Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | I₹98,600Accepted-Finance | I | Accepted-Finance Accept | |
| 2 | II₹99,400Rejected-Finance | II | Rejected-Finance Reject | |
| 3 | III₹1 LRejected-Finance | III | Rejected-Finance Reject |
Tender Value
₹99,200
EMD Value
₹1,000
Closing Date
20 Jul 2020, 12:00 pmClosed
EE
132 KV S/S Bharua Sumerpur
WORK OF REPAIR OVERHAULING AND REPLACEMENT OF DEFECTIVE POLE DEFECTIVE 33 KV VCB AT 132 KV S/S RATH AND BHARUA SUMERPUR
2020_UPTCL_490307_1
TS-10/ETDH/2020-21
Open Tender
Electrical Works
Lump-sum
90 days
132 KV Bharua Sumerpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹118
Yes
Executive Engineer
₹1,000
Yes
20 Jul 2020
6 Jul 2020
20 Jul 2020
6 Jul 2020
20 Jul 2020
6 Jul 2020
Amount
Details of Work.
Repair, overhauling and replacement of defective pole of following 33 KV CGL, Siemens & Shreem make VCB type circuit breaker which are defective due to damage of pole etc. at 132 KV S/S Rath and 132 KV S/S Bharua Sumerpur :-
(a) 33 KV VCB CGL Make at 132 KV S/S Rath (02 Nos.) (b) 33 KV VCB Siemens Make at 132 KV S/S Rath (01 No.) (c) 33 KV VCB Shreem Make at 132 KV S/S Bharua Sumerpur (01 No.) By doing following work in each circuit breaker:- (i) Cleaning of porcelain of drive insulator and porcelain of vacuum interrupter of each pole. (ii) Checking & adjustement of snatch gap, travel of drive insulator rod & tie rod of each pole. (iii) Opening, repairing of mechanism by welding, drilling, machning and filling of material as per requirement and proper fitting of it in breaker cubicle. (iv) Oiling & greasing of crank gears by opening of lock circlip etc. (v) Replacement of worn out parts such as bush, rings, lock pins and latch etc. (vi) Checking & adjustment of oil daspot of breaker for its damping action. (vii) Replcement of defective pole of 33 KV VCB with new one as per requirement. After repairing & overhauling of above VCBs, following tests are to be carried out :- (i) Opening & closing time of breaker of each pole. (ii) Carrying out Contact Resistance Measurement (CRM test) of each pole. (iii) Checking of megger values of breaker poles. (iv) Checking triping of breaker at 70% DC voltage. (v) Checking the CLOSE/OPEN operation of breaker from REMOTE & LOCAL. (vi) Prepare and submit the site ovehauling report of each breaker.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
MAXWEL ELECTRICALS
N D ASSOCIATES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .