Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.6 CrAccepted-AOC 106 BALAJI NAGAR RAWATBHATA | ₹12.6 Cr | L1 | Accepted-AOC Low Quoted |
| 2 | L2₹12.6 CrRejected-AOC | ₹12.6 Cr | L2 | Rejected-AOC High Quoted |
| Sl No | Description | Qty | Unit | ULTRA TECH ENGINEERS L2 | Om Engineering and Construction Company L1 |
|---|---|---|---|---|---|
| 1.00Supply, installation and commissioning of wall mounted/ cassette type Independent split Air conditioner units meeting the technical requirements specified in technical specification & rated cooling capacity, given below; The scope of work includes a) supply and installation of copper tube (min 3 meter length - liquid & gas lines individually) with insulation material and power & communication cable, comsumables such as fasteners and ODU bracket, b) pressure testing, vacuumising, refrigerant charging and commissioning of the units c) Supply of IDU LCD remote controller, voltage stablizer of required rating as per technical specification. The work also includes transportation, storage, shifting to the location, providing tools and tackles, manpower, machineries, scaffoldings, consumables including fasteners, leveling, aligning with base frame/ flanges, erection, fixing of vibro-isolators, bolting as per manufacturer documents, inspection, preparation and handing over of as built drawing & commissioning reports as per technical specifications for acceptance of NPCIL. | |||||
| 1.10 | 1 TR - -5 star rating (inverter type), Wall mounted | 40 | Set | 49,900 ₹20.0 L | 47,101 ₹18.8 L |
| 1.20 | 1.5 TR - 5 star rating (inverter type) Wall mounted | 220 | Set | 54,100 ₹1.2 Cr | 51,101 ₹1.1 Cr |
| 1.30 | 1.5 TR - 5 star rating (inverter type) 4 way cassette type | 2 | Set | 68,000 ₹1.4 L | 72,601 ₹1.5 L |
| 1.40 | 2 TR - 5 star rating (inverter type) Wall mounted | 40 | Set | 69,250 ₹27.7 L | 74,101 ₹29.6 L |
| 2.00VRF Outdoor Units: Supply & installation and commissioning of Digital/ Invertor based compressor with Variable Refrigerant Flow [VRF] system (with R-410 A) connectable to multiple indoor units. Outdoor unit shall be factory assembled weather proof casing constructed from heavy gauge mild steel panels with epoxy coated painting. The unit shall be completely factory wired and tested with necessary controls. The compressor shall be highly efficeint Digital scroll type controller. The aluminium fins shall be covered with anti-corrosion resin. Unit shall be equipped with oil recovery system to ensure stable operation with long refrigerant piping. The minimum Energy Efficiency Ratio shall be as per ASHRAE STANDARDS 90.1 -2001 table 6.2.1B . The COP of the system shall be greater than 4 under ARI conditions for 100% load . The unit shall be compatible for BMS operation, as per Specifications and as directed by Engineer incharge. | |||||
| 2.10 | 11 HP Nominal or higher | 3 | Nos. | 4,60,000 ₹13.8 L | 4,50,101 ₹13.5 L |
| 2.20 | 8 HP Nominal or higher | 3 | Nos. | 4,10,000 ₹12.3 L | 4,31,101 ₹12.9 L |
| 3.00VRF Indoor Units: Supply & installation and commissioning of Indoor floor standing unit. The indoor unit shall have independent electronic control valve to control the refrigerant folw rate respond to variations of the airconditioning load of the room. The fan shall be aerodynamically designed turbo multiblade type. Statically and dynamically balanced to ensure lowest noise. The cooling coil shall be made of seamless copper tube. The tube shall be Hydraulically or mechanically expanded and tested for 21Kg/cm2. The minimum Energy Efficiency Ratio shall be as per ASHRAE STANDARDS 90.1 -2001 table 6.2.1B. The cassette/ ducted type indoor unit shall have the inbuilt drain pump arrangement. Indoor units shall have a wireless/ wired remote control, as per Specifications and as directed by Engineer incharge. | |||||
| 3.10 | Floor standing type nominal capacity of 3 TR or higher | 8 | Nos. | 92,500 ₹7.4 L | 94,101 ₹7.5 L |
Tender Value
₹12.3 Cr
EMD Value
₹20.7 L
Closing Date
18 Aug 2025, 5:00 pmClosed
Project Director KK 3 to 6
NPCIL, KKNPP
Supply, installation, testing and commissioning of independent air conditioner units and associated ventilation ducting, structural supports, copper tubing and carbon steel piping, communication and power cabling, anti corrosive painting,
2025_NPCIL_240572_1
NPCIL/KK34/MECH/PT/2025/101
Open Tender
Pipes and Pipe related activities
730 days
KKNPP 3 and 4
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹20.7 L
CMM WORKS
9 Mar 2026
8 Jul 2025
20 Aug 2025
9 Jul 2025
18 Aug 2025
22 Jul 2025
9 Jul 2025 - 17 Jul 2025
18 Jul 2025
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid