Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.1 CrAccepted-AOC 858 SECTOR 23 127021 2021R109 | BHIWANI | HARYANA | 127021 | ₹6.1 Cr Quoted ₹7.8 Cr | L1 | Accepted-AOC Tender Alloted to M/s Shree Balaji Builders as Single agency quoted their rate after 3 times tender. |
Tender Value
₹5.0 Cr
EMD Value
₹10.0 L
Closing Date
16 Dec 2020, 3:00 pmClosed
Executive Engineer
Executive Engineer, PH.Engg. Division No.1 Narnaul
Nangal Choudhary Prov. sewerage system and const. of STP CM Announcement, District Mohindergarh E.Cost Rs. 1470.00 lacs. Design, construction, erection and commissioning of Sewage Treatment Plant of Capacity 3.00 MLD on SBR technology, Main pumping
2020_HRY_151071_1
EIC Pkl No.69711/PHE/Works dt. 14.08.2020
Open Tender
Civil Works
Works
365 days
Narnaul Juriduction
Please refer Tender documents.
3 documents required · 3 mandatory
₹15,000
₹10.0 L
30 May 2021
24 Nov 2020
16 Dec 2020
24 Nov 2020
16 Dec 2020
24 Nov 2020
Amount
MAIN PUMPING STATION Design, construction, erection, testing and commissioning of MPS including O&M for 6 years (1 year during defect liability period after trial run of 3 months and 5 years thereafter). (i)Panel room of 30 sq. mtr. Covered area and PLC room including toilet block of 20 sq. mtr. covered area with RCC framed structure of brick work vitrified glazed tiles flooring, powder coated aluminum frame of size 100mm x 45 mm of 10 gauge of chowkhat, 75mm x 45mm of 10 gauge for door frame, 45mm x 45mm of 10 gauge for window frame with 5mm thick glass AIS/Saint Gobain/Modi Float. The toilet block shall be with one half staff urinal & one European W/C, one wash hand basin as per approved drawings. (ii) RCC inlet chamber, screen chamber, rectangular collecting tank suitable for 3.00 MLD average flow with peak factor of 3.00, landscaping of the campus, providing and installing of Non Clog Submersible Sewage Pumps 1 No. of 375.0 m3/hour, 2 Nos. of 125.0m3/hour and 2 Nos. of 62.50m3/hour at 20 mtr. head each with suitable LT panel equipped with all safety devices, automatic capacitor bank and submersible cable from LT panel to pumping sets complete in all respects. (iii) D.I. K-9 Pipe of suitable dia at MPS including welding and screwing of flanges. ISI marked D.I. fittings, Sluice Valves Non return valves as per requirement even for bye pass arrangement complete in all respects. (iv) 3 Nos. CI Gear operated sluice Gate with SS spindle (SS 410) and seats (SS 304) (2 Nos. for screens and 1 No. for partition of collecting tank) as per design. (v) Supply and installing of 1 No. manual coarse screens of minimum length 6.00 meter for 3.00 MLD average flow (with peak factor of 3.0 i.e. 9.00 MLD) Note : 1. The connecting sewer of same diameter and material of construction, laid at adequate depth between existing sewers to newly constructed structures is included in scope of work. 2. All the infrastructure except construction of staff quarter, and path ways/roads required to be executed at site to make the MPS functional is included in the scope of work of lump sum job. 3. All the pumping Machinery, Panel Board, Level Sensor etc shall be controlled by PLC & SCADA and shall be synchronized with the PLC panels at MPS & STP site through broadband internet facility. 4. The size and quantities of all the above components will be as per approved structural/Hydraulic/Mechanical/ Electrical design to be approved by department before actual execution of work including O&M of 6 years (1 year during defect liability period after trial run of 3 months and 5 years thereafter).
SEWAGE TREATMENT PLANT “Design, construction, erection, testing & commissioning of 3.00 MLD capacity Sewage Treatment Plant based on Sequential Batch Reactor (SBR) Technology complete in all respect including Landscaping, MCC Panel Room & all other contingent Electrical, Mechanical, 2 No. fire screen (1 No. Mechanical & 1 No. Manual) Piping & instrumentation works. With PLC & SCADA Arrangement for STP & MPS along with Synchronizing it with each other including furniture & Laboratory Equipments as per detail given in the bid document and including following components including O&M for 6 years (1 year during defect liability period after trial run of 3 months and 5 years thereafter) (i) 4 Nos. High Mast of 9 mtr. GI Octagonal pole of 4 mm thickness (T=100 mm, B=200 mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 4 Nos. LED Energy efficient lamps on each pole. (ii) Supply and installation of 1 No. SS Main Gate of SS-304 Grade 12 ft. wide main gate and 4 ft. wide wicket gate (total weight not less than 500 kg) at STP site. (iii) Providing and installing 2 Nos. centrifuges (1 No. working + 1 No. Stand bye) including centrifuge feed pump, all fittings, instrumentations, electric panel board etc. as per design complete in all respect including packing dry sludge in 20 Kg. bag and supplying the same to market Kisan Sewa Kendra or as directed by Engineer-in-Charge with the lead as pointed as clause 4.4.5 of the NIT including operation & maintenance of 6 years (1 year during defect liability period after trial run of 3 months and 5 years thereafter)
CCTV CAMERAS Providing and installing 5 CCTV Cameras (3 Nos. Cameras for STP and 2 Nos. Cameras for MPS) complete as per satisfaction of the Engineer-in-Charge, within 96 hours of signing the Agreement along with 90 days recording (DVR), 32 inch LED Screen, 16 Channel DVR at STP site and 8 Channel DVR at MPS site with connectors, cables, poles and power supply with online real-time output facility. The cameras at both the sites i.e. MPS and STP shall be synchronized at STP site Including display of data on continuous basis for up-linking the data to CPCB, HSPCB & PHED web site. i) At STP & MPS site – 1 No. PTZ speed dome 360 degree 50x zoom camera, 3 Nos. 12 mm lens size, 1 No. 3.60 mm lens size. Make :- Sony/ Canon/ Panasonic/ Samsung CCTV Cameras should be installed and commissioned before starting execution of work including operation & Maintenance of 6 years.
TRANSFORMER, D.G. SET & FENCED ENCLOSURES i) Design, supply & erection of 1 No. copper wound Transformer of 100 KVA on load tap changer or suitable capacity on higher side (At STP) of standard make outdoor type, VCB Panel, G.O. Switch, H.T. Metering Panels, APFC Panels along with for each Transformer, 11 KV substation, entire cable network from G.O. Switch to H.T. Metering equipment and from H.T. Metering to Transformer Main to L.T. Panel, Earthing, Safety equipment and any other contingent thereto complete in all respect as per DNIT and getting it passed from Chief Electrical Officer including operation & maintenance of 6 years.
ii ). Design, supply & Erection of 1 No. DG Set of 110 KVA or suitable capacity on higher side (At STP & MPS) capacity with Acoustic Canopy, AMF Panel and Copper Earthing of suitable rate with change over switch & synchronizing panel complete as per DNIT including operation & Maintenance of 6 years.
iii). Construction of HT/ LT Panel room, Centrifuge house, blower room and Lab cum office building including doors, windows & fittings with toilet block including all Sanitary fittings etc. as per drawings attached in DNIT at MPS & STP site covered area with RCC framed structure of brick work with vitrified glazed tile flooring, powder coated aluminum frame of size 100 mm x 45 mm of 10 gauge for Chowkhat, 75 mm x 45 mm of 10 gauge for door frame, 45 mm x 45 mm of 10 gauge for window frame with 5 mm thick glass AIS/Saint Gobain/ Modi Float covered area (200 Sqm) including operation & maintenance of 6 years.
SUB: Online Outlet Effluent Water Quality Monitoring System for BOD, COD, TSS, PH Supply, installation, testing, commissioning, operation and Comprehensive Annual Maintenance of effluent quality monitoring system of 3.00 MLD STP at Village Nangal Kalia for MC Nangal Choudhary for online (Continuous) measurement of PH. Total suspended Solids (TSS), Chemical Oxygen Demand (COD), Biological Oxygen Demand (BOD) by single analyzer with various sensors (Spectral measurement in the UV-VIS range 200-720 mm) performing reagent and chemical free analysis with automatic cleaning of censor, signal cables and power cables, local data acquisition and display of data on continuous basis for up linking the data to CPCB, HSPCB & PHED, TUV approved complete in all respect as per Central Pollution Control Board (CPCB) guidelines for online continuous monitoring system for effluents and as contained in scope of work in the notice inviting tender: a) Multi-parameter measuring converter, for connecting up to 18 intelligent sensor scope including 8 analog inputs/outputs (4 Inputs & 4 outputs) (0/4-20Ma), wide range power supply optical COD/BOD and TSS probe with spectral processing of the UV-VIS range for measurement in the outlet/ effluent/ of Municipal waste water treatment plant of 3.00 MLD STP at Nangal kalia for M.C. Nangal Choudhary with integrated with automatic cleaning. b) Robust digital pH/ORP sensor for pH/ORP electrodes, with built in pre-amplifier & temperature sensor with Automatic Temperature Compensation (ATC) cable length 100 Metre (Minimum). c) Sensor adapter cable for all intelligent sensors, with IP68 water proof connection to the intelligent Sensor Net System, cable length 100 metre (minimum) d) Data transfer to CPCB, HSPCB & PHED servers during 1 year of O&M after commissioning after 3 months trial period (including 1 year of defect liability period). e) Providing GSM 3G, 4G modem with mobile network connectivity including network charges for 6 years of O&M after commissioning after 3 Months trial run (including 1 year defect liability period)
Bidder Name
Amount
M/S SHREE BALAJI BUILDERS(GSTN-NA)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .