Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
25 Aug 2022, 6:30 pmClosed
GE (West) Jabalpur
Garrison Engineer (West) Jabalpur Supply Marg Post Box No. 54 Jabalpur Cantt-482001 (MP)
SPL REPAIR / REPLACEMENT OF LT OH LINE PANELS, FEEDER PILLAR BOXES AND LT CABLES AND CONNECTED WORKS OF MD ACCN AREA OF MH JABALPUR UNDER GE WEST JABALPUR
2022_MES_543437_1
8509/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (West) Jabalpur
As per Tender documents
5 documents required · 5 mandatory
₹500
GE (West) Jabalpur
₹94,000
9 Sept 2022
4 Aug 2022
27 Aug 2022
4 Aug 2022
25 Aug 2022
11 Aug 2022
5 Aug 2022 - 9 Aug 2022
Amount
Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in any type of soil
M&L for sand cushioning to underground cable providing with a layer 8 cm before laying and 15 cm after laying, jointing and testing the cable all as specified and directed. Note: Punned thickness of sand shall be measured.
M&L for Brick covering with width equal to length of brick as mechanical protection to cable with well burnt sub class ‘B’ bricks laid dry flat complete all as specified and directed by Engr in charge.
Removing surplus excavated material to a distance not exceeding 5 0meter above the starting point complete all as specified and directed by Engr in charge.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed by Engr in charge.
M&L for GI Tubes, of following size, light grade ,galvanised , with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc complete all as specified and as directed.
(a) 40 mm bore
(b) 50 mm bore
(c) 80 mm bore
Dismantling existing ACSR (any size) from over head line completeall as directed by Engr-in-Charge.
Dismantling insulators any type and any size complete all as directed by Engr-in-Charge.
Dismantling of cross arm(made of MS channels / angles etc.) or clamps etc.complete and stacking aside for re-use / replacement all as directed by Engr-in-Charge
Dismantling of stay assembly embedded in concrete and removing materials from site of work complete all as directed by Engineer-in-Charge.
Dismantling of old unserviceable service connection cable with GI wire and reel insulator complete all as directed by Engr-in-Charge.
Dismantling of existing GI earth wire any size complete all as specified and directed
Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 5 of MES SSR part-I(1991) (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 40 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
Taking down of old unserviceable service connection cable of any type upto and including 240 sqmm complete all as specified and directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16.00 sq mm 4 core
do-- but size 35 sq mm 3.5 core
do-- but size 50 sq mm 3.5 core
do-- but size 70 sq mm 3.5 core
do-- but size 95 sq mm 3.5 core
do-- but size 120 sq mm 3.5 core
do-- but size 185 sq mm 3½ core
do-- but size 240 sq mm 3½ core
Dismantling of old unservicable bus bar chamber and Design, supply, erection, testing and commissioning of outdoor type LT Bus Bar Chamber box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type Aluminium bus bars (32mm x 5mm) for looping & branch connection system .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947.
The bus bar chamber shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. The bus bar chamber shall be provided with ventilation facility in the form of louvers for better heat dissipation.
(Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
Disconnecting, dismantling of existing old unserviceable LT Panel/Feeder pillar box and Design, supply, erection, commissioning and testing of outdoor type LT Panel, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main Aluminium bus bars of 630 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves of colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 9 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The LT Panel shall be made out of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation in and including dismantling of old unserviceable LT Panel complere and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges.
CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for conecting of all incoming and outgoing cables, Make of LT Panel : Mc Layer Pvt Ltd, Tricolite, Asian Switchgear
INCOMING :- MCCB 500 Amps, 4 pole, 415 volts, 36 kA, 50 Hz, electronic release Make Legrand -667659 or equivalent make of ABB, Seimens - 01 Nos
OUTGOING : (a) MCCB 160 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, thermal magnetic release, Ics = 100%Icu, Make Legrand-669010, ABB, Seimens - 04 Nos
(b) MCCB 63 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, thermal magnetic release, Ics = 100%Icu, Make Legrand-420218, ABB, Seimens - 02 Nos
(c) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 Nos
Make : Legrand, L&T, Hager, Havells
(d) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 Nos
Make : L&T, Hager, Havells
(e) Current transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos
(f) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1set of 03 Nos (Red - 01, Yellow- 01, Blue - 01)
Make : CG/L&T/Siemens
(g) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No 02 Amps HRC fuse of suitable type- 03 Nos
(h) Danger Notice Plate -02 Nos
(i) Power contactor four pole with coil voltage 230 volt of capacity 25 Amps 50 cycles.Cat Part No 412544 of Legrand - 01 Nos
(j) Time switch microrex analog time switch Cat part No 412814 of Legrand -01 Nos
(k) Pannel box made up of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved (The panel shall not be less than 2.5 Sqm front area) ' Make of Panel - Asian Switchgear/ Tricolite/Universal Switchgear/ Mc Layer Pvt Ltd
Note : Panel will be manufactured by CPRI approved firm as indicated above. The contractor shall submit drawing of the panels to Engr-in-charge before procurementof LT panel for approval alongwith CPRI approval. Foundation will prepared as per instruction and rate of fondation deemed to be included in the quoted rates.
Disconnecting, dismantling of existing old unserviceable LT Panel/Feeder pillar box and Design, supply, erection, commissioning and testing of outdoor type LT Panel, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main Aluminium bus bars of 250 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves of colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 9 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The LT Panel shall be made out of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation in and including dismantling of old unserviceable LT Panel complere and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges.
CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for conecting of all incoming and outgoing cables, Make of LT Panel : Mc Layer Pvt Ltd, Tricolite, Asian Switchgear
INCOMING :- MCCB 125 Amps, 4 pole, 415 volts, 25 kA, 50 Hz, electronic release Make Legrand or equivalent make of ABB, Seimens - 01 Nos
OUTGOING : (a) MCCB 63 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, thermal magnetic release, Ics = 100%Icu, Make Legrand- ABB, Seimens - 05 Nos
(c) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 Nos
Make : Legrand, L&T, Hager, Havells
(d) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 Nos
Make : L&T, Hager, Havells
(e) Current transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos
(f) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1set of 03 Nos (Red - 01, Yellow- 01, Blue - 01)
Make : CG/L&T/Siemens
(g) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No 02 Amps HRC fuse of suitable type- 03 Nos
(h) Danger Notice Plate -02 Nos
(k) Pannel box made up of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved (The panel shall not be less than 2.5 Sqm front area) ' Make of Panel - Asian Switchgear/ Tricolite/Universal Switchgear/ Mc Layer Pvt Ltd
Note : Panel will be manufactured by CPRI approved firm as indicated above. The contractor shall submit drawing of the panels to Engr-in-charge before procurementof LT panel for approval alongwith CPRI approval. Foundation will prepared as per instruction and rate of fondation deemed to be included in the quoted rates.
Supply, fixing and connecting PVC insulated, round,sheathed, multicore, industrial flexible cable with bright annealed copper conductor, 1100 volts grade cable of size 2.5sqmm, 3 core, confirming to IS 694-1990 complete all as specified and directed
Supply and fix thermoplastic polycarbonate street light juntion box of size 200x160x98mm which is totally safe, shock proof, impact resistant, weather proof, dust proof, rust proof ,halogen and slica free, having internal embedded gasket technology made of PUR (Make Hensel), complete with IP 65 degree of protection with cable glands (Make AGRO) material polymide in and including the following :- Junction box Cat No K-9255 (box with 5 way Hensel terminal) and having metric knock out on 4 sides ) - 01 Nos,cable gland (cat No 1555.32.1.25)M32x1.5, 03 Nos, Lock nut (Cat No 8232,M32x1.5) - 03 Nos, MCB SP, 6 Amps - 01 Nos
S&F 3 Layer PPR Pipes, UV stabilised having thermal stability upto 93 degree centrigrade complete and fixed with the pole by providing FI clamps, nuts and bolts of size 25x25x3mm with nuts & bolts for protection of connecting wires, connection from junction box to light fittings, complete for outer dia 20 mm (PN-16) Make : SFMC / WET FLOW /AQUA
Supply and fixing MCCB 4 pole 100 Amps rupturing capacity 16 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Supply and fixing MCCB 4 pole 200 Amps rupturing capacity 25 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .