel sheet of minimum Size ( 1.5x1.8 x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm, with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , with sloping canopy at top , double hinged doors at front with suitable locking arrangement , provision of louvers at sides , duly powder coated , complete for accomodating and including following accessories:- (For Hangar No. 01 left Panel)
Contd/-..... Item No 19.140 BUSBAR :- Copper bus bar 750 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- MCCB 4 pole 415 Volts of breaking capacity of 36 KA of 500 Amps with Fixed thermal and Fixed magnetic setting - 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) MCCB 3 pole 415 Volts of breaking capacity of 36 KA of 400 Amps with Fixed thermal and Fixed magnetic setting - 01 No (For Hangar No 1 for Ground Floor Left Side) (b) MCCB of 3 pole , 415 volts of capacity 100 Amps with breaking capacity of 16 KA Fixed thermal and fixed magnetic setting - 01 No (For inside hangar No 01) (c) MCCB of 3 pole , 415 volts of capacity 63 Amps with breaking capacity of 16 KA with Fixed thermal and fixed magnetic setting - 01 No (For EOT crane) (d) MCCB of 3 pole , 415volts of capacity 16 Amps with breaking capacity of 16 KA with Fixed thermal and fixed magnetic setting - 04 Nos (For Hangar gate front & back & Security lighting left side hangar and termac lighting Back side of hangar & right side). (e) Digital time switches 415 V three Phase of 16 Amp rating with contactor fitted inside steel enclosure - 02 Nos.
Supply, installation, testing and commissioning of LT outdoor Feeder pillar Box AC 415 V , 50 Hz 3 Phase 4 wire, totally enclosed self supporting structure / cubicle , fully compartmentalized type , weather proof , protection IP 54 , suitable for outdoor use double door , with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick CRCA steel sheet of minimum Size ( 1.5x1.8 x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , with sloping canopy at top , double hinged doors at front with suitable locking arrangement , provision of louvers at sides , duly powder coated complete for accomodating and including following accessories :- (For Hangar No. 01 Right side Panel)
Contd/-..... Item No 19.142 BUSBAR :- Copper bus bar 600 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- MCCB 4 pole 415 Volts of breaking capacity of 36 KA of 400 Amps with Fixed thermal and Fixed magnetic setting - 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) MCCB 3 pole 415 Volts of breaking capacity of 36 KA of 250 Amps with Fixed thermal and Fixed magnetic setting - 01 No (For hangar No 1 for Ground Floor Left Side). (b) MCCB of 3 pole , 415volts of capacity 100 amps with breaking capacity of 16 KA Fixed thermal and fixed magnetic setting - 01 No (For inside Hangar No 01). (c) MCCB of 3 pole , 415volts of capacity 63 amps with breaking capacity of 16 KA Fixed thermal and fixed magnetic setting - 04 Nos (For hangar gate front & back & Security lighting left side hangar and termac lighting Back side of hangar & right side). (d) Digital time switches 415 V three Phase of 16 Amp rating with contactor fitted inside steel enclosure - 02 Nos.
Supply, installation, testing and commissioning of LT outdoor Feeder pillar Box AC 415 V , 50 Hz 3 Phase 4 wire, totally enclosed self supporting structure / cubicle , fully compartmentalized type , weather proof , protection IP 54 , suitable for outdoor use double door, with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick with CRCA steel sheet of minimum Size ( 1.5x1.8x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , with sloping canopy at top , double hinged doors at front with suitable locking arrangement , Provision of louvers at sides , duly powder coated , complete for accomodating and including following accessories :- (For Hange No. 02 left side Panel)
Contd/-..... Item No 19.144 BUSBAR :- Copper bus bar 300 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- MCCB 4 pole 415 Volts of breaking capacity of 36 KA of 200 Amps with Fixed thermal and Fixed magnetic setting- 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 125 Amps with Fixed thermal and Fixed magnetic setting - 01 No ( For Hangar No 02 Groung floor right side). (b) MCCB of 3 pole , 415volts of capacity 100 amps with breaking capacity of 16 KA Fixed thermal and fixed magnetic setting - 01 No (For inside hangar lights). (c) MCCB of 3 pole , 415volts of capacity 16 amps with breaking capacity of 16 KA with Fixed thermal and fixed magnetic setting - 04 Nos (For Hangar gate front & back & Security lighting left side hangar and termac lighting Back side of hangar & right side). (d) Digital time switches 415 V three Phase of 16 Amp rating with contactor fitted inside steel enclosure - 02 Nos.
Supply, installation, testing and commissioning of LT outdoor Feeder pillar Box AC 415 V , 50 Hz 3 Phase 4 wire, totally enclosed self supporting structure / cubicle , fully compartmentalized type , weather proof , protection IP 54 , suitable for outdoor use double door , with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick CRCA steel sheet of minimum Size ( 1.5x1.8x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , with sloping canopy at top , double hinged doors at front with suitable locking arrangement , provision of louvers at sides , duly powder coated complete for accomodating and including following accessories :- (For Hange No. 02 Right side Panel)
Contd/-..... Item No 19.146 BUSBAR :- Copper bus bar 300 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- MCCB 4 pole 415 Volts of breaking capacity of 36 KA of 200 Amps with Fixed thermal and Fixed magnetic setting- 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 100 Amps with Fixed thermal and Fixed magnetic setting - 02 Nos. (For hangar No 02 Groung floor right side and inside hangar light). (b) MCCB of 3 pole , 415volts of capacity 63 Amps with breaking capacity of 16 KA Fixed thermal and fixed magnetic setting - 01 No (For EOT Crane Panel). (c) MCCB of 3 pole , 415volts of capacity 16 Amps with breaking capacity of 16 KA Fixed thermal and fixed magnetic setting - 04 No (For hangar gate front & back & Security lighting left side hangar and termac lighting Back side of hangar & right side). (d) Digital time switches 415 V three Phase of 16 Amp rating with contactor fitted inside steel enclosure - 02 Nos.
Supply, installation, testing and commissioning of LT Outdoor Feeder pillar Box AC 415 V , 50 Hz 3 Phase 4 wire, totally enclosed self supporting structure / cubicle , fully compartmentalized type , weather proof , protection IP 54 , suitable for outdoor use , with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick with CRCA steel sheet of minimum Size ( 1.5 x 1.2 x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , with sloping canopy at top , double hinged doors at front with suitable locking arrangement , provision of louvers at sides , and duly powder coated complete for accomodating and including following accessories :- (For ware House Panel )
Contd/-..... Item No 19.148 BUSBAR :- Copper bus bar 250 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- MCCB 4 pole 415 Volts of breaking capacity of 36 KA of 160 Amps with Fixed thermal and Fixed magnetic setting- 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 125 Amps with Fixed thermal and Fixed magnetic setting- 01 No ( For Ware House Panel Ground floor) (b) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 16 Amps with Fixed thermal and Fixed magnetic setting- 07 Nos (For GSE bay,MT, Watch tower ,GPW house Security lighting ,Hazadeous bay & Fencing right side Security light). (c) Digital time switches 415 V three Phase of 16 Amp rating with contactor fitted inside steel enclosure - 02 Nos.
Supply, installation, testing and commissioning of floor mounted LT indoor panel board AC 415 V , 50 Hz 3 Phase 4 wire, totally enclosed self supporting structure / cubicle , fully compartmentalized type , suitable for indoor use , with bottom cable entry with suitable cable glands structure made out of 2.00 mm thick CRCA steel sheet of minimum Size ( 0.9 x 0.9 x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , hinged doors at front with suitable locking arrangement , provision of louvers at sides , and duly powder coated, complete for accomodating and including following accessories :- (For 55 KVA UPS panel)
Contd/-..... Item No 19.150 BUSBAR :- Copper bus bar 150 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- MCCB 4 pole 415 Volts of breaking capacity of 16 KA of 100 Amps with Fixed thermal and Fixed magnetic setting- 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- MCCB of 3 pole , 415volts of capacity 63 Amps with breaking capacity of 16 KA, Fixed thermal and fixed magnetic setting - 03 Nos (For Electric battery, Avionics /cal shop & power train shop).
Supply, installation, testing and commissioning of LT outdoor Feeder pillar Box AC 415 V , 50 Hz 3 Phase 4 wire,totally enclosed self supporting structure / cubicle , fully compartmentalized type , weather proof , protection IP 54 , suitable for outdoor use double door type , with bottom cable entry with suitable cable glands structure made out of 3.15 mm thick CRCA steel sheet of Size ( 1.5x1.8 x 0.6) m(with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted to PCC (1:2:4) type B1 , foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter , changeover switch and MCCBs , with sloping canopy at top , double hinged doors at front with suitable locking arrangement , provision of louvers at sides , and duly powder coated , complete for accomodating and including following accessories :- (For Special Power supply panel )
Contd/-..... Item No 19.152 BUSBAR :- Electrolytic Copper bus bar 3000 Amps , supported on non hygroscopic fibres and brass screws for mounting -04 Nos. INCOMER :- ACB microprocessor based released O/L/S/C & E/F protection &metering display manual Draw out type 4 pole 415 Volts with breaking capacity 50 KA of 2000 Amps - 01 No. INDICATING DEVICES :- (a) LED Indicating lamps for Main Supply indicating R, Y, B - 01 Set (Set of three). (b) Digital Ampere Meter 3 and 1/2 digit display , incl CT having CTR 2000/5 - 01 No. (c) Digital Voltmeter 0-500 Volts including CT, SIF 96 - 01 No. OUTGOING :- (a) ACB microprocessor based released O/L/S/C & E/F protection &metering display manual Draw out type 3 pole 415 Volts of breaking capacity 50 KA of 1250 Amps - 01 No (For APFC Panel). (b) ACB microprocessor based released O/L/S/C & E/F protection &metering display manual Draw out type 3 pole 415 Volts of braking capacity 50 KA of 1000 Amps - 01 No ( For 480VAC, 50 Hz 3 Ph). (c) MCCB 3 pole 415 Volts of breaking capacity of 36 KA of 250 Amps with Fixed thermal and Fixed magnetic setting- 01 No ( For 220VAC, 50 Hz 3 Ph). (d) MCCB 3 pole 415 Volts of breaking capacity of 36 KA of 400 Amps with Fixed thermal and Fixed magnetic setting- 01 No ( For 115VAC, 50 Hz 1 Ph). (e) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 63 Amps with Fixed thermal and Fixed magnetic setting- 01 No ( For 115-230VAC)
Contd/-..... Item No 19.152 (f) MCCB 3 pole 415 Volts of breaking capacity of 36 KA of 160 Amps with Fixed thermal and Fixed magnetic setting- 01 No ( For Single voltage, 480VAC). (g) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 25 Amps with Fixed thermal and Fixed magnetic setting- 02 Nos. ( For Single voltage, 220VAC & 215 VAC) (h) MCCB 3 pole 415 Volts of breaking capacity of 16 KA of 100 Amps with Fixed thermal and Fixed magnetic setting- 01 No ( For UPS 55KVA). (j) Digital time switches 415 V three Phase of 16 Amps rating with contactor fitted inside steel enclosure - 02 Nos.
S & F for 80 mm bore medium grade GI pipe (as Tarmac Area Pole for light of 2.6m height) complete all as specified and as directed.
S & F LED street light 150 W 5700K 230 volt,AC ,50 Hz endura baybrite plus energy saving , environmental friendly, long life exclusive innovation pressure dia cast aluminium IP 66 bay light with high power LEDs as light source complete all as specified and as directed.
S & F LED street light 80 W 230 volt,AC ,50 Hz endura pearl plus energy saving , environmental friendly, long life exclusive innovation pressure dia cast aluminium IP 66 bay light with high power LEDs as light sourceand impact resistance of IKO7 with 10 KV Built-in Surge protection device complete all as specified and as directed.
S&F street light bracket made out of GI pipe light grade 40mm bore 1.5 mtr long bent to required shape as directed and fixed to pole complete with two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed. (Note: Clamps and nuts, bolts and washer shall be measured and paid seperatly under relevant items.)
M&L for Flame Retardant Low Smoke & Halogen Free FR-LSH PVC Insulated Industrial Cables insulated two core 2.5sqmm multistrand copper conductor for connection of Securiry light from junction box to Security light all complete as specified and directed (Note : Two runs of 2.5 Sqmm cable shall be measured as one length.)
Supply and fix LED flood light 200W jeta pro plus energy saving, environmental friendly ,long life exclusive innovation pressure dia cast aluminium IP 65 bay light with high power LEDs as light source complete all as specified and directed.
supply and fix Cable Junction Boxes IP 66 “halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry - Black Colour) size 200 x 160 x 98 mm for 16/25 sq.mm l fixed to pole /wall with suitable FI clamp 20X3 mm nuts , bolts and washers incl provision of 01 No miniature circuit breaker (MCBs) single pole , 240 volts 10 KA 16 Amps and incl suitable capacity aluminium bus bar, complete all as specified and as directed.
S & F LED post top lanterns 35W 6500K New generation ,Post -top ,energy saving, environment friendly ,long life aesthetically designed with good indirect symmetrical light distribution, die-cast aluminium landscape IP65 luminiare with high power COB LED as light source complete all as specified and as directed.
Supply, Installation, Testing & Commissioning of micro processor controlled True On line double conversion, Stand Alone mode 3 Phase input and 3 phase 415V output of capacity 60 KVA UPS System for Min 30 Min power backup with inbuilt isolation transformer having IGBT based rectifier and IGBT based inverter including 60 Nos of 65 AH, 12 Volt SMF Battery including battery rack and battery connecting cables complete all as specified and as directed.
Supply, Installation, Testing & Commissioning of power pack with battery charger 415V AC Input & 110 DC 20Amp Output complete with battery bank of 2 volt,120 Ah tubular cell of 55 Nos for 110 V DC with suitable stand, connecting lead and connecting cable to connect with HT panel complete with all accesories complete all as specified and directed.
Taking out serviceable HT cable of any size/ type from trench / pipe / surface and re-routing / relaying the same including making electrical connection complete all as specified and directed. (Note: Earth work shall be measured & paid separately.)
M&L for Earthing complete with GI earth plate elecrode of size 600 mm × 600 mm × 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to GI earth strip 32 mm x 6 mm by means of bolts, nuts, check nuts and washers of brass or HS steel all as shown in electrical plate No. 3 connected to earthing test point and and necessary excavation and earth work pre-cast RCC(1:2:4) type B-1 pit cover 50mm thick, reinforced with 8mm dia TMT bars @100 mm /C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast cover slab and PCC(1:2:4) type B-1 concrete pit and angle iron frame and opening arrangement ) incl providing charcoal or coke and common salt in alternate layer of 15 cm compacted thickness all around the earth electrode with funnel and 20 mm bore galvanized iron watering pipe (medium grade) wire mesh, copper lugs, complete in all respect, protected by 40 mm bore (light grade) galvanized iron pipe up to earthing test point as directed, incl disposal of spoil to a distance not exc 50 mtr and necessary testing on completion complete all as specified and as directed. (Note: GI strip beyond 7.5 RM will be measured and paid separately.)
M & L for Earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick burried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to copper strip of size 20 x 3 mm as earthing lead means of nut, bolts and washers and 40 mm dia GI pipe "light grade" for protection of earth lead and connected to board or main switch including earthing pit in PCC(1:2:4) type B-1 and pre-cast RCC (1:2:4) type B-1 pit cover of size 300 x 300 x 100 mm thick, reinforced with 8mm dia TMT bars @100 mm /C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast cover slab, 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work complete shown in electrical plated No 3 of SSR Pert-I and tesing on completion complete all as specified and as directed. (Note: copper strip beyond 7.5 RM will be measured and paid separately.)
WATER COOLER/ AIR CONDITIONING:- Supply and fix water cooler electric driven (single phase), having approx storage capacity of 80 liter and nominal cooling capacity of 40 liter per hour complete all as specified and as directed.
Supply and fix voltage stabilizer for automatic operation , single phase naturally air cooed indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of +/- 2.5% and of capacity 1.0 KVA having digital voltage display indicator for input and output voltage with overload protection, short circuit protection, over voltage and under voltage shut down complete all as specified and as directed.
