| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.4 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹9.1 L+₹18,495.92 (2.08%)Rejected-Finance 00 VILL RATI KA NAGLA SIKANDRA RAO ROAD INDUSTRIAL HATHRAS UTTAR PRADESH 204212 | HATHRAS | UTTAR PRADESH | 204212 | L2 | Rejected-Finance Being Not Lowest | |
| 3 | L3₹9.5 L+₹58,558.88 (6.59%)Rejected-Finance | L3 | Rejected-Finance Being Not Lowest | |
| 4 | L4₹10.0 L+₹1.1 L (12.3%)Rejected-Finance | L4 | Rejected-Finance Being Not Lowest |
Tender Value
₹9.9 L
EMD Value
₹19,800
Closing Date
28 Nov 2020, 6:00 pmClosed
Shri Prabhat Kumar Singh, AGE (I)
AGE (I) Manauri Allahabad-212212
REPAIR/REPLACEMENT OF DISTRIBUTION BOX / EARTHING WITH OTHER ALLIED WORKS AT 24ED UNDER AGE (I) AF MANAURI
2020_MES_383542_2
8836/E8
Open Tender
Electrical and Maintenance Works
Item Rate
182 days
Manauri, Allahabad
Class E Cat b (i)
7 documents required · 7 mandatory
₹500
AGE (I) AF Manauri
₹19,800
Yes
19 Jan 2021
12 Nov 2020
30 Nov 2020
12 Nov 2020
28 Nov 2020
13 Nov 2020
Amount
Excavating in trenches, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for wall foundation etc or for manholes etc not exceeding 10 Sqm area on plan and not exceeding 1.5 metre in depth and getting out in soft/loose soil.
Returning, filling in, including spreading, levelling, watering and well ramming in layers each not exceeding 25 cm thick in soft/loose soil.
Removing excavated surplus soil to a distance not exceeding 50 metre and depositing where directed at level not exceeding 1.5 metre above the starting point.
M&L for Sand cushioning in trenches with clean dry unsheathed gently punning around cable for protection complete. Note : Only punned thickness shall be measured for payment
M&L for brick, old sub class 'B' well burnt, laid dry flat in trenches for protection of cable over LT cable, complete all as specified and directed.
Cutting /boring to pilinth protection/ hard standing / road etc in suitable depth to across the GI pipe size upto 80 MM dia of bore for drawn through XLPE under ground cable for giving mechanical protection to cable complete all as directed. Note ; Quoted rate shall be included the cost of required material for repairing to disturbed surface all as per exisiting.
Supply and laying galvainesd steel tubing light grade 40 mm dia of bore fixed with pole/ surface of wall / laid in trench etc as site using 02 Nos clamp made out by GI strip in size 25x4 mm with nut bolt and washer etc all as directed.
Supply and laying galvainesd steel tubing light grade 80 mm dia of bore fixed with pole/ surface of wall / laid in trench etc as site using 02 Nos clamp made out by GI strip in size 25x4 mm with nut bolt and washer etc all as directed.
Supply, laying, jointing & testing of underground LT cables XLPE insulated armoured heavy duty aluminium conductor power cable 1100 Volt grade cross-sectional area 6 Sqmm 4 core (earthed) laid in trenches/ducts/along poles/through pipe under road etc with new aluminium lugs including taking out of old cable. Note :- Excavation, earth work, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule.
All as per item No 9 above but 10 Sqmm 2 core (earthed)
All as per item No 9 above but 10 Sqmm 4 core (earthed)
All as per item No 9 above but 16 Sqmm 2 core (earthed)
All as per item No 9 above but 16 Sqmm 4 core (earthed)
All as per item No 9 above but 25 Sqmm 4 core (earthed)
All as per item No 9 above but 35 Sqmm 4 core (earthed)
Supply & fixed energy saving AC single phase static energy meter of accuracy class 1.0, 240 V 50 Hz with Backlit LCD display of rating 10 - 60 A (measures and displays KWH ,V, Current I, KW, pf last month history of KWH, MD in KW) with special features like TOD, temper logging, optical communication port display in absence of power with transparent hinge type sheet metal box with locking arrangement complete. Note:- Calibration test report issued by OEM shall be submit by contractor. Make:- L&T Model EM 101+ class 1 base mounting cat No WM101BC7DL0BOX or equivalent make as specified in appendix ‘B’ to Particular specification.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, triple pole and neutral, 4 ways, 415 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, Single pole and neutral, 12 ways, 240 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, Single pole and neutral, 8 ways, 240 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, Single pole and neutral, 4 ways, 240 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement MCCB, four pole, 415 Volt ,40 Amp rating, 16 KA ultimate breaking capacity fixed in DBs catered herein before.
S&F in replacement MCCB, four pole, 415 Volt ,63 Amp rating, 16 KA ultimate breaking capacity fixed in DBs catered herein before.
S&F in replacement RCCB, double pole, 240 Volt , HPI, 40 Amp rating, 30 mA, 2 nos of 17.5mm modules for earth leakage protection fixed in DBs catered herein before.
S&F in replacement RCCB, double pole, 240 Volt , HPI, 63 Amp rating, 30 mA, 2 nos of 17.5mm modules for earth leakage protection fixed in DBs catered herein before.
S&F in replacement RCCB, four pole, 415 Volt , HPI, 63 Amp rating, 30 mA, 4 nos of 17.5mm modules for earth leakage protection fixed in DBs catered herein before.
S&F in replacement MCB, tripple pole and neutral, 415 volts, 32 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
S&F in replacement MCB, single pole and neutral, 240 volts, 32 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
S&F in replacement MCB, single pole, 240 volts, 32 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
S&F in replacement MCB, single pole, 240 volts, 6 to 10 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
Supply & fixed in replacement PVC insulated muilticore strandard copper single & multi flexible round cable size 1.5 Sqmm 3 core ISI marked 660/1100 Volt conforming to IS:694-1990 complete.
Supply & fixed in replacement PVC insulated muilticore strandard copper single & multi flexible round cable size 2.5 Sqmm 3 core ISI marked 660/1100 Volt conforming to IS:694-1990 complete.
Supply & fixed in replacement PVC insulated muilticore strandard copper single & multi flexible round cable size 4.0 Sqmm 3 core ISI marked 660/1100 Volt conforming to IS:694-1990 complete.
Supply & fixed in replacement PVC insulated sheathed aluminium conductor armoured cable with inner sheathing for service connection size 10 Sqmm 2 core 1100 Volt complete.
Supply & fixed in replacement PVC insulated sheathed aluminium conductor armoured cable with inner sheathing for service connection size 6 Sqmm 2 core 1100 Volt complete.
Earthing complete with galvanised mild steel earth electrode plate 600 X 600 X 6 mm thick buried directly and vertically in ground connected to galvanised iron earth strip 32x6mm size by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth strip protected by galvanised iron 40 mm bore medium grade pipe with all fittings from the earth electrode fixed along pole with and including 25 x 6mm flat iron clamp, bolts, nuts and washers and watering pipe shall be 20 mm bore GI medium grade from top of the earth electrode to bottom of the earth pit including all excavation and earth work in any type of soil and removal of surplus soil upto 50 metre, PCC pit with pre-cast RCC cover with handle, charcoal/salt, funnel , CI frame etc complete all as directed. Notes :-(i) The concrete pit shall be made in PCC 1:3:6 type C-1, 40mm thick precast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate with suitable MS handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. Reinforcement in RCC cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be adjusted through deviation order. (iii) Item includes cost of 7.5 metre earth strips. Any variation in length shall be adjusted through deviation order. (iv) Plate electrode shall be surrounded by adequate quantity of charcoal dust & salt to a packed thickness of 15 cm on all sides.
Earth continuity conductor or main earthing lead 32x6mm GI strip laid in pipe or fixed on wall or any other position including jointing by tinned copper/brass nuts, bolts and washers in adition brazing at every joint (beyong 7.5 metre)
M&L for erection in position of true vertical swaged tubular pole type 410 SP-31 [9.0 m long] complete with cast iron base plate, finial taper plug, bolts, nuts and screws and top cover complete including taking out old pole any type from ground and making good disturbed surface complete all as specified & directed including following:- [a] Excavation in trenches not exceeding 1.5 m wide & 2 m deep for pole foundation & getting out soft loose soil, returning filling soil in the trenches after fixing of pole in foundation ramming earth around the layers not exceeding 25 cm thick and disposal of surplus soil to a distance not exceeding 50 m. [b] M&L providing PCC 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation 600 mm x 600 mm cross section planting depth 1.8 m for concrete casing the pole up to ground level. [c] M&L providing PCC 1:3:6 type C-2 using 40 mm graded stone aggregate as in plinth band/ collar 300 mm high from ground level & 450 mm dia. [d] M&L painting of pole on external surface with one coat of black bituminous paint [up to planting depth] and above plinth band/ concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of steel surface and painting with synthetic enamel paint blue colour, circular band three number of 30 cm wide in alternate layer up to height of 1.5 m above plinth band of pole. [e] Material & labour writing letter or figures/ pole number [Block, Roman, Italic as Indian] with thick synthetic enamel paint of approved shade not exceeding 30 cm. Note: (i) Old dismantled portion of LT poles in grounds shall be filled with PCC (1:5:10) type E-2 using 40 mm graded stone aggregate. Cost of PCC filling shall be deemed included in quoted unit rate (ii) Rate shall be deemed to include cost of Eearth work, PCC & other work as mentioned here-in before (a) to (e) under this item.
M&L for advance maintenance free chemical earthing with JMV CBE 403 environment friendly ring earthing system consisting each set of 03 (three) Nos of 10 (ten) feet length 40 mm dia earth electrode made out by copper, maintenance free electrolytic grade copper earthing system of JMV make based on flat in pipe technology of 3 Mtrs length, 40 mm dia with crystalite conductive mixture COMPOUND filled with the permanent sealing at the top & bottom with the lead terminal / strip in 25x4 mm size copper with 2 holes of 10 mm dia at the top , to be lowered in 150 mm dia bore including filling of back fill ecofriendly earth enhancing compound tested by ROHS comply to IEC 62651-7 which should have passed leaching ,corrosion, sulphur & resistivity test as per IEC 62651-7 by NABL accredit LAB/JAM plus compound in 150 mm bore in immediate contract around the earth electrode and top of the bore shall be finished with 40 mm thick PCC in 1:2:4 type B 1 over 75 mm thick PCC in 1:4:8 type D-2 and back filly/ JAM compound shall be covered with FRP pit cover of suitable size for each earth electrode , joint to be made by JAM weld exothermically welded technology including copper strip size 50 x 6 mm for earthing ring system and copper strip 32x6 mm size for earthing electrode to test point with saddles & porcelain insulators suitable size on wall ,earth strip protected by light grade GI pipe 40 mm dia in case of plinth protection / floor/ hard standing crossing complete all as specified and directed. Make - JMV LPS Limited / JEF/ ALCOICE / Conducrete Note :- Earth work , PCC work, PCC cutting work by cutter, earth chamber in suitable size with testing on suitable value etc rate shall deemed to be included in quoted rate.
Supply and fixing copper strip 32mmx6 mm with saddles and fixing screws etc for roof conductors above ground level all as specified and directed.
M&L for recharging to existed earthing at E/M installation in any type upto standard value with using required chemical such as Nacl/ MgSo4 / other approved chemical including riveting / welding/ bolting to earth lead incl testing etc by tech rep with riveting, bolting replacing to nut, bolt and washer etc to GI earthing strip for making earth continuity from transformer / panels to earthing pit complete all as site required and directed. Note : Item shall be paid after getting resistance value satisfactorily and record shall be submitted to the Engineer in charge.
Note :- (i) Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material. The contract amount shall be arrived at after deduction of Schedule of Credit from the total quoted amount in BOQ. (ii) Make of material shall be as per mentioned in Particular specifications or Appendix 'B' to Particular specifications as approved by AGE (I) AF manauri if not specified in BOQ
M/S VIJAY SINGH
M/S Garg Sons
M/s M A Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .