"Electrical work in connection with "Development of GMC as Satellite station in Prayagraj division"
GSU-EL-WC-74-2026
GSU-EL-WC-74-2026
Open
Works - General
12 Months
Prayagraj, Uttar Pradesh
₹0
₹2.2 L
21 Jul 2026
21 Jul 2026
29 Jul 2026
Item Breakup - 1-NS Items
Wiring for light point/ fan point/ exhaust fan Numbers 1500.00 point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.(B)
Wiring for circuit/ submain wiring along with earth Metre wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Wiring for circuit/ submain wiring along with earth Metre wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire.
Wiring for circuit/ submain wiring along with earth Metre wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 4 sq. mm + 1 X 4 sq. mm earth wire.
Wiring for circuit/ submain wiring along with earth Metre wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.4 X 4 sq. mm + 2 X 4 sq. mm earth wire.
Wiring for circuit/ submain wiring along with earth Metre wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 10 sq. mm + 2 X 6 sq. mm earth wire.
Supplying and fixing following size/ modules, GI Each box along with modular base & cover plate for modular switches in recess etc. as required. 4 Module (125mmX75mm)
Supplying and fixing two module stepped type Each electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on Each the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing 3 pin, 5 A ceiling rose on the Each existing junction box/ wooden block including connections etc. as required.
Supply (1Number= 1 Packet). with ISI Mark
Supply and commissioning of BEND (1 Number= Numbers 150.00 1Packet). with ISI Mark.
Supply and commissioning of socket 3 pin 5/6 A Each socket outlet with ISI Mark.
Supply and commissioning of Switch 5/6 A switch Each with ISI Mark.
Supply and commissioning of socket 6 pin 15/16 Each A socket outlet with ISI Mark.
Supply and commissioning of Switch 16A with ISI Numbers 250.00 Mark.
Supplying and laying of following size DWC/HDPE Metre pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.120 mm dia (OD-120 mm & ID-103 mm nominal)
Termination of LT XLPE cables of various sizes Numbers 100.00 (One Job means all 4 cores of cables).
Collecting, Transporting from SSE/GSU/store to Metre site, laying, testing, and commissioning of above LT cable . Laying direct in ground (Including excavation, sand cushioning, protection brick covering and refilling the trench etc.), direct in RCC/Metal pipes in rod/track crossings and on surface/required in wall/in concrete floor by cutting recessed and finished originally as required as per relevant technical specifications. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Drilling of bituminous road/track and laying Metre charges of cable in road crossing for laying 110 mm diaHDPE pipe through it.
Supply and laying of B class, 50 mm dia, GI pipe Metre for cable riser/road crossing as required and as per relevant technical specification.
Supply and burying of earth electrode of 40mm Numbers dia 'B' class GI pipe of 3.0 Mtrs long having 12 mm dia holes spaced 75 mm apart drilled upto 2 mtrs length from the bottom including 340 mm wide pit is to be dug upto the depth of not less then 3750mm. The earth electrod lowered in the pit thereafter refilling of pit is to be done with 30mm alternate layer of salt and charcoal upto 2.5 Mtrs. Pit is to be made of not less than 40 x 40 x 30 Cms from inside & precast RCC cover of 40mm thick with lifting arrangement shall confirm to CEE/NR specification No. NR/Elect/Wiring/1-84 and Drg. No. Sr. DEE/G/ALD 10/94. GI pipe shall be of TATA/QST/JINDAL make.
Supply, commissioning of feeder pillar with 01 no. 250A 04 pole MCCB for incoming & 25 nos s.p. 63A MCB for outgoing as per relevant specification.
Supply, erection, testing and commissioning of Numbers approved make standard size of following Distribution board recessed in wall having earth terminal block and neutral terminal block to enable termination of conductors incoming as well as outgoing individually by screwed connections and without twisting complete in all respect as per relevant technical specification.DP distribution board of standard size confirming to technical specification No. Sr.DEE/G/ALD/94/104 comprising of one No. 2 pole 32/40 Amps MCB's of approved make.(1) 4-No SP MCB's of 6 Amps as required.
Supply, erection, testing and commissioning of Numbers approved make standard size of following Distribution board recessed in wall having earth terminal block and neutral terminal block to enable termination of conductors incoming as well as outgoing individually by screwed connections and without twisting complete in all respect as per relevant technical specification of DP distribution board of standard size confirming to technical specification No. Sr.DEE/G/ALD/94/104 comprising of one No. 2 pole 32/40 Amps MCB's & 8-No SP MCB's of 6/10 Amps as required. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, replacement, fixing, testing, connecting Numbers and commissioning of 72 Watt or above LED street lights fittings.LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute lights,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012).IS:16108(2012),IEC:62471.Type LED:- High power LED,SMD(Surface Mounting device)/COB(Clip on board).1.Input operating voltage :-105-295 V AC.2:- Normal Voltage-220V AC,3.Driver type: constant current driver with short circuit protection. 4.LED life:- >50000 burning hours.5.Depreciation:- 30% max.after 50000 burning hours.6.Control of distribution:-Full cut off. 7.Surge protection:4KV.8.Drive component :Industrial grade only.9.Efficiency of driver electronic: > 85%.10.Beam angle:>=140 degree along with road and >=80 degree across the road.11.Colour temperature:5000- 6500K.12.Colour rendering index(CRI):>=75.13.Ingress protection :IP- 66.14.Lumen output: >120 lumens/watt.15.Power factor:->0.95. 16.Total harmonics distortion(THD):-<15%.17.Lamp cover :Toughened glass or UV stabilised poly carbonate.18.Finishing:Power coated /Anodized.19.Secondry optics:poly carbonate reflector/ poly carbonates lens.20.Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum.21.Mounting:Suitable for existing pole/Truss/Lantern mounted.22.Certificate:Firm to submit LM80(In respect of LED used)& LM79(In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for compliance of BIS/IEC.23.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted with new suitable bend/elbow with clamp and proper nut and bolt and connection with twisted twin flexible cord of minimum size 16/1 mm copper conductor as per relevant technical specification. Materials parameters must remain unchanged during entire warranty period. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, replacement, fixing, testing, connecting Numbers 400.00 and commissioning of energy efficient luminaries complete with all accessories of capacity 20 watt, 4 feet length, T8 LED lamps with suitable current control driver circuit ,suitable for surface/recessed mounting.LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/Jaquar/ PHILIPS/LUMILEDS /LEDNIUM. (2):- LEDs to IS:16105(2012).IS:16108(2012),IEC:62471.1.Input operating voltage :-105-295 V AC.2:-Normal Voltage-220V AC.3.Driver type: constant current driver with short circuit protection(For tube light).4.Control of distribution:-Full cut off.5.Drive component :Industrial grade only .6.Efficiency of driver electronic: > 85% (For tube light).7.Colour temperature:5000-6500K(For tube light).8.Colour rendering index(CRI):>75(For tube light).9.Ingress protection :IP-20.10.Lumen output: >100 lumens/[email protected] drive current(For tube light).11.Power factor:->0.90(For tube light). 12.Total harmonics distortion(THD):- <20%(For tube light).13.Lamp cover :Acrylic cover which does not result in loss of lumens.14.Finishing:Power coated /Anodized.15.Secondry optics:poly carbonate reflector/ poly carbonate lens.16.Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum.17.Mounting :Suitable for surface mounting/recessed mounting.18.Certificate:Firm to submit LM80(In respect of LED used)& LM79(In respect of luminaire used) test certificate from National/International accredited Laboratory and OEM certificate for compliance of BIS/IEC.19.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Materials parameters must remain unchanged during entire warranty period.....1x20watt. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, commissioning of 24/36 watt 2x2 LED lights fittings, recess LED Fitting 24/36 watt ,suitable for surface/recessed mounting. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:- (1):- NICHIA/CREE/OSRAM/SEOUL/ PHILIPS/LUMILEDS/LEDNIUM. (2):-LEDs to IS:16105(2012).IS:16108(2012),IEC:62471.1.Input operating voltage :-105-295 V AC.2:-Normal Voltage-220V AC.3.Driver type: constant current driver with short circuit protection. 4.Control of distribution:-Full cut off. 5. Lumens-3600/5400 .6.Efficiency of driver electronic: > 85% .7.Colour temperature:4000K.8.Colour rendering index(CRI):>75. 9.Ingress protection :IP- 20.10.Lumen output: >150 lumens/[email protected] drive current. 11.Power factor:->0.97. 12.Total harmonics distortion(THD):-<20%. 13.Lamp cover :Acrylic cover which does not result in loss of lumens. 14.Finishing:Power coated /Anodized.15.Secondry optics:poly carbonate reflector/ poly carbonate lens.16.Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum.17.Mounting :Suitable for surface mounting/recessed mounting.18.Certificate:Firm to submit LM80(In respect of LED used)& LM79(In respect of luminaire used) test certificate from National/International accredited Laboratory and OEM certificate for compliance of BIS/IEC.19.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Materials parameters must remain unchanged during entire warranty period.
Supply, commissioning of storage type water cooler similar to Model SDLX 100, Cooling Capacity-170 litre per hour, 380 litre Storage with suitable foundation/platform with cage.
Supply, fixing & commissioning of LT Heat Numbers Shrinkable Straight through jointing Kit for 3.5/4 Core 50-95 Sqmm LT XLPE Cable.
Supply, fixing & commissioning of LT Heat Numbers Shrinkable Straight through jointing Kit for 3.5/4 Core 120-185 Sqmm LT XLPE Cable.
Supply, fixing, connecting and commissioning of Numbers Push Button-Industrial type Plug & socket SPN distribution board with 02 pole & earth metal Plug & socket complete with 32A S.P. MCB.
Supply, fixing, connecting and commissioning of Metre PVC drain pipe of size 3/4'.
Supply, commissioning of 300 mm sweep Exhaust Fan suitable for 230 volts, 50 Hz AC supply, more than1400 RPM heavy duty with wiring and flexible PVC pipe as required. Make: Bajaj, Havell's, RR or similar. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, commissioning of 750 mm heavy duty wall mounted air circulator Fan suitable for 230 volts, 50Hz - AC supply, 1440 RPM, with wiring in flexible PVC pipe as required.
Supply, fixing, connecting and commissioning of Numbers 5 KVA Single Phase, Sine wave Digital Voltage Stabilizer as per IS:8448 or latest amendment up to date, input voltage 160-260 Volt, output voltage 230 +10% Volt with time delay relay.Make-Blue star or similar.
Design,Supply, commissioning of LT Switch gear panel board of 2mm thick dia pressed CRC steel sheet . Panel shall be treated for anti corrosion treatment and finished with smoke gray paint as per technical specification No. Sr DEE/G/ALD/ Panel-94/113 comprising with.........Supply of Incoming ACB 630A,04 Pole draw-out 50 Hz.Coforming IS:13947-2 of make.
Supply, commissioning of of Bus Coupler ACB 630 A,04 Pole draw out,50Hz,Conforming IS:13947-3 Make- ABB/L &T/Crompton Greaves
Supply, commissioning of ACB 630 A, 415 Volt, 3 phase, 4 pole Manually draw out microproceeor basd type conforming to IS: 13947-2, IEC 60947-2 latest specification.
Supply, commissioning of MCCB of 250 A, 36 kA Standard breaking capacity, 415 volt, 3 Phase 4 Pole current rating 250 Amp.
Supply, commissioning of MCCB of 125A, 36 kA Standard breaking capacity, 415 volt, 3 Phase 4 Pole current rating 125 Amp.
Supply, commissioning of Indicator lamps with suitable holder.
Supply, commissioning of Outgoing/Feeder Panel Mounted Multi-function meter with Accuracy Class 1 as perIEC 62053-21 or Class 0.5, 0.5S as per IEC 62053-22.LED meter Cl 1 with RS485: Meter should havefollowing features built-in LED • Flush mounting 96x 96 mm • True RMS measurement • Passwordprotection provision for security • Site selectable for3 Phase 4 wire, 3 Phase 3 wire, 1 Phase, CT Secondary 1A/5A, Universal Auxiliary Supply 80-300VAC/DC, Input Voltage Measurement 50-500 VAC, •64 samples/ cycle The Meter should be able toread/display following parameters InstantaneousParameters (V1, V2, V3, V12, V23, V31, Avg (VLN,VLL), A1, A2, A3, Aavg, F, PF-1, PF-2, PF-3, PF(Avg) W1, W2, W3, W (total) VA1, VA2, VA3, VA(total) Cumulative Parameters (Import Wh, ImportVah, Import load hours, Reset (old) Cumulativeparameters (Import Wh, Import load hours,Communication (RS485 Modus RTU).complete withall accessories. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, commissioning of Fabrication works and insulated Aluminum bus bars of 1200A capacity for phases & 1200A capacity for neutral Bus bar shall be suitably insulated with heat shrinkable sleeves/ epoxy coating/insulating tap to withstand the test voltage of 2.5 KV Copper strip for connection outgoing as well as incoming with suitable size be provided.
Supply and erection of 6 Mtr.Galvanised (as per Numbers BS EN ISO 1461) octagonal pole with base plate 220x220x12mm, top 70mm and bottom 130 mm of 3mm thick sheet suitable for maximum wind speed utp 160 Km/Hr. including foundation bolts and foundation with M 20 grade RCC and FE 415 grade reinforcement (450x450x800 Cm deep ) (foundaton should be as per design approved by pole monufacturer) GI base plate G.I. anchor plate etc.as required including supplying and fxing of 1 Mtr.long double arm hot depped galvanised bracket suitable for street light fittings and supplying and drawing of 3x2.5Sq.mm FRLS copper conductor single core cable from junction box with two Nos 6/10AMP MCB to luminaire complete including termination with copper lugs as required. Confirming to IS:2062,IS:875 Part-3 & IS:4759
Design, Survey, Proposal with Technical Elevation Square Drawings & 3D layout, Supply, Manufacture, Foot Erection, Installation, testing and Display of wall / hanging / floor /pole mounting type LED illuminated, Modular, Changeable Aluminium extruded profile signage / direction board in full/half Parabolic and Elliptical square and multiangle shape and flat, with die molded internal structural brackets (Nylon/SS) and aluminium extruded heat sink. Suitable size end cap PC/ SS304 should be provided with provision of illuminated Logo. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2-3 mm thickness. The text / graphics matter vision angle shall not be less than 160 degree and visibility not be less than 75%.The approved color text and graphics shall be printed / router cut on monomeric calendered vinyl of 100 um thickness and shall be firmly pasted on display sheets. A pole with grooves for tricolor LED/Neon light installation. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the backside of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4- 8 W / sq. ft and with brightness more than ambient light. It shall confirm the latest specification issued by railway board (also uploaded).
Supply of Auto change Over panel for CLS 25KVA Numbers 150A capacity as per RDSO specification no. TI/SPC/PSI/CLS/0023
Erection ,Testing commissioning of Auto change Numbers Over pannel for CLS 25KVA 150A capacity as per RDSO specification no.TI/SPC/PSI/CLS/0023 PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, commissioning of I- Phase 5 KVA, 120 volt DC input UPS of Microteck or similar make with battery bank of 12 V, 10 Nos Tubular batteries of OKAYA of similar make each of 150AH for emergency supply.
Design, fabrication, supply and fixing of GI Metre perforated horizontal cable- tray with all connected accessories viz- bend, tree, cross, reducer, 45 ° horizontal bend, coupler plates etc.including painting besides clamping, shifting of existing cables into the trenches along with tagging and labling of shifted cables with numbering sleeves fot easy identification. size 300 mm width , 100 mm depth, 2 mm thickness.
Supply, commissioning of 1200mm sweep BEE 5 Star rated ceiling fan with Brushless Direct current (BLDC) Motor,Class of Insulation B,03 no Blade,30 Centimeter long down Rod 02 No Canopiess,Shackle kit,Safety Rope,Copper winding power factor not less than 0.9 ,Service value (CM/M/W)Minimum 6.00 Air delivery minimum 210 Cum/Min,350 RPM(Tolerance as per IS:374-2019) THD Less than 10 % remote or Electronic regulator unit for speed control & all remaining accessories including Safety fin,Nut Bolts,Washers,temperature rise=75 degree C Maximum,Insulation Resistance more than 2 Mega ohm suitable for 230 volts,50 HZ,Single phase,AC Supply,Earthing with suitable fan hook etc,complete as required.
Supply, commissioning of maintenance free Earthing RDSO spec no.RDSO/SPN/197/2008 or Latest consisting of. Earth electrode of copper bonded high tensile low carbon steel rods, specially designed for electrical grounding as per RDSO Spec. No RDSO/SPN/197/2008 or latest. RDSO approved earth enhancing compound in 10 Kg pack - 05 No. Copper tape of 25mm x 6mm x 300mm with 99.9% purity - 2 Nos and another of 25mm x 6mm x 150mm to terminate on earth electrode Supply of insulated connecting cable as per RDSO Spec No RDSO/SPN/197/2008 or latest to connect equipment bus bar 10 meter each earth Installation of Unit Earth consisting materials covered in item 1 in accordance to RDSO Spec No RDSO/SPN/197/2008 or latest Digging of earth to the required depth Insertion of electrodes - 1 Nos Filling of earth enhancing compound, provision of exothermic weld connection on copper tape of 25mmx 6mmx 150mm to the earth electrodes. (All materials tools and fixtures required for the weld to be arranged by the contractor) -5No. 25mm x 6mm x 150mm to the earth electrodes (All materials tools and fixtures required for the weld to be arranged by the contractor)- 1 No. Provision of exothermic weld connection on copper tape of 25mm x 6mm x 150mm to the earth electrodes (All materials tools and fixtures required for the weld to be arranged by the contractor) - 1 No. Provision of exothermic weld one to connecting cable to the earth electrodes and another to the copper tape to be fixed inside the Equipment/Relay rack/apparatus room (features for mounting the copper tape inside the relay room, weld materials, tool, fixtures and other materials required for the weld shall be arranged by the contractor). PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, commissioning of wall mounted Bracket Fan 750 MM including heavy duty associated works as per relevant technical specification. Make-Bajaj ,Havells etc.
Supply,fixing,testing,connecting commissioning of LED Type 12 watt LED Surface panel round spot light,suitable for 230 Volts,50 Hz AC supply with wiring and flexible PVC pipe as requires Make-Havells, orient or ISI Marked.
Supply, commissioning of 200W LED flood Light fittings as per IS:10322. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute lights, to position and protect the light source and to connect the light source to a branch circuit. The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:-(1):-NICHIA/CREE /OSRAM/SEOUL/ PHILIPS/LUMILEDS /LEDNIUM (2):- LEDs to IS:16105(2012).IS:16108(2012),IEC:62471.Type LED:- High power LED,SMD(Surface Mounting device) /COB(Clip on board).1.Input operating voltage :-105-295 V AC.2:- Normal Voltage-220V AC,3.Driver type: constant current driver with short circuit protection. 4.LED life:- >=50000 burning hours.5.Depreciation:- 30% max.after 50000 burning hours.6.Control of distribution:-Full cut off. 7.Surge protection:4KV.8.Drive component :Industrial grade only.9.Efficiency of driver electronic: >= 85%.10.Beam angle:>=140 degree along with road and >=80 degree across the road.11.Colour temperature:5000- 6500K.12.Colour rendering index( CRI ): >=75 . 13. Ingress protection:IP- 66.14.Lumen output: >=120 lumens/watt.15.Power factor:- >=0.95.16.Total hormonics distrotion(THD):- <15%.17.Lamp cover: Toughened glass or UV stabilsed poly carbonate.18.Finishing:Power coated /Anodized.19.Secondry optics:poly carbonate reflector/ polycarbonates lens.20.Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum.21.Mounting:Suitable for existing pole/Truss/Lantern mounted.22.Certificate:Firm to submit LM80(In respect of LED used)& LM79(In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for compliance of BIS/IEC.23.Warranty:Firm to submit warranty certificate for five year along with the supply. All fittings shall be fitted with new suitable bend/elbow with clamp and proper nut and bolt and connection with twisted twin flexible cord of minimum size 16/1 mm copper conductor as per r e l e v a n t technical specification. Material parameters must remain unchanged during entire warranty period.
Shifting work of HT/LT Panels/ Transformers /DG Job set, Reinstallation, commissioning & testing of all (foundation not included) with provision of tripping arrangement through control circuit
LT fault charges PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, installation, testing, connecting and Set commissioning of LED base name board of different stations (01 set includes 01 No Hindi, 01 No English& 01 No Urdu name board) with power LEDs, Drivers & wiring of board. The signage board should have alphabet of vertical peak height of 600 mm and proportionate horizontal span. Approximate size of Hindi, English signage panel shall have Length-6400 mm, Height- 912 mm Detailed spec. mentioned in tender document. Note -01 set includes a. Hindi board 01 No b. English board 01No c. Urdu board 01 No.
Excavation of cable trench in soft morrum plain Metre ground concrete/pucca surface etcand back filling of cable for laying of LT cables including placing of bricks incross position etc.
Excavation of cable duct by horizontal boring Metre method 2.5 to 4.0 mtr depths from the bottom of sleeper for trench less track crossing and laying of120 mm outer dia. DWC pipe. The work shall be done as per extent practice and instruction of site engineer. It includes supply of DWC/HDPE pipes conforming to IS : 14930 (Part 2, 2001).( Rex Poly Extrusion or similar make. Mouling shall be carried out in the presence of Representative of Dy.CEE/GSU/PRYJ. In this regards written information shall be submitted before two days of execution. Total 11194638.89
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC2022
ATTACHMENT
LatestANNEXUREVVA.pdf
ATTACHMENT
Ann-VIBforFinanacialcriteria.pdf
ATTACHMENT
ACS01to11_1.pdf
ATTACHMENT
SIGNAGEEXPLANATORY.pdf
ATTACHMENT
Signageguidelines_PRYJ.pdf
ATTACHMENT
TENDERDOCUMENTGMC.pdf
ATTACHMENT
GCC_April-2022_2022_CE-I_CT_GCC-2022_POLICY_27.04.22_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].