EOT CRANE Supply, installation, testing and commissioning of electrically operated through pendant push button station floor operated type EOT crane, double girder box type, having span of 53.20m (Aprox) of capacity 12.5 Ton having hoisting height 9.10 m (Approx) complete with and including main frame, platform, bridge girders/box girders, end carriages, trolley with frame, crab, buffers, gears with gear boxes, shafts, rope drum, rope sheaves, wire rope, wheels, lifting hook, brakes, motors, limit switches, control panel, pendant push button station, micro speed arrangements, wiring etc as per IS-3177, IS-807 complete all as specified and directed:- (i) Capacity - 12.5 Ton (12500 Kg). (ii) Span - 53.20 m (Approx). (iii) Lift - 9.10 m (Approx). (iv) Hoisting speed - 3 m/min (Slow speed through AC drive). (v) CT speed - 15 m/min (Slow speed through AC drive). (vi) LT speed - 20 m/min (Slow speed through AC drive). (vii) LT Motor Twin Drive - 5 HP each with gear box. (viii) CT Motor - 5 HP. (ix) Hoisting Motor - 12.5 HP. (x) Main girder - Box type. (xi) Operating Pendant - Push button from floor. (xii) Class of Duty - Class-II (Indoor). (xiii) EOT crane fitted should be comply with the saftey specification such as limit swiches, alarm, guards, isolating switches, emergency stop button and interlocking, power and control cabling complete etc confirming to IS-807, IS-3177, IS-3938 specifications. (xiv) Supply, Installation, Testing and Commissioning of Crane shall be undertaken through Manufacturers/ Specialist Firms.
MONORAIL CRANE Supply, installation, testing and commissioning of electrin hoist/monorail electrically operated through pendant push button station floor operated type, capacity 4 Ton having hoisting height 4 m (Approx) complete with and including gears with gear boxes, shafts, rope drum, rope sheaves, wire rope, wheels, lifting hook, brakes, motors, limit switches, control panel, pendant push button station, micro speed arrangements, wiring etc as per IS-3177, IS-807 complete all as specified and directed:- (i) Capacity - 4 Ton (4000 Kg). (ii) Lift - 4 m (Approx). (iii) Hoisting speed - 3 m/min (Slow speed through AC drive). (iv) CT speed - 10 m/min (Slow speed through AC drive). (v) CT Motor - 1 HP. (vi) Hoisting Motor - 7.5 HP. (vii) Operating Pendant - Push button from floor. (viii) Class of Duty - Class-II (Indoor). (ix) Crane fitted should be comply with the saftey specification such as limit swiches, alarm, guards, isolating switches, emergency stop button and interlocking, power and control cabling complete etc confirming to IS-807, IS-3177, IS-3938 specifications. (x) Supply, Installation, Testing and Commissioning of Crane shall be undertaken through Manufacturers/ Specialist Firms.
Supply, installation, testing and commissioning of electrin hoist/monorail electrically operated through pendant push button station floor operated type, capacity 1 Ton having hoisting height 3 m (Approx) complete with and including gears with gear boxes, shafts, rope drum, rope sheaves, wire rope, wheels, lifting hook, brakes, motors, limit switches, control panel, pendant push button station, micro speed arrangements, wiring etc as per IS-3177, IS-807 complete all as specified and directed:- (i) Capacity - 1 Ton (1000 Kg). (ii) Lift - 3 m (Approx). (iii) Hoisting speed - 3 m/min (Slow speed through AC drive). (iv) CT speed - 10 m/min (Slow speed through AC drive). (v) CT Motor - 0.5 HP. (vi) Hoisting Motor - 1.5 HP. (vii) Operating Pendant - Push button from floor. (viii) Class of Duty - Class-II (Indoor). (ix) Crane fitted should be comply with the saftey specification such as limit swiches, alarm, guards, isolating switches, emergency stop button and interlocking, power and control cabling complete etc confirming to IS-807, IS-3177, IS-3938 specifications. (x) Supply, Installation, Testing and Commissioning of Crane shall be undertaken through Manufacturers/ Specialist Firms.
COMPRESSED AIR SUPPLY M & L for heavy duty MS seamless pipe 50mm bore including socket, elbow and tee of suitable size for compressed air supply complete all specified and directed.
M & L for heavy duty MS seamless pipe 25mm bore including socket, elbow and tee of suitable size for compressed air supply complete all specified and directed.
M & L for isolation valve of 50mm bore with necessary fitting complete all as specified and directed.
M & L for isolation valve of 25mm bore with necessary fitting complete all as specified and directed.
S & F high flow Air Pressure Regulator for controlling pressure for each gas pipe with output pressure range 0-120 psig with pressure guage and pressure lock facility for 25mm inlet and outlet ports complete all specified and directed
Design, supply, installing, testing and commissioning of Air conditioning system to list of rooms enclosed at Appendix ‘B’ including following items and other items as required for satisfactory performance of the plant to achive the inside design conditions as per Appendix ‘A’ enclosed here-in-after complete all specified and directed. Note:- (a) Contractor/ bidder should submit complete design of Air conditioning system comparing to heat load calculation working drawings complete duly vetted by IIT/NIT/OEM of AC manufacture shall be submitted through GE for the approval of Accepting officer before execution of work. (b) Rooms ( 3 Nos ) having 24 Hours working required Stand by AC unit (c) Contractor /Bidder will be responsible for performance and guarantee of complete AC’s. (d) In case design will to be vetted by / submitted by the OEM the contractor will install the plant of from same manufacture.
Supply and installation of refrigerator, 5 star rating, electric driven, inveter type, monimum 300 ltr capacity, 230 volts, 50 Hz, frost free having auto defrost to stop ice build up having rotary compressor of warranty 10 years complete all specified and directed.
Supply, installation and testing of air cooled split unit air conditioner electric driven single phase of capacity of 2 TR, BEE 5 star rated inverter type complete all specified and directed. (Break down Details of ACs are given in Appindix C (OIC Tech Flight ; SEW Section ; Server Room ; STO Tech Control Room ;Ref Tech Library ; Battary Storage Room ; Conference Room ; Ups Room )
S & F Voltage stavlizer for protection of AC with IC controlled electronic circuit ensuring positive switching of Relay, Elegantly designed Spray/Powder coated metallic chasis,Input Voltage 150 to 280 Volts Output Voltage 195 to 245 V,Capacity 5 K.V.A. copper wound having digital display indicator for input & output voltage with overload protection, short circuit protection, over voltage & under voltage shut down complete all as specified and directed.
S&F 4 Way vertical TPN distribution boared as Per IEC 61439-3 suitable for flush mounting or surface mounting having copper busbar of 250 Amps for each phase. Having 2 neutral bar, 2 earth bar and cable tiea for cable management. Busbar should be filly insulated and neutral busbar also should be shrouded. VTPN DB having improved pan assembly for easy to installation, prefitted masking sheet and reversible door with IP-43 & IP-54 degree of protection with provision of and including 3 pole, 35 KA, 250 Amps MCCB as incomer and SP/TP MCB's as outgoing complete all specified and directed.
M&L for LT panel board indoor type wall mounted of suitable size having double door system with locking arrangement,having one incoming MCCB of 400 Amp as a main incomer and 4 outgoings for MCCBs of various sizes ,suitable aluminium busbar and fixed on angle iron base suitable for wall mounting complete all specified and directed. (Note: Incoming and outgoing MCCBs shall be measured and paid saparately.)
Supply, fixing, connecting, testing and commissioning MCCB in panel etc. MCCB, TP (3 Pole) with microprocessor release 200 Amps, 36kA breaking capacity with overload and thermal tripping feature, 415Volts AC, 50Hz, ICU = 100%, including certain addition or alteration if required at site complete all as specified and directed.
SOLAR WATER HEATER Supply and installation of Solar water heating,Flat plate collector type,with heat exchanger of 100 liter per day capacity, with electrical heating back up complete all as specified and directed.
SARAOGI BUILDERS LIMITED
Inderjit Mehta Constructions Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid