Loading…
Loading…
Tender Value
₹26.0 Cr
EMD Value
₹26.0 L
Closing Date
1 Jul 2026, 11:00 am
Development of Institutional Plot No. 1 admeasuring 2457.01 sqm. (43.03 m x 57.10 m) located in Sector-25 at Panchkula, Haryana
NBCC/CPG/Panchkula/Haryana/2026/576
NBCC/CPG/Panchkula/Haryana/2026/576
Open Tender-Domestic
Civil Works General
Panchkula, Haryana
₹59,000
₹26.0 L
10 Jun 2026
10 Jun 2026
1 Jul 2026
1 Jul 2026
GENERAL ABSTRACT OF COST
Amount on Amount on Amount on Total Amount (in
Amount on Amount on Amount on Total Amount (in
S.NO DESCRIPTION
DSR-2023 DSR 2025 Non- DSR Rs.)
A HUDCO BUILDING
1 Civil Work including UGT, Boundary Wall 12,22,61,781.54 4,94,85,623.02 17,17,47,404.56
B External Development Work
2 Rainwater Harvesting Pit 7,48,585.58 7,48,585.58
C Electrical & HVAC Work.
1 CIRCUIT CUM POINT WRING. 22,81,497.00 - 22,81,497.00
2 DISTRIBUTION BOARDS. 1,91,125.00 - 1,91,125.00
3 CABLE TRAYS , RACEWAY , JUNCTION BOX. 4,37,730.00 2,08,454.00 6,46,184.00
5 LIGHTING CONDUCTOR. 73,444.00 - 73,444.00
6 INTERNAL, EXTERNAL LIGHT FIXTURES, FANS & POLE. 5,96,718.00 3,11,560.00 9,08,278.00
8 ELECTRICAL VEHICLE CHARGER (EV CHARGER ) & BOOM BARRIER. 9,82,522.00 1,25,105.00 11,07,627.00
9 SOLAR PHOTOVOLTAIC POWER PLANT . 54,28,000.00 - 54,28,000.00
10 PASSENGER LIFTS ( 13 PASSENGER 884 kg). - 53,05,956.00 53,05,956.00
11 COMPACT SUB-STATION & L T PANEL. - 1,16,63,420.00 1,16,63,420.00
12 DIESEL GENERATOR SET & UNINTERRUPTED POWER SUPPLY (UPS). 1,33,700.00 37,96,924.00 1,51,178.00 40,81,802.00
13 FIRE ALARM & DETECTION SYSTEM & PA SYSTEM. 23,87,911.00 36,750.00 24,24,661.00
Digitally signed by ANKIT
NBCC INDIA LIMITED
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA
GENERAL ABSTRACT OF COST
Amount on Amount on Amount on
S.NO DESCRIPTION
DSR-2023 DSR-2022 Non- DSR
Digitally signed by ANKIT
NBCC (INDIA) LTD
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
BILL OF QUANTITY (CIVIL ITEMS)
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
1.0 CARRIAGE OF MATERIAL
1.1 By Mechanical Transport including loading,unloading and stacking
1.1.2 Carriage of earth
1.1.4 Carriage of excavated rock
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual
means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on
plan) including getting out and disposal of excavated earth lead upto 50 m and for
all lift, as directed by Engineer-in-charge.
Earth work in excavation by mechanical means (Hydraulic excavator) /manual
means in foundation over areas (exceeding 30cm in depth , 1.5 m in width or 10
2.7 sqm on plan), including disposal of excavated earth, for all leads and lifts,
disposed earth to be levelled and neatly dressed.
Filling available excavated earth (excluding rock) in trenches, plinth, sides of
2.25 foundations etc. in layers not exceeding 20cm in depth, consolidating each Cum 6971.16 6971.16 196.00 1,366,347.36
deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Supplying and filling in plinth with sand under floors, including watering, ramming,
consolidating and dressing complete.
Supplying chemical emulsion in sealed containers including delivery as specified.
2.34.1 Chlorpyriphos/Lindane Emulsifiable concentrate of 20%. Ltr. 74.00 74.00 234.75 17,371.50
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-
termite treatment:
Along the external wall below concrete or masonry apron using chemical emulsion
2.35.2 @ 2.25 litres per linear metre including drilling and plugging holes etc.: With metre 123.88 123.88 53.45 6,621.39
Chlorpyriphos/ Lindane E.C. 20% with 1% concentration
Providing and laying in position cement concrete of specified grade excluding the
cost of centering and shuttering - All work up to plinth level
1:4:8 (1 Cement : 4 coarse sand (zone-lll) derived from natural sources : 8 graded
stone aggregate 40 mm nominal size derived from natural sources)
Centering and shuttering including strutting, propping etc. and removal of form for
4.3.1 Foundations, footings, bases of columns sqm 29.80 29.80 392.15 11,686.07
1 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3
coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick
4.17 bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and Sqm 74.44 74.44 749.30 55,777.89
grouted with fine sand, including necessary excavation, levelling & dressing &
finishing the top smooth.
Reinforced cement concrete work in beams, suspended floors, roofs having slope
up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills,
staircases and spiral stair cases above plinth level up to floor five level, including
the cost of centering, shuttering, finishing and excluding reinforcement with
1:1.5:3 (1 cement: 1.5 coarse sand: 3 graded stone aggregate 20 mm nominal
Centering and shuttering including strutting, propping etc. and removal of form for
5.9.1 Foundations, footings, bases of columns etc. for mass concrete. sqm 1945.00 1945.00 392.15 762,731.75
Walls (any thickness) including attached pilasters, butteresses, plinth and string
5.9.3 Suspended floors, roofs, landings, balconies and access platform. sqm 5533.00 5533.00 927.25 5,130,474.25
5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers. Sqm 4026.00 4026.00 736.40 2,964,746.40
5.9.6 Columns, Pillars, Piers, Abutments, posts and Struts Sqm 2535.00 2535.00 961.30 2,436,895.50
5.9.7 Stairs, (excluding landings) except spiral-staircases. Sqm 480.61 480.61 764.95 367,642.62
5.9.16 Edges of slabs and breaks in floors and walls.
5.9.19 Weather shade, chajjas, corbels etc. including edges. sqm 49.57 49.57 951.10 47,146.03
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in
position and binding all complete upto plinth level
5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 153808.072 153808.07 107.85 16,588,200.35
Steel reinforcement for R.C.C. work including straightening, cutting, bending,
placing in position and binding all complete above plinth level.
5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500 D or more. kg 222724.38 222724.38 107.85 24,020,824.38
2 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Providing and laying in position ready mixed or site batched design mix cement
concrete for reinforced cement concrete work; using coarse aggregate and fine
aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland
/Portland Slag cement, admixtures in recommended proportions as per IS: 9103
to accelerate / retard setting of concrete, to improve durability and workability
without impairing strength; including pumping of concrete to site of laying, curing,
5.33 for all leads; but excluding the cost of centering, shuttering, finishing and
reinforcement as per direction of the engineer-in-charge, for the following grades
Note: Extra cement up to 10% of the minimum specified cement content
in design mix shall be payable separately. In case the cement content in
design mix is more than 110% of the specified minimum cement content,
the contractor shall have discretion to either re-design the mix or bear the
cost of extra cement.
5.33.1 All works upto plinth level
5.33.1.2 Concrete of M30 grade with minimum cement content of 350 kg /cum cum 1151.21 1151.21 9,655.70 11,115,738.40
5.33.2 All works above plinth level upto floor V level
5.33.2.2 Concrete of M30 grade with minimum cement content of 350 kg /cum cum 1827.44 1827.44 10,011.35 18,295,141.44
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C.
Add for using extra cement in the items of design mix over and above the
specified cement content therein.
Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in foundation and plinth in:
6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 97.25 97.25 7,132.25 693,611.31
Brick work with common burnt clay F.P.S. (non modular) bricks of class
6.4 designation 7.5 in superstructure above plinth level up to floor V level in
all shapes and sizes in:
6.4.2 Cement mortar 1:6 (1 cement: 6 coarse sand) cum 473.19 473.19 9,105.95 4,308,844.48
Half brick masonry with common burnt clay F.P.S. (non modular) bricks
6.13 of class designation 7.5 in superstructure above plinth level up to floor
6.13.1 Cement mortar 1:3 (1 cement :3 coarse sand) sqm 244.93 244.93 1,150.50 281,791.97
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third
course of half brick masonry.
Brick edging 7cm wide 11.4 cm deep to plinth protection with common burnt clay
6.44 F.P.S. (non modular) bricks of class designation 7.5 including grouting with Mtr 247.75 247.75 59.45 14,728.74
cement mortar 1:4 (1 cement : 4 fine sand).
3 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Stone work, plain in copings, cornices, string courses and plinth courses, upto 75
mm thick in Cement mortar 1:6 (1 cement : 6 coarse sand), including pointing with
white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of
pigment matching the stone shade.
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and
prepolished, machine cut for kitchen platforms, vanity counters, window sills,
facias and similar locations of required size, approved shade, colour and texture
laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints
treated with white cement, mixed with matching pigment, epoxy touch ups,
including rubbing, curing,
moulding and polishing of edges to give high gloss finish etc. complete at all
8.2.2 Granite stone slab of colour black, Cherry/Ruby red
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc.,
including machine polishing to edge to give high gloss finish etc. complete as per
design approved by Engineer-in-Charge.
Extra for providing opening of required size & shape for wash basin/ kitchen sink
in kitchen platform, vanity counter and similar location in marble/ Granite/ stone
work, including necessary holes for pillar taps etc. including moulding, rubbing
and polishing of cut edges etc. complete.
Providing and fixing dry cladding upto 10 metre height with 30 mm thick gang saw
cut stone with machine cut edges of uniform colour and size upto 1mx1m, fixed to
structural steel frame work and/ or with the help of cramps, pins etc. and sealing
the joints with approved weather sealant as per Architectural drawing and
direction of Engineer-in-charge. (The steel frame work, stainless steel cramps and
pins etc. shall be paid for separately).
8.20.2 White sand stone - 30 mm thick gang saw cut stone sqm 380.97 380.97 3,040.10 1,158,186.90
Providing wood work in frames of doors, windows, clerestory windows and other
frames, wrought framed and fixed in position with hold fast lugs or with dash
fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for
9.1.1 Second class teak wood cum 1.96 1.96 142,949.70 280,181.41
Providing and fixing ISI marked flush door shutters conforming to IS :2202 (Part |)
decorative type, core of block board construction with frame of 1st class hard
wood and well matched teak 3 ply veneering with vertical grains or cross bands
and face veneers on both faces of shutters.
4 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
35 mm thick including ISI marked Stainless Steel butt hinges with necessary
Extra for Providing and fixing flush doors with decorative veneering instead of non
decorative ISI marked flush door shutters conforming to IS: 2202 (Part I)
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum
9.23 depth on all edges of flush door shutters (over all area of door shutter to be sqm 22.18 22.18 462.35 10254.92
Extra for cutting rebate in flush door shutters (Total area of the shutter to be
Providing and fixing wooden moulded beading to door and window frames with
iron screws ,plugs and priming coat unexposed surface etc.complete.
9.40.1 2nd class teak wood
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10
mm diameter bolts, nuts and wooden plugs and embedding in cement concrete
block 30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone
aggregate 20mm nominal size).
Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and
screws etc. complete (Copper oxidised as per IS 1378)
Providing and fixing bright finished brass tower bolts (barrel type) with necessary
screws etc. complete :
Providing and fixing bright finished brass 100 mm mortice latch and lock with 6
9.76 levers and a pair of lever handles of approved quality with necessary screws etc. Each 29.00 29.00 854.65 24,784.85
9.81 Providing and fixing bright finished brass handles with screws etc. complete:
Providing and fixing bright finished brass hanging type floor door stopper with
necessary screws, etc. complete.
Providing and fixing aluminium extruded section body tubular type universal
hydraulic door closer (having brand logo with ISI, IS: 3564, embossed on the
9.84 body, door weight upto 36 Kg. to 80 Kg. and door width from 701 mm to 1000 Each 28.00 28.00 983.15 27,528.20
mm), with double speed adjustment with necessary accessories and screws etc.
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-
section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter
of 30 mm thickness. The laminate shall be moulded with fire resistant grade
9.121 unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm metre 135.56 135.56 570.95 77,397.98
thick and shall be filled with suitable wooden block in all the three legs. The frame
shall be covered with fiber glass from all sides. M.S. stay shall be provided at the
bottom to steady the frame.
9.122 Providing and fixing to existing door frames.
5 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
30 mm thick Fiberglass Reinforced Plastic (F.R.P.) flush door shutter in different
plain and wood finish made with fire retardant grade unsaturated polyester resin,
moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks
inside at required places for fixing of fittings and polyurethane foam
9.122.2 (PUF)/Polystyrene foam to be used sqm 55.08 55.08 4,488.95 247,251.37
as filler material throughout the hollow panel, casted monolithically with testing
parameters of F.R.P. laminate conforming to table - 3 of IS: 14856, complete as
direction of Engineer-in-charge.
Providing & Fixing decorative high pressure laminated sheet of plain / wood grain
in gloss / matt / suede finish with high density protective surface layer and reverse
side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of
adhesive of approved quality.
Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim
9.139 Latch & Lock on back side of the Panic Latch of reputed brand and manufacture each 21.00 21.00 8,366.15 175,689.15
to be approved by the Engineer- in- charge, all complete.
Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal
side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm
thick GI sheet ( Zinc coating not less than 120gm/ sqm) suitable for mounting 120
minutes Fire Rated Glazed Door Shutters. The frame shall be filled with mineral
wool Insulation having density minimum 96Kg/cum. The frame will have a
provision of G.I. anchor FAstners 14 nos ( 5 each on vertical style & 4 on
horizontal style of size M10 x 80 ) suitable for fixing in the opening along with
factory made template for SS ball bearing hinges of Size 100x89x3mm for fixing
of fire rated glazed shutter . The frame shall be finished with a approved fire
resistant primer or powder coating of not less than 30 micron in desired shade as
per the directions of Engineer - in- Charge . (Cost of SS ball bearing hinges is
Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 minutes
fire rating confirming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as
per laboratory approved by Engineer-in-Charge, with suitable mounting on door
frame, consisting of vertical styles, top rail & side rail 60 mm x 60 mm wide and
bottom rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet (zinc coating
120gm/sqm) duly filled mineral wool insulation having density minimum 96 kg/cum
and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm
of approved make, including applying a coat of approved fire resistant primer or
powder coating not less than 30 micron etc all complete as per direction of
Engineer-in-Charge (panelling to be paid for seperately).
6 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions
etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less
than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at
distance 75 mm from the edges and 150 mm c/c , including applying a coat of
approved fire resistant primer/ powder coating of not less than 30 micron on G.I.
beading, & special
ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC
2016, IS 16231 (Part 3):2016 and as per direction of Engineer-in-charge
9.164 with glass of required thickness having 120 minutes of fire resistance sqm 33.60 33.60 43,677.65 1,467,569.04
both integrity & radiation control (EW120) and minimum 20 minutes of
insulation (EI20). The manufacturer have to give test report/certification
of fire glass and the glass should have the stamp showing the value of
E, EW & EI. The glass shall be tested in approved NABL accredited lab
or by any other accreditation body which operates in accordance with
ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and
calibration scopes shall be eligible. The maximum glazing size shall
not be more than 1100x2200 mm (w x h) or 2.42 sqm.
Structural steel work riveted, bolted or welded in built up sections, trusses and
10.2 framed work, including cutting, hoisting, fixing in position and applying a priming kg 23342.76 23342.76 133.70 3,120,927.01
coat of approved steel primer all complete.
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes,
channels, plates etc., including welding, grinding, buffing, polishing and making
curvature (wherever required) and fitting the same with necessary stainless steel
nuts and bolts complete, i/c fixing the railing with necessary accessories &
10.28 stainless steel dash fasteners , stainless steel bolts etc., of required size, on the kg 2516.00 2516.00 772.40 1,943,358.40
top of the floor or the side of waist slab with suitable arrangement as per approval
of Engineer-incharge, (for payment purpose only weight of stainless steel
members shall be considered excluding fixing accessories such as nuts, bolts,
fasteners etc.).
Crazy marble stone flooring, including filling the gaps with light shade pigment
with white cement marble powder mixture (3 parts of white cement: 1 part of
marble powder) by weight in proportion of 4:7 (4 cement marble powder mix : 7
11.15 white, black or white and black marble chips of sizes from 1 mm to 4 mm nominal
size by volume), with under layer 25 mm thick cement concrete 1:2:4 (1 cement :
2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size), including
rubbing, polishing andcement slurry etc. complete :
11.15.1 18 mm thick crazy marble stone white, black or as specified sqm 676.2 676.20 1,714.80 1,159,547.76
7 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed
with grey cement slurry mixed with pigment to match the shade of the slab,
including rubbing and polishing complete with base of cement mortar 1 : 4 (1
cement : 4 coarse sand)
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on
12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed
with grey cement slurry mixed with pigment to match the shade of the slabs,
including rubbing and polishing complete.
Providing and laying Vitrified tiles in floor in different sizes (thickness to be
specified by the manufacturer) with water absorption less than 0.08% and
conforming to IS:15622, of approved brand & manufacturer, in all colours and
shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing
11.41A with grey cement slurry @3.3 kg/sqm including grouting the joints with white
cement and matching pigments etc. The tiles must be cut with the zero chipping
diamond cutter only . Laying of tiles will be done with the notch trowel, plier,
wedge, clips of required thickness, leveling system and rubber mallet for placing
the tiles gently and easily.
11.41A.1 Double charge vitrified tile polished finish of size
Providing and laying 500x500x40 mm thick Turf paver (Turfpave XD) on 150 mm
thick sub grade of compacted bed of 20 mm thick nominal size stone aggregate
11.45 and base course and filling with 150 mm thick Jamuna sand, including spreading, Sqm 100.00 100.00 1,708.10 170,810.00
well ramming, consolidating and finishing smooth etc. all complete as per direction
of Engineer-in-charge.
Providing and laying Vitrified tiles in different sizes (thickness to be specified by
manufacturer), with water absorption less than 0.08 % and conforming to |.S.
15622, of approved make, in all colours & shade, in skirting, riser of steps, over
12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with
grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement &
matching pigments etc.
Providing and laying machine cut, mirror polished Marble stone flooring, in
required design (Simple geometrical, abstract etc.) and in patterns in combination
with Italian marble stones of different colours, shades and finished surface texture
etc., in linear portions of the building, all complete as per the architectural
drawings, with 18 mm thick stone slab laid over 20 mm (average) thick base of
cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with white cement
slurry @ 4.4 kg/sqm, including pointing with white cement slurry admixed with
pigment to match the marble shade, including rubbing, curing and polishing etc.
all complete as specified and as directed by the Engineer-in-Charge.
8 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
18 mm thick Italian Marble stone slab, Perlato, Rosso verona, Fire Red or Dark
Emperadore etc.
Providing and laying flamed finish Granite stone flooring in required design and
patterns, in linear as well as curvilinear portions of the building all complete as per
the architectural drawings with 18 mm thick stone slab over 20 mm (average)
thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with
cement slurry and pointing with white cement slurry admixed with pigment of
matching shade including rubbing, curing and polishing etc. all complete as
specified and as directed by the Engineer-in-Charge :
Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or
Providing and laying Polished Granite stone flooring in required design and
patterns, in linear as well as curvilinear portions of the building all complete as per
the architectural drawings with 18 mm thick stone slab over 20 mm (average)
11.56 thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with
cement slurry and pointing with white cement slurry admixed with pigment of
matching shade including rubbing , curing and polishing etc. all complete as
specified and as directed by the Engineer-in-Charge.
Polished Granite stone slab of all colour and texture except Black, Cherry/Ruby
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
stone aggregate 10mm and down gauge) including finishing with cement mortar
1:3 (1 cement : 3 fine sand) as per standard design : In 75x75mm deep chase
Making khurras 45x45 cm with average minimum thickness of 5 cm cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm
12.22 nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm each 9.00 9.00 298.25 2,684.25
cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,
rounding the edges and making and finishing the outlet complete.
9 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Providing and fixing false ceiling at all height including providing and fixing of
frame work made of special sections, power pressed from M.S. sheets and
galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277
and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of
27 mm and 37mm, at
1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5
mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle
hangers of 25x10x0.50 mm of required length with nuts & bolts of required size
and other end of angle
hanger fixed with intermediate G.I. channels 45x15x0.9 mm running
at the spacing of 1200 mm centre to centre, to which the ceiling
section 0.5 mm thick bottom wedge of 80 mm with tapered flanges
of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre,
12.45 shall be fixed in a direction perpendicular to G.I. intermediate channel
with connecting clips made out of 2.64 mm dia x 230 mm long G.I.
wire at every junction, including fixing perimeter channels 0.5 mm
thick 27 mm high having flanges of 20 mm and 30 mm long, the
perimeter of ceiling fixed to wall/partition with the help of rawl plugs
at 450 mm centre, with 25mm long dry wall screws @ 230 mm
interval, including fixing of gypsum board to ceiling section and
perimeter channel with the help of dry wall screws of size 3.5 x 25
mm at 230 mm c/c, including jointing and finishing to a flush finish
of tapered and square edges of the board with recommended jointing
compound , jointing tapes , finishing with jointing compound in 3
layers covering upto 150 mm on both sides of joint and two coats of
primer suitable for board, all as per manufacturer's specification and
also including the cost of making openings for light fittings, grills,
12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board Sqm 541.20 541.20 1,529.10 827,548.92
10 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight
calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true
horizontal level, suspended on inter locking metal grid of hot dipped galvanised
steel sections (galvanising @ 120 grams per sqm including both side) consisting
of main ‘T’ runner suitably spaced at joints to get required length and of size
24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to
centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet,
1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid
of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm
made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x
600 mm panel to from grid of size 600x600 mm, resting on periphery walls
/partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm
12.53 made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm Sqm 141.90 141.90 2,158.15 306,241.49
centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying
15 mm thick densified edges calicum silicate ceiling tiles of approved texture in
the grid, including, cutting/ making opening for services like diffusers, grills, light
fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be
suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to
ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable
rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200
mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections
shall be pre-painted with polyster baked paint, for all heights, as per
specifications, drawings and as directed by Engineer-in-Charge.
Providing and laying roof insulation with 40 mm thick impervious sprayed, closed
cell free Rigid Polyurethane foam over deck insulation conforming to IS - 12432
Pt. Ill (density of foam being 40-45 kg/ cum), over a coat of polyurethane primer
applied @ 6-8 sqm per litre, laying 400 G polythene sheet over PUF spray and
12.56 providing a wearing course of 40 mm thick cement screed 1:2:4 (1 cement : 2 sqm 804.30 804.30 1,570.00 1,262,751.00
coarse sand : 4 stone aggregate 20 mm nominal size) in chequered rough finish,
in panels of 2.5 m x 2.5 m and embedding with 24 G wire netting and sealing the
joints with polymerized
mastic, all complete as per direction of Engineer-in-Charge.
13.1 12 mm cement plaster of mix :
13.11 18 mm cement plaster in two coats under layer 12 mm thick cement plaster
1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement
plaster 1:6 (1 cement : 6 fine sand).
13.16 6 mm cement plaster of mix :
11 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Distempering with 1st quality acrylic distemper (ready mixed) having VOC content
13.41 less than 50 gram/litre, of approved manufacturer and of required shade and
colour all complete to achieve even shade and colour :
New work (two or more coats) over and including water thinnable priming coat
with cement primer having VOC content less than 50 gram/litre
Finishing with Epoxy paint (two or more coats) at all locations prepared and
13.52 applied as per manufacturer’s specifications including appropriate priming coat,
preparation of surface, etc. complete.
13.82 Wall painting with acrylic emulsion paint of approved brand and manufacture to
give an even shade :
13.82.1 Two or more coats on new work Sqm 369.15 369.15 137.45 50,739.67
13.80 Providing and applying white cement based putty of average thickness 1 mm, of
approved brand and manufacturer, over the plastered wall surface to prepare the sqm 4502.00 4502.00 156.05 702,537.10
surface even and smooth complete.
13.83 Wall painting with premium acrylic emulsion paint of interior grade, having VOC
(Volatile Organic Compound ) content less than 50 grams/ litre of approved brand
and manufacture, including applying additional coats wherever required to
achieve even shade and colour.
16.71 Providing and fixing G.I. chain link fabric fencing of required width in mesh
size 25x25 mm made of G.I. wire of dia 3 mm including strengthening with
2 mm dia wire or nuts, bolts and washers as required complete as per the
direction of Engineer-in-charge
19.6 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars
jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2
fine sand) including testing of joints etc. complete :
ALUMINIUM WORK:
12 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Providing and fixing aluminium work for doors, windows, ventilators and partitions
with extruded built up standard tubular sections/ appropriate Z sections and other
sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash
fasteners of required dia and size, including necessary filling up the gaps at
junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene
21 gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and
jointed mechanically wherever required including cleat angle, Aluminium snap
beading for glazing / panelling, C.P. brass / stainless steel screws, all complete as
per architectural drawings and the directions of Engineer-in-charge. (Glazing,
paneling and dash fasteners to be paid for separately) :
21.1.1 For fixed portion
Anodised aluminium (anodised transparent or dyed to required shade according
to IS: 1868, Minimum anodic coating of grade AC 15)
Providing and fixing glazing in aluminium door, window, ventilator shutters and
partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the
architectural drawings and the directions of engineer-in-charge . (Cost of
aluminium snap beading shall be paid in basic item):
With float glass panes of 5.5 mm thickness (weight not less than 12.50 kg/ sqm)
Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by
21.8 providing weather silicon sealant over backer rod of approved quality as per
architectural drawings and direction of Engineer-in-charge complete.
21.8.1 Upto 5 mm depth and 5 mm width metre 2507.96 2507.96 96.75 242,645.13
Providing and fixing aluminium casement windows fastener of required length for
aluminium windows with necessary screws etc. complete.
21.15.1 Anodized (AC 15) aluminium each 192.00 192.00 89.40 17,164.80
Providing and fixing 12 mm thick frameless toughened glass door shutter of
approved brand and manufacture, including providing and fixing top & bottom
pivot & double action hydraulic floor spring type fixing arrangement and making
necessary holes etc. for fixing required door fittings, all complete as per direction
of Engineer-incharge (Door handle, lock and stopper etc.to be paid separately).
STRUCTURAL GLAZING:
Providing and supplying aluminium extruded tubular and other aluminium sections
as per the architectural drawings and approved shop drawings , the aluminium
quality as per grade 6063 T5 or T6 as per BS 1474,including super durable
powder coating of 60-80 microns conforming to AAMA 2604 of required colour
25.1 and shade as approved by the Engineer-in-Charge. ( The item includes cost of kg 837.52 837.52 414.30 346,984.54
material such as cleats, sleeves, screws etc. necessary for fabrication of extruded
aluminium frame work. Nothing extra shall be paid on this account). The weight of
aluminium extruded section shall be taken for purpose of payment.
13 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Designing, fabricating, testing, protection, installing and fixing in position semi
(grid) unitized system of structural glazing (with open joints) for linear as well as
curvilinear portions of the building for all heights and all levels, including:
(a) Structural analysis & design and preparation of shop drawings for the specified
design loads conforming to IS 875 part III (the system must passed the proof test
at 1.5 times design wind pressure without any failure), including functional design
of the aluminum sections for fixing glazing panels of various thicknesses,
cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps
etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-
smoke seals, microwave cured EPDM gaskets for water tightness, pressure
drainage and protection against fire hazard including:
25.2 b.) Fabricating and supplying serrated M.S. hot dip galvanised / Sqm 55.83 55.83 3,510.50 195,991.22
Aluminium alloy of 6005 T5 brackets of required sizes, sections
and profiles etc. to accommodate 3 Dimentional movement for
achieving perfect verticality and fixing structural glazing system
rigidly to the RCC/ masonry/structural steel framework of building
structure using stainless steel anchor fasteners/ bolts, nylon
seperator to prevent bimetallic contacts with nuts and washers
etc. of stainless steel grade 316, of the required capacity and in
required numbers.
c.) Providing and filling, two part pump filled, structural silicone
sealant and one part weather silicone sealant compatible with
the structural silicone sealant of required bite size in a clean
and controlled factory / work shop environment, including double
sided spacer tape, setting blocks and backer rod, all of approved
14 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Providing, assembling and supplying vision glass panels (IGUs) comprising
of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel
units of size and shape as required and specified, comprising of an outer heat
strengthened float glass 6mm thick, of approved colour and shade with
reflective soft coating on surface 2 of approved colour and shade, an inner Heat
strengthened clear float glass 6mm thick, spacer tube 12mm wide,
dessicants, including primary seal and secondary seal (structural silicone
sealant) etc. all complete for the required performances, as per the Architectural
drawings, as per the approved shop drawings, as specified and as directed by
the Engineer-in-Charge. The IGUs shall be assembled in the factory/
workshop of the glass processor.
25.3 (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item Sqm 55.83 55.83 3,718.70 207,615.02
For payment, only the actual area of glass on face # 1 of the glass panels
(excluding the areas of the grooves and weather silicone sealant) provided and
fixed in position, shall be measured in sqm.
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on
face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved
make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light
reflection internal 10 to 15%, light reflection external 10 to 20 %, shading
coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The
properties of performance glass shall be decided by technical sanctioning
authority as per the site requirement.
Extra for openable side / top hung vision glass panels (IGUs) including
providing and supplying at site all accessories and hardwares for the openable
panels as specified and of the approved make such as heavy duty stainless steel
friction hinges, min 4 -point cremone locking sets with stainless steel plates,
handles, buffers etc. including necessary stainless steel screws/ fasteners,
nuts, bolts, washers etc. all complete as per the Architectural drawings, as
per the approved shop drawings, as specified and as directed by the Engineer- in-
Providing, fabricating and supplying shadow box of required size and shape,
for fixing in the spandrel portion of the structural glazing, in linear as well as
curvilinear portions of the building by providing semi -rigid, inorganic, non-
combustible fibre glass wool insulation 50 mm thick, conforming to IS: 8183 and
BS: 3958 Part 5. The insulation layer shall have facing (factory bonded on surface
25.5 # 1 of the fibre glass insulation layer), of black non-woven fibre glass tissue of Sqm 13.96 13.96 2,159.65 30,148.71
nominal thickness 0.5 mm and nominal mass not less than 60 gm / sqm, made of
randomly oriented glass fibres distributed in a binder by a wet- lay process
including fixing 1.5 mm thick solid aluminum sheet backing using, 6 mm thick
cement board including SS rivets, nuts, bolts, washers etc complete.
15 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Providing and laying Neelgiri/Mexican grass turf with earth 50mm to 60mm
2.33 (DSR- thickness of existing ground prepared with proper level and ramming with required
2025 tools wooden (Dhurmos) and than rolling the surface with light roller make the
Horticulture surface smoothen and light, watering with sprinkler and maintenance for 30 days
) or more till the grass establish properly as per direction of officer-in-charge.
7.12 (DSR- Providing and stacking of Bottle palm ht. 270-300 cm bottom girth 40-
2025 50 cm well developed in big HDPE bag as per direction of the officer-incharge.
7.44 (DSR- Providing and stacking of Foxtail palm ht. 240-270 cm bottom girth 35-40 cm well
2025 developed in big size HDPE bag as per direction of the officer-in-charge.
7.71(DSR- Providing and stacking of Plumeria alba dwarf height 90-105 cm. with 3-4
2025 branches and thick stem in big size HDPE bag as per direction of the officer-in-
Horticulture charge
7.72(DSR- Providing and stacking of Plumeria rubara height 120-150 cm., 3-4 branches and
2025 thick stem in big size HDPE bag as per direction of the officer-in-charge.
Illuminated signages (Rate applicable on total plinth area)
TOTAL OF SCHEDULE ITEM 122,261,781.54
NON-SCHEDULE ITEM
Wire-cut brick work (230 × 110 × 75 mm) with common burnt clay F.P.S. bricks of
class 7.5 in superstructure above plinth level up to floor V, in all shapes and sizes,
in 1:6 cement-sand mortar, including scaffolding, curing, and finishing, complete
as per drawings and specifications
DSR-NS-2 Providing and fixing 1st quality vitrified wall tiles of approved make and size, over
cement mortar bed, including jointing with cement slurry and pointing with sqm 534.08 534.08 1,686.45 900,698.38
matching pigment, complete as per specifications.
Providing & fixing in position necessary Glass Door Fittings. The work shall be
MR-1 carried out as per specifications, drawings and as per directions of the engineer-in-
Top Patch - Variable pivot point of 55 or 65mm -With SS 304 cover- Finish: SSS
Bottom Patch- Variable pivot point of 55 or 65mm- With SS 304 cover - Finish:
c.) High security patch lock - Finish: SSS each 4.00 4.00 1,557.00 6,228.00
16 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
32X457MM -D Type Pull Handle 325 back to back fixing for glass, wood and
d.) metal doors in satin stainless steel. Length =457mm, 32mm dia, -Finish-SSS, 304 each 4.00 4.00 2,939.00 11,756.00
Grade; Center to Center - 305mm x 12mm Hole Dia.
Supply and install a 1.5 mm thick pre-applied, flexible PVC-P sheet membrane
with factory-laminated geotextile for waterproofing of raft foundation, resistant to
chlorides and sulphates and ensuring durability for the design life of the structure.
Provide and install a 1.5 mm thick PVC waterproofing membrane with protective
MR-3 layer for retaining walls, ensuring long-term durability and proper installation. sqm 625.86 625.86 1,358.00 849,917.88
Provide and apply a terrace slab waterproofing system comprising 1.2 mm thick
single-component polyurethane (PU) membrane combined with 1 mm thick PVC
MR-4 membrane on the RCC slab, ensuring high elongation, tensile strength, and long- sqm 766.00 766.00 2,019.00 1,546,554.00
term durability, with all surfaces cleaned to expose hairline cracks and aggregate
texture prior to application.
Providing and fixing eco-friendly epoxy primer and two coats of single-component
MR-5 PU waterproofing with 0.3 mm PVC membrane, total thickness ≥1.2 mm on sqm 303.01 303.01 818.00 247,862.18
prepared concrete
Providing and applying two coats of 2-component acrylic cementitious coating
followed by coal tar epoxy coating on the inner side of the tank.
Providing and applying two coats of 2-component acrylic cementitious coating
followed by food-grade epoxy coating on the inner side of the tank.
Providing, fabricating, supplying, and fixing Glass Fiber Reinforced Concrete
(GRC) jali panels of approved pattern, size, and thickness at all heights and levels
as per architectural drawings, including supporting system, anchoring, finishing,
and all incidental works complete
Providing and applying epoxy flooring in basement, consisting of surface
MR-9 preparation, primer coat, epoxy resin layer(s), and finishing coat, with all sqm 779.10 779.10 1,246.00 970,758.60
materials, labour, curing, and incidental works complete.
Providing, fitting, installing, and commissioning of a two-level over-ground puzzle
parking system with mechanical hydraulic system, accommodating 2 cars per
module, each with a carrying capacity of 2000 kg and car dimensions of 5000 mm
length × 2000 mm height, complete in all respects
MR-11 Terrace Garden (Designed to be discussed and approved by HUDCO) nos. 1.00 1.00 1,000,000.00 1,000,000.00
Providing and fixing Vertical Garden System on wall surface comprising of
suitable MS supporting framework, backing panels, modular planting system,
irrigation system, and plantation, complete in all respects as per specifications
Providing, fabricating, supplying and fixing of louvers for covering service/utility
MR-13 shaft, made of aluminium sections, designed to allow ventilation while concealing Sqm 93.96 93.96 6,229.00 585,286.18
shaft area, complete in all respects.
17 Digitally signed by ANKIT
DSR 2023 Qty-Block
DESCRIPTION Unit Qty Rounded Rate DSR Amount
Supply and install 12 mm thick modular toilet cubicle, 600×1930 mm door,
1950 mm divider, 2100 mm overall height with 100 mm bottom gap, complete with
SS hinges, coat hook, knob, occupancy lock, top rail, U-channel, shoe box covers,
floor anchors, and rubber inserts.
Design, supply, fabrication, installation, and handover of a factory-fabricated
external façade glazing system using 24 mm DGU glass (6 mm CT + 12 mm air
MR-15 gap + 6 mm CT), installed on-site with brackets, anchors, fasteners, aluminium sqm 1095.27 1095.27 27,565.00 30,191,089.99
framing, pressure plates, EPDM gaskets, sealants, and all necessary hardware,
complete as per site requirements.
TOTAL OF NON-SCHEDULE ITEM 49,485,623.02
18 Digitally signed by ANKIT
NBCC (INDIA) LTD
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
ESTIMATE - Road Works
DSR NO. DESCRIPTION OF ITEM Rounded
UNIT QTY RATE (RS.) AMOUNT (RS.)
SCHEDULE ITEMS:
1.1. By mechnical transport including loading, unloading & stacking
1.1.4 Excavated rock
2.6 Earth work in excavation by mechanical means (Hydraulic
excavator)/manual means over areas (exceeding 30 cm in depth, 1.5
m in width as well as 10 sqm on plan) including getting out and
disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as
directed by Engineer-in-charge.
2.7 Earth work in excavation by mechanical means (Hydraulic excavator)/
manual means over areas (exceeding 30 cm in depth, 1.5 m in width
as well as 10 sqm on plan) including getting out and disposal of
excavated earth lead upto 50 m and lift upto 1.5 m, as directed by
Engineer-in-charge.
4.1 Providing and laying in position cement concrete of specified grade
4.1.8 excluding the cost
1:4:8 (1 Cement : 4ofcoarse
sandand shuttering
(zone-lll) - All from
derived work natural
5.9 : 8 graded and
Centering stone aggregate
shuttering 40 mm nominal
including strutting,size derived
etc. andnatural
5.9.1 Foundations, footings, bases of columns etc. for mass concrete.
5.9.16 Edges of slabs and breaks in floors and walls
5.9.16.1 Under 20 cm wide
Steel reinforcement for R.C.C. work including straightening, cutting,
5.22A bending, placing in position and binding all complete above plinth level
5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500 D or more. kg 8694.00 8694.00 107.85 937647.90
Add for using extra cement in the items of design mix over and above
5.35 the specified cement content therein. quintal 99.36 99.36 733.50 72880.56
Road-1 Digitally signed by ANKIT
Preparation and consolidation of sub-grade with power road roller of 8
to 12 tonne capacity after excavating earth to an average of 22.5cm
depth, dressing to camber and consolidating with road roller including
making good the undulations etc. and re-rolling the sub-grade and
disposal of surplus earth lead upto 50 mtr.
Extra for compaction of earth work in embankment under optimum
16.2 moisture conditions to give at least 95% of the maximum dry density Cum 437.40 437.40 24.85 10869.39
16.3 Supplying and stacking at site.
16.3.1 90 mm to 45 mm size stone aggregate Cum 162.00 162.00 2098.40 339940.80
16.3.3 53 mm to 22.4 mm size stone aggregate Cum 162.00 162.00 1842.30 298452.60
Laying, spreading and compacting stone aggregate of specified sizes
to WBM specifications in uniform thickness, hand picking, rolling with 3
wheeled road / vibratory roller 8-10 tonne capacity in stages to proper
16.4 grade and camber, applying and brooming requisite type of screening / Cum 270.00 270.00 1046.95 282676.50
binding material to fill up interstices of coarse aggregate, watering and
compacting to the required density .
Providing and fixing in position pre-moulded joint filler in expansion per
Providing and applying 2.5 mm thick road marking strips
(retroreflective) of specified shade/ colour using hot thermoplastic
material by fully/ semi automatic thermoplastic paint applicator
16.62 machine fitted with profile shoe, glass beads dispenser, propane tank sqm 72.00 72.00 747.80 53841.60
heater and profile shoe heater, driven by experienced operator on road
surface including cost of material, labour, T&P, cleaning the road
surface of all dirt, seals, oil, grease and foreign material etc. complete
Road-2 Digitally signed by ANKIT
16.75 Providing and laying C.C. pavement of mix M-25 with ready mixed
concrete from batching plant. The ready mixed concrete shall be laid
and finished with screed board vibrator , vacuum dewatering process
and finally finished by floating, brooming with wire brush etc. complete
as per specifications and directions of Engineer-incharge. (The panel
shuttering work shall be paid for separately). (Note:- Cement content
considered in this item is @ 330 kg/cum. Excess/less cement used as
per design mix is payable/ recoverable
TOTAL OF SCHEDULE ITEMS 5,823,888.84
Road-3 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
S.NO DESCRIPTION DSR-2023/AMOUNT NON SCHEDULED AMOUNT
1 SANITARY FIXTURE 436,469.55 1,139,093.62
SOIL ,WASTE & VENT PIPES AND
4 RAIN WATER PIPING WORK 113,898.70 49,164.60
5 SEWERAGE & DRAINAGE 170,889.15 0.00
6 EARTH WORK 33,285.75 0.00
GRAND TOTAL 4,391,714.55
GRAND TOTAL 4,391,714.55
Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
ESTIMATE - PLUMBING WORK
DESCRIPTION OF ITEM RATE (RS.) AMOUNT (RS.)
ITEM No. UNIT QUANTITY
DSR-2023 NS DSR-2023 NS
SANITARY FIXTURE
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm
with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe,
spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I.
trap with outlet grating and other couplings in C.P. brass, including painting of fittings and
cutting and making good the walls and floors wherever required :
17.5.1 Single half stall urinal basin with 5 litre white P.V.C. automatic flushing cistern Each 1 12,071.75 12,071.75
17.5.2 Range of two half stall urinal basin with 5 litre white P.V.C. automatic flushing cistern Each 10 18,008.75 180,087.50
Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50
cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width
with chase cutter and embedding the stone in the chase with epoxy grout or with cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as
per direction of Engineer-in-charge and finished smooth.
8.10.2 Granite Stone of approved shade Each 16 4,051.85 64,829.60
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I.
17.10 brackets and stainless steel plug 40 mm,including painting of fittings and brackets, cutting
and making good the walls wherever required :
17.10.1 Kitchen sink with drain board
Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per
17.22A the direction of Engineerin-charge. Each 51 1,034.80 52,774.80
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality)
17.31 complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws Each 28 1,607.95 45,022.60
and washers complete.
17.34 Providing and fixing toilet paper holder :
Providing and fixing uplasticised PVC connection pipe with brass unions :
Digitally signed by ANKIT
15mm nominal bore
Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :
18.49.1 15mm nominal bore Each 6 506.80 3,040.80
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved
18.53 quality conforming to IS:8931
18.53.1 15mm nominal bore Each 56 574.30 32,160.80
Providing and fixing C.P. Brass extension nipple (size 15mmx50mm) of approved make and
18.53A quality as per direction of Engineer-in-charge. Each 56 74.80 4,188.80
SUB TOTAL( SANITARY FIXTURE) 436,469.55 0.00
Providing and fixing Rimless,Wall Hung WC with UF soft close slim seat cover, hinges,
accessories set, size: 380x515x360 mm ,concealed flushing cistern & flush plate with wall
mounting frame, Installation kit and “P-Type” drain pipe connection set complete in all
respect as per the direction of Engineer-in-charge.
Providing and fixing health faucet (ABS body) ,1 meter long spirochrome flexible tube & wall
NS-2 hook as per direction of Engineer-in-charge. Each 28 1,211.12 33,911.36
Providing and fixing table top wash basin (425x340x175 mm minimum) with all fixing
NS-3 accessories along with C.P Brass pillar cock with extension body complete in all respect as per Each 28 4,982.11 139,499.02
direction of engineer-in-charge.
Providing and fixing C.P. brass sink cock with pipe swinging spout wall mounted with wall
flange complete in all respect.
Providing and fixing stainless steel waste coupling 32 mm dia full thread with 80mm height
NS-5 complete in all respect. Each 28 605.56 16,955.68
Providing and fixing liquid soap dispenser with glass bottle including all fittings complete in all
Providing and fixing stainless steel hinge type grating with frame for floor traps or drains of
NS-7 required pattern complete in all respect. Each 56 770.71 43,159.92
Providing and fixing Flash touch-free infrared hand dryer with 1150W rated power & carbon
NS-8 brush motor ,material: 304 stainless steel,finish: stainless steel complete in all respect . Each 22 10,955.13 241,012.90
Providing & Fixing of Swing type stainless steel Grab bar , O.D 32 mm , use in disabled toilet
NS-9 complete with brackets suitable for wall installation as per approved sample complete in all Each 6 7,400.44 44,402.65
Providing & Fixing straight stainless steel Grab bar size 600 mm length , O.D 32 mm ,
NS-10 complete in all respect. Each 6 2,087.94 12,527.63
SUB TOTAL( NS-SANITARY FIXTURE) 1,139,093.62
Digitally signed by ANKIT
NON SCHEDULED SOIL ,WASTE & VENT PIPES AND FITTINGS
Providing and fixing Acoustic Multilayer Polyproplene piping system as per EN 1451-Part 1-6
with 3 layer pipe made of PP + PP-MD + PP and one layer fittings in PP MD, push-fit
type,Halogen and Cadmium free, having high impact resistance as per DIN EN ISO 291:2008-
08 , Ring stiffness SN6 6KN/m2 as per ISO 9969, offering sound levels of 21 dBA as per EN
14366 at a flow rate of 4 l/s, water tightness as per EN 1451-1 minimum of 0.5 bar for 15
NS-11 minutes, density of pipe = 1.15gms/cm3, elongation = 0.09mm/mn/K and E modulus 2300-
3000 as per ISO 178, along with factory fitted SBR - NR, NBR lip ring, Fire Behavior
Classification according to EN 13501-1:2009 & classified D-s2-d2 (EN 13501-1), meets the
requirements of EN 4102-2 with Fire Classification B2, Smoke Development Category Q1 &
Drip Formation category TR1. (With all fittings)
(A) 160 mm dia Ultra Silent Pipe with One Socket L 3000 Mtr 130 2,088.14 271,457.97
(B) 110 mm dia Ultra Silent Pipe with One Socket L 3000 Mtr 399 1,017.60 406,023.78
(C) 75 mm dia Ultra Silent Pipe with One Socket L 3000 Mtr 60 868.75 52,124.75
(D) 50 mm dia Ultra Silent Pipe with One Socket L 3000 Mtr 20 452.37 9,047.32
Supply , installation , testing and commissioning Polypropylene (PP) 110mm x 110mm size P
trap (Floor trap) of self cleaning design with Min. 50mm water seal with and without vent
arm jointing with push fit rubber ring socket fittings complete, cutting chases / hole in floors /
slabs and bringing the same in proper condition and shape after placing the trap in right
position in case of suspended / open plumbing or setting the trap in 1:2:4 CC in case of
concealed plumbing , etc. complete, as required. The trap shall be of following sizes:
Temporary airtight, End Cap to be provided to prevent dirt entry.
Supply , installation , testing and commissioning Polypropylene (PP) 110x50x50 mm size
ULTRA SILENT CORNER BRANCH 90 DEG after placing the trap in right position in case of
NS-13 suspended / open plumbing or setting the trap in 1:2:4 CC in case of concealed plumbing , Each 16 1,160.33 18,565.22
etc. complete, as required. The trap shall be of following sizes: Temporary airtight End Cap to
be provided to prevent dirt entry.
Supply , installation , testing and commissioning Polypropylene (PP) ultra silent inspection
Providing and fixing uPVC (SCH-80) pipe for waste, wash basin to floor trap with fittings
NS-15 complete in all respect
SUB TOTAL NON SCHEDULED ( SOIL, WASTE & VENT PIPES) 882,763.72
Digitally signed by ANKIT
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for
hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing
18.7 the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step
CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.
Internal work - Exposed on wall
18.7.2 20 mm nominal outer dia Pipes Mtr 21 335.00 7,035.00
18.7.3 25 mm nominal outer dia Pipes Mtr 71 401.55 28,510.05
18.7.4 32 mm nominal outer dia Pipes Mtr 38 518.75 19,712.50
18.7.5 40 mm nominal outer dia Pipes Mtr 96 702.95 67,483.20
18.7.6 50 mm nominal outer dia Pipes Mtr 16 934.15 14,946.40
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for
hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe
18.8 with clampsat 1.00 m spacing. This includes jointing of pipes & fittings with onestep CPVC
solvent cement and the cost of cutting chases and making good the same including testing of
joints complete as per direction of Engineer in Charge.
Concealed work, including cutting chases and making good the walls etc.
18.8.1 15 mm nominal outer dia Pipes Mtr 39 497.80 19,414.20
18.8.2 20 mm nominal outer dia Pipes Mtr 162 537.60 87,091.20
18.8.3 25 mm nominal outer dia Pipes Mtr 50 627.25 31,362.50
18.8.4 32 mm nominal outer dia Pipes Mtr 22 739.30 16,264.60
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making
18.10 good the walls etc.
Internal work-Exposed on wall
18.10.4 32 mm dia nominal bore Mtr 32 667.00 21,344.00
18.10.5 40 mm dia nominal bore Mtr 57 811.90 46,278.30
18.10.6 50 mm dia nominal bore Mtr 54 1,048.35 56,610.90
Making connection of G.I. distribution branch with G.I. main of following sizes by providing
18.13 and fixing tee, including cutting and threading the pipe etc. complete :
18.13.1 25 to 40 mm nominal bore Each 2 911.90 1,823.80
Providing and fixing gun metal gate valve with C.I. wheel of approved
18.17 quality (screwed end) :
Digitally signed by ANKIT
18.17.1 25mm nominal bore Each 30 622.40 18,672.00
18.17.1 A 20 mm nominal bore Each 12 539.95 6,479.40
18.17.2 32mm nominal bore Each 5 689.60 3,448.00
18.17.3 40mm nominal bore Each 6 826.10 4,956.60
18.17.4 50mm nominal bore Each 3 1,026.65 3,079.95
18.17.5 65 mm nominal bore Each 1 1,742.15 1,742.15
Providing and fixing gun metal non- return valve of approved quality
18.19 (screwed end) :
18.19.4 50 mm nominal bore
18.19.5 65 mm nominal bore
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS :
12701 marked, with cover and suitable locking arrangement and making necessary holes for
inlet, outlet and overflow pipes but without fittings and the base support for tank
SUB TOTAL( WATER SUPPLY) 531,264.45
NON SCHEDULED ( WATER SUPPLY )
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for
hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing
NS-16 the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step
CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.
Internal work - Exposed on wall
(A) 65 mm nominal outer dia(CPVC SCH-80) Mtr 20 1,453.75 29,074.96
Providing & Fixing Stainless Steel Water Cooler ,Number of faucets-2,Cooling Capacity - 40
L/h ,Storage capacity-80 L ,Refrigerant - R-134a eco friendly (Non CFC) USP- #High-quality
stainless steel tank and components for safe drinking water # Reliable reciprocating
NS-17 compressor for longer product life #Accessories: Water inlet hosepipe and overflow pipes Each 5 68,061.13 340,305.67
provided with the unit #Specially designed float valves made of food-grade plastic
#Adjustable pedestals made of highly non-corrosive and strong material including Water
Purifier (RO) of 25 ltr/hour with minimum tank capacity of 6 ltr.
Digitally signed by ANKIT
Self-priming close-coupled centrifugal pumps with built-in ejector system, coupled with a
Asynchronous, squirrel cage rotor, IE2 efficiency class , enclosed construction in aluminum
casing, external ventilation, Protection: IP55. / 415 or 230 V / 50 Hz, Class 155 (F) insulation.
Performances according to EN 60034-1. ,Maximum ambient temperature: 40°C. , (- Single-
phase version: 220-240 V 50 Hz, 2 poles with built-in automatic reset overload protection.
Three-phase version: 220-240/380-415 V 50 Hz), with SS body , SS 304 impeller & with fill &
drain plug , with mechnical seal complying to Mechanical seal with mounting dimensions
according to EN12756
Discharge 40 lpm, 30 mtr head SB) 1 153,793.03 153,793.03
Submersible single stage single entry pumps with C.I.body and C.I. two vane enclosed type
impeller connected to TEFC submersible motor for 415 volts, 3 phase, 50 cycles including
MCC panel with level controllers, auto control, sequential change over facility with one
NS-19 proper working at low level & two proper working at high level with an audible alarm
including all interconnectivity cables, with both pumps connected to common outlet header
including valves, non return valves, lifting chains etc. complete in all respect
(one working + one standby/both working in high flow conditions)
(Solid handiling capacity 10-12mm)
Capacity- 150-200 lpm (Each)
Head - (10- 15) m Set(1W+1
SUB TOTAL NON SCHEDULED ( WATER SUPPLY) 1,034,885.01
RAIN WATER PIPING
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter
12.44 and weighing not less than 440 grams. Each 10 54.70 547.00
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS :
12.41 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for
thermal Expansion,(i) Single socketed pipes.
Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for
unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing
with seal ring conforming toIS : 5382, leaving 10 mm gap for thermal expansion.
12.42.1 Coupler
Digitally signed by ANKIT
12.42.2 Single push fit Coupler
12.42.3 Single tee with door
12.42.6 Shoe (Plain)
Providing and fixing unplastisized PVC pipe clip approved design to unplastisized PVC rain
water pipes by meanes of 50x50x50 mm hard wood plugs,screwed with M.S screws of
12.43 required length,including cutting brick and fixing in cement morter 1:4(1 cement:4 coarse
sand) and making good the wall etc complete.
SUB TOTAL( RAIN WATER PIPING) 113,898.70 0.00
NON- SCHEDULED RAIN WATER PIPING
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS :
NS-20 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for
thermal Expansion,(i) Single socketed pipes.
SUB TOTAL (NON- SCHEDULED RAIN WATER PIPING) 49,164.60
SEWERAGE & DRAINAGE
Providing and laying non-pressure NP2 class (light duty) R.C.C.pipes with collars jointed with
19.6 stiff mixture of cement mortar in theproportion of 1:2 (1 cement : 2 fine sand) including
testing of joints etc. complete :
Digitally signed by ANKIT
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with
R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone
19.7 aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1
cement : 3 coarse sand) finished with floating coat of neat cement and making channels in
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal
size) finished with a floating coat of neat cement complete as per standard design :
Inside size 90x80 cm and 45 cm deep including C.I. coverwith frame (light duty) 455x610 mm
19.7.1 internal dimensions,total weight of cover and frame to be not less than 38 kg(weight of cover
23 kg and weight of frame 15 kg) :
19.7.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Each 4 12,770.55 51,082.20
Constructing brick masonry circular type manhole 0.91 m internaldia at bottom and 0.56m
dia at top in cement mortar 1:4 (1 cement: 4 coarse sand), inside cement plaster 12 mm thick
with cementmortar 1:3 (1 cement : 3 coarse sand) finished with a floating coatof neat
cement, foundation concrete 1:3:6 mix (1 cement : 3 coarsesand : 6 graded stone aggregate
40 mm nominal size), and makingnecessary channel in cement concrete 1:2:4 (1 cement : 2
coarsesand : 4 graded stone aggregate 20 mm nominal size) finishedwith a floating coat of
neat cement, all complete as per standard
0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560 mm
internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less
than 182 kg., fixed in cement concrete 1:2:4 (1cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot
rests and 12mm thick cement plaster at the external surface shall be paid for separately) :
19.9.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 EACH 1 12,725.00 12,725.00
Providing orange colour safety foot rest of minimum 6 mm thickplastic encapsulated as per IS
: 10910, on 12 mm dia steel barconforming to IS: 1786, having minimum cross section as 23
mmx25mm and over all minimum length 263 mm and width as 165 mm with minimum 112
mm space between protruded legs having 2 mm treadon top surface by ribbing or
chequering besides necessary andadequate anchoring projections on tail length on 138 mm
19.16 as perstandard drawing and suitable to with stand the bend test and chemical resistance test Each 16 553.70 8,859.20
as per specifications and having manufacture's permanent identification mark to be visible
even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6
(1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per
Making connection of drain or sewer line with existing manhole including breaking into and
making good the walls, floors with cementconcrete 1:2:4 mix (1 cement : 2 coarse sand : 4
19.21 graded stoneaggregate 20 mm nominal size) cement plastered on both sideswith cement
mortar 1:3 (1 cement : 3 coarse sand), finished with afloating coat of neat cement and
making necessary channels forthe drain etc. complete :
19.21.1 For pipes 100 to 250 mm diameter Each 1 810.45 810.45
Digitally signed by ANKIT
Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar
19.27 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with
frame complete as per standard design :
19.27.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Each 8 5,957.90 47,663.20
SUB TOTAL( SEWERAGE & DRAINAGE) 170,889.15 0.00
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over
areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting
2.6 out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by
Engineer-in-charge.
2.6.1 All kind of soil Cum 15 177.50 2,588.38
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc.
2.25 in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and Cum 9 196.00 1,821.08
watering, lead up to 50 m and lift upto 1.5 m
Excavating trenches of required width for pipes, cables, etc including excavation for sockets,
and dressing of sides, ramming of bottoms,depth upto 1.5 m, including getting out the
2.10 excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in
depth,including consolidating each deposited layer by ramming, watering,etc. and disposing
of surplus excavated soil as directed, within a leadof 50 m :
2.10.1 All kinds of soil
2.10.1.2 Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm dia Mtr 82 352.15 28,876.30
SUB TOTAL( EARTH WORK)
Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
S.NO. DESCRIPTION DSR-2025(E & M) AMOUNT NON SCHEDULED
A FIRE FIGHTING WORK 7,473,279.00 502,354.32
Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
(A) PUMPS AND PANEL
(A) Supplying, installation, testing and commissioning of Electric driven Main Fire Pump
27.1 confirming to IS 12469:2019 suitable for automatic operation and consisting of following,
complete in all respects, as required :
(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body &
bronze impeller with stainless steel shaft, mechanical seal as required.
(C) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM,
suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection
for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-
(D) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as
(E ) Suitable cement concrete foundation duly plastered with anti vibration pads.
27.1.5 2280 lpm at 70 m Head (For Spinkler) Each 1 388,181.00 388,181.00 0.00
Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2
pressure at the highest/farthest point.
(A) Supplying, installation, testing and commissioning of diesel engine driven main
27.2 fire pump conforming to IS 12469: 2019 suitable for automatic operation and
consisting of following, complete in all respects, as required : (Diesel Driven Pump)
(B) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller
with stainless steel shaft, mechanical seal as required.
(C) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant
IS standard complete with auto starting mechanism, 12/24 volts electric starting equipment,
diesel tank,exhaust pipe extended upto 10 m outside pump house duly insulated with 50
mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer,
instruments and protection as per standard specification, stop solenoid for auto stop in the
event of fault with audio indications, painted with post office red colour etc. as required.
(D) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as
FF 1 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
(E ) Suitable cement concrete foundation duly plastered and with anti vibration pads.
Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2
pressure at the highest/farthest point.
(A) Supplying, installation, testing and commissioning of electric driven pressurisation
27.3 pump suitable for automatic operation and consisting of following, complete in
all respects, as required : (Jockey Pump)
(B) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller
with stainless steel shaft, mechanical seal conforming to IS : 1520.
(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3
phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted
type with Class 'F' insulation, conforming to IS-12615: 2018.
(D) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as
(E )Suitable cement concrete foundation duly plastered and with anti vibration pads.
Supplying, installation, testing and commissioning of electric driven terrace pump
27.4 conforming to IS 12469: 2019 suitable for automatic operation and consisting of following,
complete in all respects, as required: (Terrace Pump)
Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze
impeller with stainless steel shaft, mechanical as required.
Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3
(c) phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted
type with Class'F' insulation, conforming to IS-12615: 2018.
M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as
(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
27.5 CONTROL PANELS
FF 2 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical
construction, floor mounted type, fabricated out of 2mm thick CRCA sheet,
compartmentalised with hinged lockable doors, dust and vermin proof, powder coated
of approved shade after 7 tank treatment process, cable alley, inter-connection with
suitable size copper conductor cable/solid copper strip, having switchgears and
27.5 accessories, mountings and internal wiring, earth terminals, numbering etc.
complete in all respect, suitable for main fire pump, pressurisation pump & diesel
pump set complete as per CPWD specification with following in coming and Outgoings,
suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class
IP 42 as required :
27.5.5 Incomings
630A, 50kA 4 Pole MCCB, Ics=100% Icu Rating
Digital Voltmeter 0-500V with selector switch
Ammeter (0-630 A) with selector swtich & CTs etc.
LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps
Set of Copper Bus Bar 800Amps
( Note : All outgoing feeders for pumps should have digital Ammeter with selector
switches, and LED type ON, OFF, trip indicating lamps)
200 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter
suitable for 100 hp pump with overload protection, current sensing type single phase
preventor complete with all acceessories and internal wiring required for automatic
operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets
100 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic
Star/Delta starter with overload protection, current sensing type single phase preventor
complete with all acceessories and internal wiring required for automatic operation,
selector switch for local/remote, auto/manual/OFF operation. - 2 sets
DIESEL ENGINE CONTROL
Control for diesel engine comprising -
FF 3 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as
required, push buttons, start/stop in manual mode
Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on
Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC
volt meter, and 0-20 A DC Ammeter
All standard relays and accessories for automatic operation of diesel engine
System Controller
Designing, Supply, Installation, Testing and commissioning of system controller to
control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace
pump in sequence as per specification consisting of relays, timers. Sensors,
annunciation window for fault indication, complete as per specification
(B) PIPES ,VALVES & ACCESSORIES
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming
to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in
ground including welding, excavation & providing cement concrete blocks as
supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the
trench etc. of following sizes complete as required.
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS
1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts
27.7 bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame
and painting with two or more coats of synthetic enamel paint of required shade complete
27.7.9 200 mm dia (wall thickness 6.3 mm) Meter 18 6,620.00 119,160.00
FF 4 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
Providing, laying, testing & commissioning of 'B' class medium duty G.I. pipe conforming to IS
1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and
27.8 fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two
or more coats of synthetic enamel paint of required shade complete as required
Supplying and fixing single headed internal hydrant valve with instantaneous
Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked
conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and
chain as required :
27.9.2 Single headed Stainless steel Each 7 6,632.00 46,424.00
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia
instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked,
conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as
27.10.2 Single headed Stainless steel Each 5 6,632.00 33,160.00
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with
27.11 bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets
conforming to IS 13095 of following sizes as required :
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN
1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts,
bolts, washers, gaskets and conforming to IS 780 of following sizes as required :
FF 5 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with
orifice of required size to be fitted between flange & landing valve of external and internal
27.13 hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. Each 12 1,436.00 17,232.00
Providing, installation, testing and commissioning of non-return valve of following sizes
27.14 confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated
27.15 out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with
stainless steel flange.
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and
27.16 female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as
27.16.2 Stainless Steel (Grade 304) Each 24 4,667.00 112,008.00
Supplying and fixing first-aid Hose Reel with MS construction spray painted in
27.17 post office red, conforming to IS 884 complete with the following as required.
(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as
(b) 20 mm nominal internal dia gun metal globe valve & nozzle.
FF 6 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
(c ) Drum and brackets for fixing the equipmets on wall.
(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal
27.18 diameter size nozzle conforming to IS 903 suitable for instantaneous connection to
interconnect hose pipe coupling as required :
27.18.2 Stainless Steel (Grade 304) Each 12 3,402.00 40,824.00
Supplying and fixing of fire brigade connection of cast iron body with gun metal male
27.19 instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS
pipe connection conforming to IS 904 as required :
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in
height with air release valve on top and flanged connection to riser, drain arrangement
27.20 with 25 mm dia gun metal wheel valve with required accessories, pressure gauge Set 1 19,402.00 19,402.00
and paintingwith synthetic enamel paint of approved shade as required.
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of
27.21 rating 68 degree centigrade with required accessories :
27.21.1 Pendent Sprinkler Each 475 599.00 284,525.00
27.21.2 Upright Sprinkler Each 170 599.00 101,830.00
27.21.3 Horizontal side wall sprinkler Each 40 699.00 27,960.00
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as
FF 7 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
Providing, fixing, testing & commissioning of installation control valve of
cast iron body, brass/bronze working parts comprising of water motor alarm, bronze
seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound
27.24 continuous alarm when the wet riser/sprinkler system activates, pressure gauges,
emergency releases, strainer, pressure switch, cock valve complete with drain valve
and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate,
gasket etc of follwing sizes as required :
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed)
of stainless steel complete with 15 NPT on reducer thread with maximum working
pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT
27.25 male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple,
2 side brackets, center bracket, stockbar of following sizes complete as required.
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in
27.29 white finish UL Listed or FM approved complete as required. Each 515 264.00 135,960.00
(C ) NON-SCHEDULED ITEMS
Providing and fixing of Fire Hose Cabinet size not less than (2.1 x 1.2 x 0.6 )mtr made out of
M.S. sheet not less than 1.5 mm thick having central opening and Fire hose cabinet door
(40mm x 40mm x 5mm) suitably marked on the outside 'with the letters "FIRE HOSE"
NS-1 including necessary locking arrangement and painting in PO red colour suitable to Each 7 26,424.44 184,971.07
accommodate, internal hydrant valve, 2 nos 15 mtr long Hose pipe, branch pipe, nozzle and
fire man's axe. It shall be fixed inside the FHC Cabinet Complete as required .
Providing & fixing of MS fire Hose box (Double Door) (750mm x 600mm x 250mm) 16 gauge
NS-2 suitable for 2 no. 15mtr. Hose and 1 no short branch pipe. Complete in all respect . Each 5 9,579.00 47,895.00
Providing and fixing stainless steel standard fireman's axe with heavy insulated rubber
NS-3 handle tested to 20000 volts as per IS : 926 complete. Each 7 587.00 4,109.00
FF 8 Digitally signed by ANKIT
NAME OF THE PROJECT: PROPOSED OFFICE BUILDING FOR HUDCO, SECTOR 25, PANCHKULA (HARYANA)
INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
DSR -2025 RATE AMOUNT
(E&M)/NS DESCRIPTIONS UNIT QTY
DSR -2025 DSR -2025
ITEM No's NS NS
Providing & fixing of 25mm dia. gunmetal air release valve with all fittings and forged ball
NS-4 valve on header complete as required and as per enclosed specification. Each 4 1,997.00 7,988.00
Providing and fixing following size Pressure gauge (0-15 Kg/Cm2) complete with shut off
NS-5 valve duly calibrated before installation complete as required & as per enclosed Each 17 249.00 4,233.00
Providing and fixing inspectors test assembly complete with test valve, sight glass sectional
NS-6 drain valve, union with corrosion resistant orifice all complete strictly as per drawing. Each 6 18,000.00 108,000.00
Providing and fixing CO2 type Fire Extinguisher of capacity 4.5 kg confirms to IS 15683,
bearing ISI marked, consisting of High Pressure seamless steel cylinder (IS 7285) and duly
NS-7 approved by Chief controller of Explosive Nagpur, fitted with wheel type valve, fully charged Nos. 12 7,398.84 88,786.11
with CO2 gas (IS 15222), with non- conductor of electricity discharge PVC horn along with
Bend Pipe, internally siphon tube, & mounting brackets having fire rating 55B.
Providing and fixing Stored Pressure (ABC Dry Chemical Powder) type Fire Extinguisher of
Capacity 6 kg Confirms to IS 15683, bearing ISI marked complete with brass forged squeeze
grip type valve fitted with pressure gauge , pressurize with dry Nitrogen gas filled, with
discharge nozzle with wall mounting bracket, having fire rating of 3A & 89B.
Providing and fixing Stored Pressure Water type Fire Extinguisher of Capacity 9 Ltr Confirms
to IS 15683, bearing ISI marked complete with brass forged squeeze grip type valve fitted
with pressure gauge , pressurize with dry Nitrogen gas filled, with discharge nozzle with wall
mounting bracket, having fire rating of 3A.
TOTAL SCHEDULED & NON SCHEDULED 7,473,279.00 502,354.32
FF 9 Digitally signed by ANKIT
NAME OF PROJECT:-HUDCO OFFICE BUILDING, SEC- 25 , PANCHKULA (HARYANA)
SUMMARY OF COST OF STP
S No. DESCRIPTION DSR-2023 Amount (Rs) MR Amount (Rs)
Digitally signed by ANKIT
Supplying , Testing and Commissioning of Electomechanaical of 15 KLD MBBR Technology Package Sewage Treatment Plant including Electro
Mechanical Components.
Sr. Description Qty Unit Rate Amount
Providing Design, Construction and Commissioning of 15 KLD MBBR Technology Package
Sewage Treatment Plant including Electro Mechanical Components
Supply, Installation, Testing & Commissioning of 15 KLD Sewage treatment Plant based on
MBBR technology. (The detail of electro mechanical parts, components, parts of STP systems
are indicative only. The agency /contractor on award of work shall submit schematic design,
system of STP .
1 COARSE SCREEN:
Screening of floating matter Material of construction: SS 304 Type-Coarse
SEWAGE LIFT PUMPS of following specifications:-2Nos (1W +1S )
To feed Pump with positive displacement to take Sewage from Equalization tank to MBBR
tank. Capacity: 1.0 cum / hr, head : 10 meter, Type : Centrifugal, Non clog, Self priming,
construction: CI
3 AERATION GRID FOR EQUALIZATION TANK
For providing air. Accessories: Complete with all piping & all valves with accessories.Material
of construction: UPVC :- 1Set 1 Lot
4 AIR DIFFUSER IN EQUALIZATION TANK
For providing air., Type: Coarse membrane, Material of construction: Silicon :-1Set
5 MBBR TANK - AERATION GRID FOR BIOLOGICAL REACTION Tank
Application - For providing air to biological reactor. Accessories- Complete with piping &
valves, MOC: uPVC :- 1 Job
6 AIR DIFFUSER IN BIOLOGICAL REACTOR: Tank
Application - For providing air to biological reactor, Type- Fine membrane, Material- Silicon :-
7 AERATION GRID FOR MBBR TANK Two
Application: For providing air to Tank Accessories- Complete with all piping & all valves,
Material: uPVC,
8 AIR DIFFUSERS FOR MBBR TANK
Digitally signed by ANKIT
Application - For providing air to MBBR Tank. Type- Fine membrane, Material: EPDM : 1 Job 1 Lot
9.00 MBBR /LAMELLA -Mild Steel Epoxy Painted - MSEP TANK
Supply ,Installation ,Testing & Commissioning of INDION Prefabricated 15 KLD MSEP sewage
treatment plant with MBBR Tank size 3.6 x 2.13 x 2.2 mtr comprising of in built compartments
of , Lamella settling zone with FRP Plates and chlorination Zone for disinfection with all
required all valves,complete piping with all accessories. Application : For removal of BOD/COD 1 NO
& sludge produced in aeration tank. & lamella Settler FRP plate with MSEP box for lamella used
for sludge settlement .Skid Tank MSEP
10 AIR BLOWER WITH ACCESSORIES
Application - Supply of air for mixing OF SEWAGE IN EQUALIZATION & MBBR Tank As
per design, Material of construction – CI, Pressure -not less than 0.35 kg/cm2 Capacity: not less
than 50 cum / Hr 2 Nos
Accessories- MS base plate, safety valves, suction filter, silencer, NRV, V belt, Belt guard, Drive
and driven pulleys (1W+1S) - 2 Job
11 SLUDGE FEED PUMP
Type: self Priming non clog Pump , Capacity: 1.0 cum / hr, Head: 15 meter positive
displacement 2 Nos
Material: CI (1W+1S) : 2 Job
12 HYPO DOSING SYSTEM
Tank capacity: 100 L, Material: HDPE,High density Poly Ethylene/ Poly Propylene, Dosing
Pump Capacity: (Not less than) 6 LPH,
13 FILTER FEED PUMPS
Supplying, installing, testing & commissioning of Horizontal centrifugal filter feed water pumps
CI Head & Base, SS 304 Impeller along with motor, pressure gauge with isolation cock,
Isolation valve, NRV on
delivery line. Isolation valve, strainer at suction. Mechanical seal, suitable vibration elimination
pads of approved design, drain pipe with valve for the pump. The pump shall be suitable for
415±10% volts 3 phase AC supply (solid handling size for this pump shall be – 5 mm). Capacity
: 1.0 m3/Hr at 25 Mtrs Head (1 Working+1 Standby) -2 Job (Note :- It is ensure that pump
should pass the water upto treated water tank)
14 MULTI GRADE FILTER (MGF)
Digitally signed by ANKIT
Multigrade Sand Filter :Supplying, installing,testing and commissioning of FRP filter -NGMF
30 shall be suitable for test pressure of 5.0 kg / cm2 and Working Pressure of 3.5 kg/cm2 shall
include media(Pebbles,Sand, Silex, Fine Sand, Fine Silex), including all standard fittings like 1 No
pressure gauges, sampling cock, backwash , including frontal piping and,valves:
Activated Carbon Filter : Supplying, installing, testing and commissioning of FRP Activated
Carbon filter NGMA 20 shall be suitable for test pressure of 5.0 kg / cm2 and Working Pressure
15 of 3.5 kg/cm2 shall include media(Activated Carbon with supporting Media ), including all 1 No
standard fittings like pressure gauges, sampling cock, backwash, including frontal piping
16 CENTRIFUGE SLUDGE HANDLING
CENTRIFUGE BOWL TYPE TOP LID WITH SS STRAINNER
Sludge holding Tank - All PVC pipeline with all valve, Coupling & including all accessories
CENTRIFUGE - System Suitable for 15 kld stp - 5 kg/day sludge handling capacity .Material:
17 MS with Body painted 1 No
18 ELECTRICAL WORKS
Fabrication, supplying, Installation, Testing & Commissioning of Control panel for 15 KLD STP
shall be fabricated in 2 mm thick CRCA sheet with non- compartment, dust & vermin proof,
machine mounted with suitable size of main AL busbar with (100% neutral), panel should be of
protection IP55 & incomer MCCB and outgoing of suitable rating MCCB/MCB as per rating of
differents Equipments(motors / drives) like pumps,blowers etc for STP of 15 KLD plant. and for
STP, blowers, sludge handling & dosing system, feeder compartment is in scope of work . Make
of Switchgears - Siemens / L & T/Schnieder/ Legrand or equivalent make as approved by 1 No
Engineer-in-charge. CABLING:-cabling shall be provided from control panel to various
units/equipments, Pumps,blowers of entire sewage treatment plant and entire ultrafiltration
system including interconnections and all accessories. Size of cable: As per approved OEM
design & drawing & respective capacity of the motors / drives of STP blowers, dosing pumps.
Control Wiring should be of 2.5sq.mm
19 3000 LTRS HDPE Tank for Treated water Tank 1 NO
TOTAL 4,502,780
Digitally signed by ANKIT
NAME OF PROJECT:-HUDCO OFFICE BUILDING, SEC- 25 , PANCHKULA (HARYANA)
SUMMARY OF COST OF RAIN WATER HARVESTING
S No. DESCRIPTION OF SUB-HEAD DSR-2023 Amount (Rs) MR Amount (Rs)
1 RAIN WATER HARVESTING - 1 No 748,585.58 -
Digitally signed by ANKIT
NAME OF PROJECT:-HUDCO OFFICE BUILDING, SEC- 25 , PANCHKULA (HARYANA)
DETAILED ESTIMATE FOR RAIN WATER HARVESTING
Note:- The given quantities are based on assumptions , the quantities may varies during executionas actual
DSR- QTY FOR 1 DSR-2023 DSR-2023
DESCRIPTION OF ITEMS UNIT MR AMOUNT
2023/MR No. RATE AMOUNT
2.8 Earthwork in excavation by mechanical means ( Hydraulic excavator) / manual means
in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan)
including dressing of sides and ramming of bottoms, lift up to 1.5m, including getting out
the excavated soil and disposal of surplus excavated soil as directed, with in a lead of
2.26 Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated
or stacked materials
2.26.1 All kinds of soil
Qty for 1.5-3.0 M depth RWH & Desilt Chamber Cum 54.71 126.80 6,937.65 0.00
Qty for 3.0-4.5 M depth RWH-Rate 2 Times Cum 41.79 253.60 10,597.40 0.00
Qty for 4.5-5.75M depth-RWH -Rate-3 Times Cum 34.82 380.40 13,246.76 0.00
19.16 Providing orange color safety foot rest of minimum 6mm thick plastic encapsulated as
per IS : 10910 on12mm dia steel bar conforming to IS :1786 having minimum cross
section as 23mm x 25mm and over all minimum length 263mm and width as 165mm
with minimum 112mm space between protrude legs having 2mm tread on top surface
by ribbing or chequering besides necessary and adequate anchoring projections on tail
length on 138mm as per standard drawing and suitable to with dtand the bend test and Nos 2.00 553.70 1,107.40 0.00
chemical resistance test as per specifications and having manufacture's permanent
identification make to be visible even after fixing, including fixing in manholes with
30x20x15cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20mm nominal size) complete as per design.
13.4.1 12 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand) Sqm 54.46 357.35 19,461.28 0.00
13.7 12 mm cement plaster finished with a floating coat of neat cement of mix :
4.1 Providing and laying in position cement concrete of specified grade excluding the cost
of centering and shuttering - All work up to plinth level :
Digitally signed by ANKIT
DSR- QTY FOR 1 DSR-2023 DSR-2023
DESCRIPTION OF ITEMS UNIT MR AMOUNT
2023/MR No. RATE AMOUNT
4.1.8 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) Cum 3.74 6,812.00 25,502.58 0.00
6.2 Brick work with common burnt clay modular bricks of class designation 7.5 in
foundation and plinth in:
6.2.2 Cement mortar 1:6 (1 cement :6 coarse sand) Cum 58.12 6,295.15 365,874.71 0.00
23.1 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method
prescribed in IS: 2800 (part I), including collecting samples from different strata,
preparing and submitting strata chart/ bore log, including hire & running charges of all
equipments, tools, plants & machineries required for the job, all complete as per
direction of Engineer-in-charge, upto 90 metre depth below ground level.
23.1.1 All types of soil
23.3 Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized
PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including
required hire and labour charges, fittings & accessories etc. all complete, for all depths,
as per direction of Engineer -in-charge.
23.4 Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized
PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire
& labour charges, fittings & accessories etc. all complete, for all depths, as per direction
of Engineer-in-charge.
23.5 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in
recharge pit, in the required thickness, for all leads & lifts, all complete as per direction Cum 6.28 1,509.80 9,481.54 0.00
of Engineer-in-charge.
23.6 Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the
recharge pit, over the existing layer of boulders, in required thickness, for all leads & Cum 6.28 1,538.25 9,660.21 0.00
lifts, all complete as per direction of Engineer-in-charge.
23.7 Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in
recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as Cum 6.28 1,538.25 9,660.21 0.00
per direction of Engineer -in-charge.
23.8 Gravel packing in tubewell construction in accordance with IS: 4097, including providing
gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all Cum 1.50 2,024.50 3,036.75 0.00
complete as per direction of Engineer-in-charge
Digitally signed by ANKIT
DSR- QTY FOR 1 DSR-2023 DSR-2023
DESCRIPTION OF ITEMS UNIT MR AMOUNT
2023/MR No. RATE AMOUNT
5.1 Providing and laying in position specified grade of reinforced cement concrete,
excluding the cost of centering, shuttering, finishing and reinforcement - All work up to
5.1.2 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm
5.9 Centering and shuttering including strutting, propping etc. and removal of form for
5.9.3 Suspended floors, roofs, landings, balconies and access platform Sqm 15.56 927.25 14,428.01 0.00
5.9.16 Edges of slabs and breaks in floors and walls
5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in
position and binding all complete upto plinth level.
TOTAL OF RAIN WATER HARVESTING 748,585.58 0.00
Digitally signed by ANKIT
NBCC INDIA LIMITED
NAME OF THE WORK :- HOUSING AND URBAN DEVELOPMENT CORPORATION LIMITED, NEW DELHI.
ABSTRACT OF COST
COST AS PER COST AS PER DSR AS PER MARKET TOTAL AMOUNT
COST AS PER COST AS PER DSR AS PER MARKET TOTAL AMOUNT
DSR 2023 (RS.) 2025 (RS.) RATE (RS.) (Rs.)
1.0 SUB HEAD-I :- CIRCUIT CUM POINT WRING. 2,281,497.00 - 2,281,497.00
2.0 SUB HEAD-II - DISTRIBUTION BOARDS. 191,125.00 - 191,125.00
3.0 SUB HEAD-III - CABLE TRAYS , RACEWAY , JUNCTION BOX. 437,730.00 208,454.00 646,184.00
4.0 SUB HEAD-IV - EARTHING. 684,336.00 - 684,336.00
5.0 SUB HEAD-V - LIGHTING CONDUCTOR. 73,444.00 - 73,444.00
6.0 SUB HEAD-VI - INTERNAL, EXTERNAL LIGHT FIXTURES, FANS & POLE. 596,718.00 311,560.00 908,278.00
8.0 SUB HEAD-VIII -ELECTRICAL VEHICLE CHARGER (EV CHARGER ) & BOOM BARRIER. 982,522.00 125,105.00 1,107,627.00
9.0 SUB HEAD-IX -SOLAR PHOTOVOLTAIC POWER PLANT . 5,428,000.00 - 5,428,000.00
10.0 SUB HEAD-X: PASSENGER LIFTS ( 13 PASSENGER 884 kg). - 5,305,956.00 5,305,956.00
11.0 SUB HEAD-XI:COMPACT SUB-STATION & L T PANEL. - 11,663,420.00 11,663,420.00
12.0 SUB HEAD-XII -DIESEL GENERATOR SET & UNINTERRUPTED POWER SUPPLY (UPS). 133,700.00 3,796,924.00 151,178.00 4,081,802.00
13.0 SUB HEAD-XIII:FIRE ALARM & DETECTION SYSTEM & PA SYSTEM. 2,387,911.00 36,750.00 2,424,661.00
14.0 SUB HEAD - XIV :- IP CCTV SYSTEM . 1,749,565.00 - 1,749,565.00
15.0 SUB HEAD -XV:-HVAC SYSREM (VRV SYSTEM). 26,564,970.00 4,242,037.00 30,807,007.00
TOTAL (I+II+III+IV+V+VI+VII+VIII+IX+X+XI+XII+XIII+XIV+XV) 133,700.00 45,845,896.00 23,800,073.00 69,779,669.00
GRAND TOTAL (Rs.) 69,779,669.00
GRAND TOTAL (Rs.) 69,779,669.00
Digitally signed by ANKIT
NBCC INDIA LIMITED
NAME OF THE WORK :- HOUSING AND URBAN DEVELOPMENT CORPORATION LIMITED, NEW DELHI.
DSR -2025/NS Qty NS Rate (Rs) DSR-2025 Amount NS Amount
Description of items Unit 2023/2025
Nos. (Rs) (Rs)
SUB HEAD-I:CIRCUIT CUM POINT WRING.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper
conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box
and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
1.54 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent
switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel
conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as
Wiring for light/ power plug with 2X4 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ 864000
1.5 recessed steel conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop Meter 1800 480
earthing as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper
1.7 conductor, single core cable in surface/ recessed steel conduit as required
1.7.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Meter 600 414 248400
1.7.3 2 X 4 sq. mm + 1 X 4 sq. mm earth wire Meter 200 476 95200
1.7.4 2 X 6 sq. mm + 1 X 6 sq. mm earth wire Meter 100 652 65200
1.7.8 4 X 4 sq. mm + 2 X 4 sq. mm earth wire Meter 20 744 14880
1.7.9 4 X 6 sq. mm + 2 X 6 sq. mm earth wire Meter 120 1001 120120
1.7.10 4 X 10 sq. mm + 2 X 6 sq. mm earth wire Meter 120 1253 150360
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing
1.17 surface/ recessed steel/ PVC conduit as required.
Supplying and drawing co-axial TV cable RG-6 grade,0.7 mm solid copper conductor PE insulated, shieldedwith fine
1.19 tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. Meter 120 54 6480
Supplying and fixing of following sizes of steel conduitalong with accessories in surface/ recess including painting in
1.20 case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including
connections but excluding modular plate etc. as required.
1.24.6 Telephone socket outlet Each 5 168 840
1.24.7 TV antenna socket outlet Each 4 168 672
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in
recess etc. as required.
1.27.1 1 or 2 Module (75mmX75mm) Each 20 354 7080
1.27.2 3 Module (100mmX75mm) Each 10 384 3840
1.28 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
Digitally signed by ANKIT
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including
1.31 providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. Each 30 545 16350
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including
1.32 providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as Each 25 659 16475
Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including
1.57 providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting Each 10 807 8070
etc. as required. (Gysers & AC.)
Total of Sub-Head - I 2281497 0
SUB HEAD-II - DISTRIBUTION BOARDS.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB on surface/ recess, complete with
2.3 tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc.
as required. (But without MCB/ RCCB/Isolator)
2.3.2 8 way , Double door Each 6 2773 16638
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415
2.4 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections,
powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
2.4.3 8 way (4 + 24), Double door Each 5 6337 31685
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive
2.10 load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as
2.10.1 Single pole Each 168 285 47880
2.10.3 Double pole Each 6 696 4176
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections,
testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections,
testing and commissioning etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker
2.14 (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker
2.15 (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm
2.21 thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side Each 10 315 3150
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and
2.22 vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. Each 2 340 680
Digitally signed by ANKIT
Total of Sub-Head - II 191125 0
SUB HEAD-III - CABLE TRAYS , RACEWAY , JUNCTION BOX.
Supplying and installaton following size of perforated painted with powder coating M.S.cable trays with perforation
not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers
4.1 MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required.
4.1.1 100 mm width X 50 mm depth X 1.6 mm thicknes Meter 80 623 49840
4.1.3 200 mm width X 50 mm depth X 1.6 mm thicknes Meter 60 775 46500
4.1.4 300 mm width X 50 mm depth X 1.6 mm thicknes Meter 20 866 17320
4.1.11 600 mm width X 62.5 mm depth X 2.0 mm thickness Meter 50 1597 79850
Hot Dipped Galvanized Iron Cable Tray
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness
not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts,
fastner etc as required.
4.6.1 100 mm width X 50 mm depth X 1.6 mm thickness Meter 80 754 60320
4.6.3 225 mm width X 50 mm depth X 1.6 mm thickness Meter 60 991 59460
4.6.4 300 mm width X 50 mm depth X 1.6 mm thickness Meter 20 1062 21240
4.6.11 600 mm width X 62.5 mm depth X 2.0 mm thickness Meter 50 2064 103200
Supplying, installation, testing & commissioning of Race way made from minimum 2.0 mm thick GI raceway, factory
fabricated, with internal partition of the following sizes including providing removable double folded cover of 2.0 mm
thick , knock out holes and fixing accessories & coupling, earthing stud for terminating 8 SWG copper earth wire
NS-1 complete Supports, bends, access boxes, tap off boxes and cross over as per site requirement. (overhead / wall
mounted recovery & junction boxes shall be 2.0 mm thick). The pregalvenised sheet shall be as per IS 277 or BS 2989
having tensile strength of minimum 500 N/sq.m. and minimum zinc coating of 275 GSM & coupler plate. as required
NS- 1.1 100 mm wide x38 mm deep in ceiling/floor Metre. 120 616 73920
NS- 1.2 225 mm wide x38 mm deep in ceiling/floor Metre. 100 1100 110000
NS- 1.3 300 mm wide x38 mm deep in ceiling/floor Metre. 10 1391 13910
Supplying, installation, testing & commissioning of floor/ceiling recessed 2 mm thick pregavanised sheet outlet
junction box including providing cover with provision to adjust overall height, knock outs on four sides to accept
raceways of specified sizes and cutouts to fix required outlets for following size of race ways with painted GI plate (
Colour as approved Architect/Consultant).
Total of Sub-Head - III 437730 208454
SUB HEAD-IV - EARTHING.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry
5.4 enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke Set 14 8351 116914
and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry
5.6 enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke Set 8 15004 120032
and salt as required.
Supplying and laying 6 SWG G.I. wire at 0.50 Meter below ground level for conductor earth electrode, including
connection/ termination with GI thimble etc. as required.
Digitally signed by ANKIT
5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. Meter 270 1246 336420
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Total of Sub-Head - IV 684336 0
SUB HEAD-V - LIGHTING CONDUCTOR.
6.2 Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required. Each 4 422 1688
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting /
nut bolting/ sweating and soldering etc as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as
required.(For vertical run)
Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as
required.(For horizontal run)
Laying copper/ G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
Total of Sub-Head - V 73444 0
DSR-2025 SUB HEAD-VI - INTERNAL, EXTERNAL LIGHT FIXTURES , FANS & POLE.
DSR-2025-8.5 LED Down lighter (COB Type) (System lumen efficacy ≥120 lm/Watt )
Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round / square/
Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the
requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp
range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95,
IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time (LED, Driver &
electrical circuitry), life time of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends ,
CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum
power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in
house NABL lab setup for all testing facilities for LED fixtures. "complete in all respect i/c external connections with
1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with
Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and
all testing required for LED fixtures as per BIS shall be submitted Shape size and CCT shall be as approved by
Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED
junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim
with Aluminium Reflector.
DSR-2025-8.8 LED Panel light 2x2 ft., (System lumen efficacy >135 lm/Watt)
Digitally signed by ANKIT
Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as
per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt,
frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open
circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free, (flicker should
be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial
Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation
Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be
of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.
complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single
core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt
output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size
and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of
aluminium housing such that LED junction temperature shall not rise above 90°C).
DSR-2025-8.11 LED Batten light (System lumen efficacy >135 lm/Watt)
Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material
and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%
,Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge
protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker
should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70%
of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),
SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified
rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/
Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC
insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.
System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures
as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.
(Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above
Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
9.1 Brush Less Direct Current (BLDC) Fan with Remote
Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of
insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope,
copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350
RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app
based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75
0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan
compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor
single core cable and earthing etc. as required.
9.1.3 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) Each 8 2882 23056
EXTERNAL LIGHT FIXTURES.
Digitally signed by ANKIT
Supply, Installation, Testing and Commissioning of 5m Conical Pole with single arm. Material for pole section: Hot
rolled product of non alloy structural steel grade S355, Other parts: MS as per IS 2062. Material as per BS EN 10025
equivalant to Indian standard.. Bottom (O.A.F.) 130mm and top (O.A.F.) 70mm. Size of Base Plate: 220 SQ, thickness
NS-3 of base plate should be minimum 12mm, hole PCD 220, Fdn. bolt of M16. Tolerance on material thickness as per Each 14 13245.00 185430
IS:1852/85. Pole shall be hot dip galvanized as per IS: 2629. 5mtr. octagonal pole with single arm of 500mm length
and 48.3mm dia .as required .
Supply, Receiving, Unloading, Shifting, Installation, Testing & commissioning of 35W LED Post top luminaire
consisting of a high-pressure powder coated die-cast aluminium housing, a canopy made of plastamid and a UV
resistant high impact polycarbonate protector. The luminaire emits a pleasant, glare-free light due to the highly
NS-4 efficient white reflector (symmetrical light distribution). The complete luminaire is sealed to IP 66 & Impact Each 2 12057.00 24114
resistance of IK08. Electronic temperature monitoring prevents overheating of LEDs and power supply within the
LED compartment (ThermiX®). It is designed for LED light sources of 25W having a neutral white light. Surge
protection of 10kV. (For Entrance Gate).as required .
Supply, Installation, Testing & commissioning of IP65 8W LED Bollard with dark grey polyester coated rust proof Die
cast Aluminium housing, with symmetrical dual optics and PC diffuser The luminaire shall have initial system lumen
of 400lm with System efficacy of >50Lumen/W. The LED shall have a CCT of 3000K with LEDs shall be LM80 Compliant
NS-5 with TM21 report for life of 25000 hrs at 35 Deg C. and CRI 80 with beam angle of 360°.The Fixture shall have IP65 Each 10 6406.00 64060
potted driver with THD<25%, PF>0.9, with operating volatge range of 180-270V. The fixture shall comply with IS
10322 part 5/Sec 1 1987 and LM79 LM80 reports are tested and certified by NABL accredited Lab. (for landscaped
area).as required .
Supply, Installation, Testing & Commissioning of Energy saving, 15 watt decorative UP-down Luminaire with wall
surface mounting using COB LED as light source. The fixture shall comply with IS 10322 part 5/Sec 1 1987 and LM79
LM80 reports are tested and certified by NABL accredited Lab. (for building outer wall façade).as required .
Supply, Installation, Testing and Commissioning of 10 w LED Bulkhead with a nominal system lumen output of 1000
lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 25,000
burning hours at L70. The luminaire should have a color temperature of 5700K and CRI > 80. The luminaire shall meet
NS-7 IP65 rating and IK 08 rating with THD < 20% and PF > 0.9. The luminaire housing should made of pressure die cast Each 12 1663.00 19956
Aluminium with polycarbonate front diffuser. The total power consumption should not exceed 6.5W (including
driver). as required
LED Smart Street light fixture, powder coated pressure die cast aluminium (System. System lumen efficacy ≥105
and <120 lm/Watt)
Supplying, installation, Testing & Commissioning of Smart Street light LED fixture, powder coated pressure die
cast aluminium body with built in or separate driver as per the requirement ( < 700ma), Input voltage: 140-270 Volt
AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as
per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK 08, CRI >70,
under voltage and over voltage protection, EMI- EMC as per CISPR-15, lenses for beam angle as per IESNA type
I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time of
minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES
TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), Maximum power consumption
should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c
external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and
earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt
output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape
size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of
aluminium housing such that LED junction temperature shall not rise above 90°C). Smart inbuilt controller shall have
following features.
Digitally signed by ANKIT
1 1.Control and monitor LED luminaries with bi directional control ( Status, Fault, Alarm, dimming level, wattage,
2 to measure voltage, current, power, power factor, apparent energy, active energy, operating hours.
3 Inbuilt ambient light sensor, motion sensor based on Passive Infra Red (PIR).
4 Wi-Fi LoRA/Zigbee/Powerline with ethernet network based IOT feature as per site requirement
or engineer in charge.
5 should be controlled through auto/ manual
6 Programmable level of not less than 48 different light intensity settings,
7 inbuilt repeater & relay signals function to other controllers
DSR-2025-8.21 Solar outdoor LED light .
Supplying, installation, Testing & Commissioning of the integrated type solar PV lighting system on the existing pole
structure, comprising of 35 watt, 6V Mono Passivated Emitter and Rear Contact (PERC) Solar Panel (minimum
efficiency 21%),, Pulse with modulation (PWM)/Maximum Power point tracking (MPPT) Charge Controller in the box
with a sleek appearance and a sturdy structure, is weather-proof, and is simple to install, with Lithium-Iron
Phosphate Battery (LiFePO4), charging time 8-10 hours, Battery backup time 12 hours (minimum), LED fixture watt
35 watt, Input voltage: 12V DC , Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per
IEC 61000-4-5, Driver efficiency >85%, IP-66,IK-08, CRI >70 , under voltage and over voltage protection, Electro
Magnetic Interference (EMI) Electro Magnetic Compatibility (EMC) As per CISPR 15 , lenses for beam angle as per
Illuminating Engineering Society of North America (IESNA) type I/II/III as per the width of the road and the project
requirement, Correlated Colour Temperature (CCT) 5700°K (As per American National Standard Institute (ANSI Bin)),
life time (LED, Driver & electrical circuitry) of 50K hours lamp buring hours till the 70 % of initial Lumen maintained as
per LM80 extrapolation IES TM-21-11 report, automatic swich on/off, Alliuminium or Acrylonitrile Butadiene Styrene
(ABS body), can be installed on a pole or wall. System lumen efficacy >120 lm/Watt output. LM79 & LM80 Test report
and all testing required for LED fixtures as per BIS shall be submitted.. All as per pre approved by Engineer in-charge
complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single
core cable and earthing etc. as required, complete with mounting structure for the battery and accessories suitable
for withstand wind storm speed as per the site location. (Thermal management: heat sink of aluminium housing
such that LED junction temperature shall not rise above 90°C).
8.21.3 35 Watt (System lumen efficacy >120 lm/Watt) Each 6 29329 175974
Total of Sub-Head - VI 596718 311560
NS-8 SUB HEAD-VII- L.T. CABLES.
Supply of following sizes of XLPE insulated Aluminum conductor strip/ wire Armoured, overall PVC sheathed 1.1 KV
grade cables conforming to relevant IS-7098 Code and technical specifications.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of
following size in the existing masonry open duct as required.
10.6.2 Above 35 sq. mm and upto 95 sq. mm Meter 500 58 29000
10.6.3 Above 95 sq. mm and upto 185 sq. mm Meter 120 80 9600
10.6.4 Above 185 sq. mm and upto 400 sq. mm Meter 600 146 87600
Digitally signed by ANKIT
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC
insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars,
DSR-2025-15.14 jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend,
couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm
below ground level) including excavation and refilling the trench but excluding sand cushioning and protective
covering etc., complete as required.
15.16.1 63 mm dia (OD-63 mm & ID-51 mm nominal) Meter 200 289 57800
Total of Sub-Head - VII 671154 1755613
DSR-2025-18 SUB HEAD-VIII - ELECTRICAL VEHICLE CHARGER (EV CHARGER ) .
Supplying Installation, Testing and Commissioning of EV charging station As per specifications and in Compliance to
relevant IS codes etc.
Light EV AC Charger (Mode-3) Power : 7 kW, Input power supply: 1phase 230 +10% Volt, output supply: 230 Volt AC,
Frequency:50 Hz +/-3%, Operational temperature range : -25 to 55 0C (outdoor), -5 to 55 0C (Indoor)., RH upto 95%,
Charging Device as per IS-17017-22-1 EV-EVSE Communication: as per relevant IS Codes, Bluetooth Low Energy, one
Charge Point Plug/ Socket as per IS-60309 and IS-17017-2, Vehicle Inlet/ Connector As per EV manufacturer, suitable
for 2 Wheelers and 4 wheelers. Indoor use: at least IP42; Outdoor use: at least IP54. Mechanical Strength: protection
18.1.1 of the external enclosure against mechanical impact shall be IK08 according to IEC 62262.O/L,S/C protection. Each 4.00 23385 93,540.00
Insulation Resistance > 1 M Ω. Cable Length: 7.5 m. RCD having a rated residual operating current not exceeding 30
mA; Separate RCD for multiple outputs. Telecommunication port of the EV supply equipment according to IS 13252
(Part 1): 2010. OCPP(Open charge point protocol) 1.6J upgradable to ocpp 2.0. Device Should follow 17017 series of
IS codes in general and the installation of the system shall comply with relevant IS Codes.
Parkbay DC Charger (Mode-3) Power Level 2: Normal Power ~24KW and above, 3 phase 415VAC(-40% to +20%),
Frequency:50 Hz +/-5%, output supply: DC 12/24 Volt, Operational temperature range : -25 to 550C (outdoor), -5 to
55 0C (Indoor), RH upto 95%,Charging Device as per Device/protocol: IS-17017-23,EV-EVSE Communication as per IS-
17017-24, ISO-15118, Infrastructure Socket as per IS-17017-2-2/3,Vehicle Connector as per IS-17017-2-3 Vehicle
Inlet/Connector As per EV manufacturer, suitable for 4 wheelers. Indoor use: at least IP42; Outdoor use: at least
18.1.4 IP54. Mechanical Strength: protection of the external enclosure against mechanical impact shall be IK08 according to Each 1.00 888982 888,982.00
IEC 62262. O/L,S/C protection. Insulation Resistance > 1 M Ω. Cable Length: 7.5 m. RCD having a rated residual
operating current not exceeding 30 mA; Separate RCD for multiple outputs elecommunication port of the EV supply
equipment according to IS 13252 (Part 1) : 2010.OCPP (Open charge point protocol) 1.6J upgradable to ocpp 2.0.
Device Should follow 17017 series of IS codes in general and the installation of the system shall comply with relevant
Supplying Installation, Testing and Commissioning of Electromechanical boom barrier with all accessories upto 6
NS-8.7 metre length. as required. Each 1.00 125,105.00 0.00 125,105.00
Digitally signed by ANKIT
Total of Sub-Head - VIII 982,522.00 125105
DSR-2025-17 SUB HEAD-IX -SOLAR PHOTOVOLTAIC POWER PLANT .
Supplying Installation, Testing and Commissioning of on-grid Solar Photovoltaic Power Plant conforming to various
applicable standards BIS, IEC, MNRE guidelines, the Central Electricity Authority Regulations and CPWD Specifications
as amended up to date, consisting of Mono/Poly Crystalline silicon solar cells module, net metering facility,
17.1 necessary control, protections, earthing, cabling, mounting structure, junction boxes, power conditioning units, Real
time online web interfaced Data Monitoring System, Distribution panels, grid connecting arrangement, conduits,
pipes, cable trays and other accessories etc. as required.
High Energy Efficiency Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to
IS 14286/IEC 61215, IS/IEC 61730- Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall
not be less than 23% at STC with temperature coefficient of Pmax better than -0.30% per 0C. PV modules used in
solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than
90% at the end of 10 years and 80% at the end of 25 years. Solar Modules shall be designed to operate in relative
a) humidity upto 100% with temperature between -10 0C and +85 0C. Further, each PV module used in any solar power
project must have Radio frequency identification tag with information such as name of manufacturer, month and
year of manufacturing, country of origin (separately for Solar cell and module), I-V curve, Unique Serial No and Model
No of the module, Wattage, Im, Vm and FF, name of test lab issuing IEC certificate.
Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 415 V AC, three phase, 4 wire, 50Hz +/- 2.5
Hz, output voltage suitable to generate AC with a variation of 10% at nominal voltage. Power with efficiency not less
than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 0C, Minimum IP-
65 for outdoor and Minimum IP 21 for indoor, Built-in meter and data logger, MPPT, switching devices
IGBT/MOSFETs and controller Microprocessor /DSP. PCU/inverter shall be capable of complete automatic operation
including wake-up, synchronization & shutdown. The PCU shall be able to withstand unbalanced load conforming to
IEC standard with shutdown/standby mode. It must be provided with grid islanding along with manual disconnect
b) pole isolation switch besides automatic disconnection. Minimum protections: Mains Under / Over Voltage, Over
current, Over/Under grid frequency, Over temperature, Surge voltage induced at output due to external source,
Short-circuit, Lightening, Anti Islanding (for grid synch. Mode) and other protections as per applicable standards.
LCD/LED display of minimum parameters: DC input voltage, DC current, AC Voltage and current (all 3 phases, in case
of 3 phase), Instantaneous & cumulative AC output power, Daily DC energy produced and other parameters
applicable standard. Communication interface RS 485 / RS 232.
Module mounting structure: The roof top solar plant generation units shall be installed by using supporting
Aluminium/Galvanized MS structure (mass of zinc coating shall be as per IS4759 ) having minimum head room
clearance of 2.4 meter above the terrace level / ground level. The mounting structure would be designed to sustain
c) wind load and seismic parameter of the site of installation. All the structure shall be design as per applicable BIS code
and the material shall also confirm the applicable BIS Code. Structural material shall be corrosion resistant and
electrolytically compatible with the materials used in the module frame, its fasteners, nuts and bolts. The suitable
arrangements for maintenance and cleaning shall be provided.
Real time online web interfaced Data Monitoring System complete with accessories for various parameters such as
Solar Irradiance, temperature, AC Output Voltage and current, Output Power, Power factor, DC Input Voltage and
d) Current, Time Active,Time disabled, Time Idle, Power produced and other parameters as per standard practices.
Digitally signed by ANKIT
Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and
outgoing cable along with glands, lugs and other accessories etc. as required. Each junction box shall be made of
GRP/FRP/Powder Coated Aluminium /cast aluminium alloy with full dust, water & vermin proof arrangement with
e) High quality Suitable capacity Metal Oxide Varistors(MOVs) (semiconductor diode with resistant applied voltage)/
surge arrestors and suitable Reverse Blocking Diodes, isolation switche isolate the DC input to Inverter, copper bus
f) Lightning, surge voltage protection, earthing protection and grid islanding.
Cables: Connections & Interconnections by required size IR/UV protected XLPE insulated copper conductor 1.1 kV
g) grade armored power and control cables(ISI Marked) along with supplying & fixing of necessary channel/conduit, GI
cable trays, supports, lugs, thimble and other accessories etc. as required.
DC Distribution Board And AC Distribution Panel Board: IP65, free standing, metal cladded, having copper bus bar,
h) having required protection and control gears, connection-interconnection, etc. as required. kWp 100 54280 5428000
Total of Sub-Head - IX 5428000 0
NS-9 SUB HEAD-X: PASSENGER LIFTS ( 13 PASSENGER 884 kg).
Supplying, Installation, Testing & Commissioning of following capacity passenger Machine room less (MRL) lift with
regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes,
NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards
for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed
specifications enclosed and as under including all other equipment and accessories complete as required:-
(i) Speed-1 MPS
(ii) Floors-6 (G+4+T)
(iii) Travel -21.4 Meters (approx.)
(iv) Stops & opening- 6 stops and 6 openings
(v) Controller: A.C. variable voltage & variable frequency
(vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.
Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective
selective with/without attendant
(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system
Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel
decorative ceiling with fans (indirect throw) and LED fitting.
(x) The car flooring should be smooth and antiskid as approved by engineer-in-charge.
(xi) Type of doors
Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/
Hairline Finish).
(b) Landing doors: stainless steel scratch proof .
(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.
Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or
stops at floor served by the elevator.
Digitally signed by ANKIT
Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire
rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings,
BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn,
(xiv) Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage
backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1
hour, pit ladder.
The lift doors shall have a vision panel to enable ersons with hearing impairment to signal for help or assistance in
the event of an emergency.
An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) to
(xvi) respond to the emergency requirements of person with
hearing impairment or deafness.
(xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided
Supplying, Installation, Testing & Commissioning of following capacity passenger Machine room less (MRL) lift with
regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes,
NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards
for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed
specifications enclosed and as under including all other equipment and accessories complete as required:-
(i) Speed-1 MPS
(ii) Floors-6 (B+G+4)
(iii) Travel -21.4 Meters (approx.)
(iv) Stops & opening- 6 stops and 6 openings
(v) Controller: A.C. variable voltage & variable frequency
(vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.
Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective
selective with/without attendant
(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system
Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel
decorative ceiling with fans (indirect throw) and LED fitting.
(x) The car flooring should be smooth and antiskid as approved by engineer-in-charge.
(xi) Type of doors
Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/
Hairline Finish).
(b) Landing doors: stainless steel scratch proof .
(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.
Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or
stops at floor served by the elevator.
Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire
rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings,
BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn,
(xiv) Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage
backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1
hour, pit ladder.
The lift doors shall have a vision panel to enable ersons with hearing impairment to signal for help or assistance in
the event of an emergency.
Digitally signed by ANKIT
An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) to
(xvi) respond to the emergency requirements of person with
hearing impairment or deafness.
(xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided
Total of Sub-Head - X 0 5305956
NS-10 SUB HEAD-XI:COMPACT SUB-STATION (CSS) & L T PANEL.
500 KVA COMPACT SUB-STATION.(CSS).
Supplying, Installation, Testing & Commissioning of The 11kV Outdoor Package Sub-Station shall be
consisting of following:
A HT SWITCHGEAR
1 No.11kV, 630Amps 21KA for 3 Sec. SF6 insulated Non-Extinsible Compact switchgear (Type DV)
consisting of One No. fixed Direct Cable Module and one No. Fixed Manual Vacuum Circuit Breaker (VCB)
having inbuilt load break switch and earth switch within SF6 insulated robotically welded non ferrite non
magnetic stainless steel enclosure of thickness 2.5mm having IP 67, with series trip,self powered
microprocessor based numerical 3 O/C & 1 E/F relay (IDMTL + Inst.) protection.
Interconnection between HT switchgear and transformer shall be using 1Cx3x95 sq.mm Al.
unarmorured XLPE Cable .
1 No.Relay shall be self powered of Ashida/C&S Make. ( 50,50N,51,51N) with RS485 communication port
1 No.Protection CT shall be 40/1A 2.5VA 5P10.
1 No. Standard Manometer (SF6 Gas Pressure Indicator)
1 No. Voltage presence indicator (VPIS) for incoming Healthy Indications
1 No.Manual push button for breaker ON/OFF
1 No.Mechanical Indication for Breaker & LBS ON/OFF/EARTHED.
1 No. Operating handle
All incoming modules of the RMU shall be capable for cable termination of 3C x 300 sq.mm Al XLPE
Cable, incoming cable termination kits shall be in the scope of purchaser only.
1 No. 500 KVA 11kV/433V Dyn11 Copper Wound Cast Resin Dry Type (AN) distribution Transformer with
Off Circuit Tap Links (Make: Ames Impex/ECS/OEM Approved vendors)
Off Circuit Tap Links (OCTL), Tapping range +5% to -5% in a steps of 2.5% (4 Steps/5 Positions)
Insulation Class: F
Temp. Rise Shall be 90 Deg. C Over an ambient of 50 Deg.C Temp.
Transformer Losses: As per ECBC
1 No. Rating & Diagram (R&D) Plate (Fitted on Transformer)
1 No. Surgee Arrestor (Fitted on Transformer CCA on HV Side)
Winding Temp. Indicator with Alarm and Trip Contacts
LT PANEL- 800 A Aluminium Busbar (100% for Phase & 50% for Neutrals) Current density
C 1amp/sqmm, having IP2X, Fabrication using 1.5/2mm CRCA sheet steel complete with internal
wiring consisting of following.
INCOMER From transformer
Digitally signed by ANKIT
1 No. 800Amps 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB) with microprocessor based
Ekip Dip release for Overload (O/L), Short circuit (S/C) & Earth Fault (E/F) protection.
1 No. 250A 4P MCCB
1 No. 100A 4P MCCB
1 No. 63A 4P MCCB
1 No. 40A 4P MCB
1 No.LED type Indicating Lamp - RYB, ON-OFF-TRIP.
1 No.LT side metering CT 1000A/ 5A, 5VA, Cl:1.0.
1 No.Digital Multifunction Meter (MFM), CL-1.0 Accuracy with RS485 Port .
D OUTDOOR ENCLOSURE
1 No.Outdoor type enclosure having construction of Galvanised Sheet Steel having 1.5mm thickness for Non-
load bearing & 2 mm for Load bearing partition sheets & Door with HRCA 4 mm base frame. The Enclosure
shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for
Transformer compartment. The enclosure exterior shall be Powder Coated (Colour Light gray and dark
gray ). Each compartment will be provided with the door and pad locking arrangement. The Compartment
illumination lamp with door operated switch shall be provided for MV & LV compartment. As per IEC 62271-
E INTERCONNECTION AND EARTHING
1 No.Interconnection Between HT switchgear & Transformer using 1Cx3Rx95 Sq.mm XLPE Single Core
Aluminum Unarmored Cable & Interconnection between Transformer & LT switchgear using Aluminum
Busbars with aluminum flexible. Internal earthing connections by using 50X6mm GI strips including
Transformer Neutral.
NS-10.2 MAIN L.T. PANEL ( TTA PANEL).
Supply, Installation, Testing & commissioning of Main LT Panel. The panel will be totally enclosed type with, free
standing, floor mounted, indoor duty, dust & vermin proof, , front operated, electrical panel fabricated from 2 mm
thick CRCA Sheet as per specifications & drawing laid in this document and will be complete with the main and
auxiliary bus bars, interconnection wiring, earth bus and will be powder coated finish with 70 micronor more
thickness. All the busbar joint shall be protected by clip on type sleeve. The Main LT Panel shall use all draw out type
breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall have changeover
facility & interlocking through, buscoupler switching, auto operation of incommer and bus coupler etc and having
following incomming and outgoing Air Circuit Breakers, MCCB as per the drawing and specification.
LT Panel shall conform to IEC-61439/CPRI with Form 4B construction (TTA)
Each incoming / outgoing breaker shall have microprocessor release with adjustable over current, short circuit &
earth fault protection with instantaneous as mentioned in specification. The Panel will be made as per detailed
specifications & drawings forming part of this document.
All the MCCB up to 250 Amp shall have thermal release with adustable overload, short circuit & earth fault
protection and above shall have microprocessor release with adjustable overload, short circuit & earthfault
protection. The panel shall be manufactured as per BOQ, tech specification and drawing. Fault level of panel shall be
All the incomings & outgoings of Main LT Panel shall have Multifunction meter with RS-485 communications and
integrated to BMS / SCADA, internal control wiring shall be done. Nothing extra shall be payable.
INCOMING FOR TRANSFORMERS
Digitally signed by ANKIT
1 Nos. 800 Amp FP Electrically operated horizontal drawout type Air Circuit Breaker microprocessor based releases
for O/C,S/C & earth fault protection with instantaneous. (For Transformer Incommer) (50 KA)
INCOMING FROM DG SETS
1 Nos. 800 A feeder incomer and Each incomer breaker feeder shall have following: (For 1 x 800 KVA D.G. Set)
One set Solar provision shall be made as per site conditions.
One set of Generator control relay for Each D.G. Set with accessories for AMF, Load Management, Synchronizing and
Interlocking through micro PLC. (Make of relay - Woodword / Dief).
One number incomer 3P 800 amps EDO breaker with 200 Amp TP neutral contactor. Each breaker shall have
microprocessor based releases for O/C,S/C & earth fault protection with instantaneous. (For each 800 KVA DG Set)
3 No. indicating lamps to show the incoming power along with protection SP MCB's.
1 Nos. Digital Ammeter 800 A wth ASS, CT's.
1 Nos. Voltmeter & VSS.
1 Nos. Multifunction Meter with CT's.
1 No. Load Manager EM 6400 with RS 485 port
1 No. REF relay
Announciation window to cover LLOP, HWT, OIL Pressure, U/V, O/V, U/F, O/F, O/C, E/F, REF relay faults shall be
provided. 2 nos phase reversal relay shall be provided.
Engine should trip on LLOP, HWT, oil temp, O/V, O/F and breaker should trip on other faults.
Initially U/V & U/F will be bye passed till oil pressure is picked up.
Indicating lights for ACB ON / OFF, ACB trip, neutral contactor ON, D.G. on mains, D.G. fails to start.
Generator start /stop facility through push button from panel, necessary cranking relay shall be provided.
Suitable battery charger for 24V with d.c voltmeter & d.c ammeter. D.C voltmeter and ammeter will be analouge
Whenever D.G. stop through PB, load shall be disconnected first.
1 Nos. master trip relay (one for each Incoming Breaker).
1200 Amp TPN busbars of aluminium alloy as per SLD.
INSTRUMENTS FOR TRANSFORMER INCOMMER
1 Nos. Multifunction Meter with CT's.
1 Sets of phase indicating lights (RYB) with protection SP MCB's. (one set for each incoming breaker).
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).
1 Sets trip circuit healthy indicating lamp (one set for each incoming breaker).
1 Sets of CT's one of 800/ 5Amp ratio for APFC relay.
1 Nos. master trip relay (one for each Incoming Breaker).
1 Nos. 3 phase, over voltage & under voltage relay. (one for each Incoming Breaker).
Digitally signed by ANKIT
1 Nos. 3 phase, phase reversal relay with single phasing preventor. (one for each Incoming Breaker).
1 Nos. 8 window announciator with accept, reset push button & hooter. (one for each Incoming Breaker).
1 Nos. Transit Voltage Surge Suppressor (TVSS) with control MCB.
AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.
Micro PLC shall be provided to achieve the AMF, Changeover, Interlocking and synchronizing shall be through
Synchronizing relay for following functions.
Auto start of DG Set in case of grid failure & phase reversal.
Auto stop of DG Set in case of availability of Grid power with correct phase sequence.
Auto changeover
Hardwire and through micro PLC interlocking between each incommer & buscoupler.
Synchronizing of D.G. Set through synchronizing relay.
Necessary hardware shall be provided to achieve above functions including micro PLC with real time clock, digital
inputs/outputs, MMI with 2 line display, power supply, auxillary relays, PB's indication etc. & software for the above.
Automatic system shall be user friendly and shall have manual override.
EACH OUTGOING FEEDER SHALL HAVE DUAL SOURCE DIGITAL MFM & ON-OFF INDICATION LAMP
1 Nos. 630A TP+N Moulded Case Circuit Breaker with microprocessor based adjustable over current, short circuit,
earth fault protections, ON /OFF indication (Isc=50kA).
1 Nos. 320A TP+N Moulded Case Circuit Breaker with microprocessor based adjustable over current, short circuit,
earth fault protections, ON /OFF indication (Isc=50kA).
04 Nos. 200A TP+N Moulded Case Circuit Breaker with microprocessor based adjustable over current, short circuit,
earth fault protections, ON /OFF indication (Isc=50kA).
04 Nos. 160A TP+N Moulded Case Circuit Breaker with microprocessor based adjustable over current, short circuit,
earth fault protections, ON /OFF indication (Isc=50kA).
3 Nos. 100A TP+N Moulded Case Circuit Breaker with microprocessor based adjustable over current, short circuit,
earth fault protections, ON /OFF indication (Isc=50kA).
1 Nos. 40A TP+N Moulded Case Circuit Breaker with microprocessor based adjustable over current, short circuit,
earth fault protections, ON /OFF indication (Isc=50kA).
175 KVAR CAPACITOR - SHALL BE PART OF MAIN L.T. PANEL
1 No 300 Amp FP Moulded Case Circuit Breaker. (To be considered in Main L.T. Panel)
1 Nos. 0 to 500 Volt digital voltmeter with Voltmeter Selector Switch & Protective SP MCB (96mm square).
1 No. 0 to 500 Amp digital ammeter (96mm square) with CT's)
Digitally signed by ANKIT
1 Sets of phase indicating lights (RYB) with protection fuses.
1 Sets breaker 'ON' & 'OFF' indicating lamp.
10 Step Automatic Power Factor Correction relay (APFC relay).
2 Nos. 125 Amp TP MCCB.
3 Nos. 63 Amp TP MCCB.
2 Nos. capacitor duty contactor (one for each 50KVAR capacitor unit).
3 Nos. capacitor duty contactor (one for each 25KVAR capacitor unit).
2 Nos. 50 KVAR Capacitor Bank 525 Volt with 14% reactor.
3 Nos. 25 KVAR Capacitor Bank 525 Volt with 14% reactor.
5 sets of push button stations Red and Green for manual operation of capacitor units with auto/manual selector
1 No. Indicating lamp for each 50 / 25 KVAR capacitor unit to indicate that the unit is 'ON'.
1 No. Toggle switch for changing automatic to manual operation of capacitor units.
NS-10.2 Main LT Panel describe as above Set 1 4368464.00 4368464
NS-10.3 M V PANEL FOR FIRST GLOOR , SECOND FLOOR , THIRD FLOOR & FORTH FLOOR.
A INCOMER FROM EXISTING MAIN LT PANEL
1 Nos. of 200 A, 4P MOTORISED type MCCB with Ics=Ics=50KA having Mircroprocessor based releases for O/L, S/C &
E/F protection.
1 Nos. SPD Type 1
1 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage,
current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Sets - 0-500V, digital Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power
with control SP MCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-400A) Ammeter with ASS with 3 nos. 300/5A CT's
1 Set of 300 A TPN Aluminium Bus Bar with colour coded PVC Sleeves
i) 3 No. 63A 4P MCCB (25 KA)
ii) 2 No. 63A 4P MCCB (25 KA) (SPARE)
iii) 2 No. 40A 4P MCCB (10 KA)
NS-10.3 Main LT Panel describe as above Set 4 400654.00 1602616
NS-10.4 M V PANEL FOR BASEMENT FLOOR + STILL FLOOR , GROUND FLOOR.
A INCOMER FROM EXISTING MAIN LT PANEL
1 Nos. of 160A, 4P MOTORISED type MCCB with Ics=Ics=50KA having Mircroprocessor based releases for O/L, S/C &
E/F protection.
Digitally signed by ANKIT
1 Nos. SPD Type 1
1 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage,
current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Sets - 0-500V, digital Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power
with control SP MCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-250A) Ammeter with ASS with 3 nos. 300/5A CT's
1 Set of 240 A TPN Aluminium Bus Bar with colour coded PVC Sleeves
i) 3 No. 63A 4P MCCB (25 KA)
ii) 2 No. 63A 4P MCCB (25 KA) (SPARE)
iii) 2 No. 40A 4P MCCB (10 KA)
NS-10.4 Main LT Panel describe as above Set 2 357928.00 715856
NS-10.5 M V PANEL FOR LIFT PANEL & ELECTRICAL VEHICLE CHARGER PANEL .
A INCOMER FROM EXISTING MAIN LT PANEL
1 Nos. of 100A, 4P MOTORISED type MCCB with Ics=Ics=50KA having Mircroprocessor based releases for O/L, S/C &
E/F protection.
1 Nos. SPD Type 1
1 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage,
current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Sets - 0-500V, digital Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power
with control SP MCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-150A) Ammeter with ASS with 3 nos. 300/5A CT's
1 Set of 150A TPN Aluminium Bus Bar with colour coded PVC Sleeves
i) 3 No. 63A 4P MCCB (25 KA)
ii) 3 No. 63A 4P MCCB (25 KA) (SPARE)
iii) 2 No. 40A 4P MCCB (10 KA) (SPARE)
NS-10.5 Main LT Panel describe as above Set 2 389568.00 779136
NS-10.6 FRONT OPERATED FEEDER PANEL
Supply, installation, testing and commissioning of outdoor front operated, front access, totally enclosed,
free standing, dust and vermin proof Panel with IP65 ingress protection, fabricated from 2 mm thick CRCA
sheets, with hinged, gasketted and lockable doors including the cost of interconnections, copper crimping
lugs, brass glands, bonding to earth and painting, suitable for use at 415 volts, 3 phase 4 wire 50 Hz system
with 31 MVA rupturing capacity at 415 volts complete as per specifications, as required and as below.
Digitally signed by ANKIT
External lighting Feeder piller
1 No. 40A,4P MCCB (25kA) and ON/OFF indicating lamps.
1 No. 40A, 3 phase Timer Switch for automatic operation.
B METERING & INDICATION
i) 1 set of R,Y,B phase indicating lamps.
ii) 1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB.
iii) 1 No. (0-40A) Ammeter with ASS with 3 nos. 160/5A CT's.
1 Set of 100A TPN Aluminium Bus Bar with colour coded PVC Sleeves.
12 nos 16 Amp 4P MCB, 10 KA.
NS-10.6 Main LT Panel describe as above Set 1 108751.00 108751
Sub-Head - XI 0 11663420
DSR - 2025-29 SUB HEAD-XII -DIESEL GENERATOR SET & UNINTERRUPTED POWER SUPPLY (UPS).
DIESEL GENERATOR SET.
Supplying, Installation, Testing & Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV + or better
norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415
V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for
29.1 test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should
contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code
etc. and consisting of the followings:
Diesel Engine:Tourbocharged Diesel engine 4 stroke water cooled,multi cylinder, dynamically balanced fly wheel,
electricstart of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter
MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be
(A) with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning)
lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor
shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to
BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.
(B) Engine mounted Instrument Panel fitted with and
having digital dis Plate for following i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(B) (v) Battery charging indication and Voltage indication
(vi) RPM indication
(vii) Over speed indication
(viii) Low lubricantion Oil trip indication
(ix) Engine Running Hours indication
Digitally signed by ANKIT
Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8lagging
power factor at 40 0C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof
(C) (SPDP) enclosure IP23 , brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading
for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR
conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.
Base Frame & Foundation:
Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary
(D) reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement
as per recommendations of
(E) Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet
complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of
Exhaustdia. Complete with valves, level indications & accessories as required as per specifications.
(F) Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor.
Starting System:
12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation
(G) complete with suitable numbers of batteries
(180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the
acoustic enclosure of DG Set.
Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator,
extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level
outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking.
(H) Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The
enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications.
Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as
below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser
to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH),
KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power
(I) (aluminium) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set
including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet
/RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM
make etc. as per approved by Engineering in charge and including the following:
Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3
1 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip.
2 Auto/Manual/Test/Off selector switch
Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2
3 Nos. under voltage relay).
4 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering
5 Energy analyser unit to indicate current, Voltage( L N & LL), kW, kVA (Phase & Total), Frequency, KWH,PF.
6 LED Indicating lamps for load on mains and load on set
Digitally signed by ANKIT
7 Fuse/ MCB for instruments
Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off
and boost and current adjustment.
9 Main supply failure monitor
10 Supply failure timer
11 Restoration timer
12 Control unit with three impulse automatic engine start/stop and failure to start lockout.
13 Impulse counter with locking and reset facility.
14 ON/OFF/Control circuit switch with indicator
15 Audio/Video annunciation for
(i) High water temperature
(ii) Low lubricating oil pressure
(iii) Engine over speed
(iv) Engine fails to start
(v) Full load/maximum
Protection loadFrequency,
for over/under warning Loss of AC sensing, Over Current, Unbalancing load with suitable number of
16 relays and accessories
17 Maintenance notification based on Engine Run Hour & due date.
Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of
essential panel , interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to
18 auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software
required to perform the operation shall be provided by the contractor including all control wiring.
UNINTERRUPTED POWER SUPPLY (UPS).
Online UPS- Input supply: Three Phase, Output supply: Three Phase.
Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) at operating
temperature 0 to 40 0C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot
swapable (allow for the replacement or addition of battery modules without shutting down the entire system)
modular Power Supply (UPS) system with N+1 modules (N denotes total number of modules required for rated
capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH
capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be
VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation
transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction.
The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable
operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM
(Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the
relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96%
while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total
harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor
(C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor
(PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS
shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming
supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload
capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance,
protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current,
short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage
Digitally signed by ANKIT
short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage
electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and
Frequency Independent (VFI)-type UPS. . Communication RS232/RS485/SNMP port open protocol for BMS
integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required
battery racks and interconnecting copper conductor cables of suitable size and connectors and all required
accessories are inclusive of the cost). This system must provide a means for logging and alarming of all monitored
points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS
should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in
compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more
LC Display / LED) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output:
Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f) Temperature: STS,
Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events
like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail /
Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time,
etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging
and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm,
UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under
Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain
drawing, test report OEM manual, Geo- Tag of manufacturing location etc . as required.
26.2.2 20KVA (Each Power module shall be < 10 KVA) Each 1 341772 341772
PIPES & ACCESSORIES.
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589
including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the
wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of
required shade complete as required :
INSULATION ON EXISTING PIPE .
Supplying, laying/ fixing of following thickness insulation with fire retardant quality expanded polystrene moulded
pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g
DSR-2025-30.6 polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1
roofing feltstrip(as per IS:1322 as amended up to date ) at joints repairing etc. as per specifications and as required
complete in all respect.
DSR (Civil)-2023- Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting,
10.2 hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Total of Sub-Head - XII 3796924 151178
Digitally signed by ANKIT
NBCC INDIA LIMITED
NAME OF THE WORK :- HOUSING AND URBAN DEVELOPMENT CORPORATION LIMITED, NEW DELHI.
ESTIMATE OF FIRE ALARM SYSTEM.
NS Rate (Rs) NS Amount DSR-2025 Amount
DSR- 2025 SUB HEAD-XIII:FIRE ALARM & DETECTION SYSTEM & PA SYSTEM. Unit Qty DSR-2025 (Rs.)
Supplying, installation, testing and commissioning of micro processor based
intelligent addressable main fire alarm panel, central processing unit with the
following loop modules and capable of supporting not less than 240 devices
(including detectors) and minimum 120 detectors per loop and loop length up to 2
km, network communication card, minimum 320 character graphics/ LCD display
with touch screen or other keypad and minimum 4000 events history log in the non
volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up
with 24 volt sealed maintenance free batteries with automatic charger. The panel
shall have facility to connect printer to printout log and facility to have seamless
integration with analog/digital voice evacuation system (which is part of the
schedule of work under SH: PA System) and shall be complete with all accessories .
The panel shall be compatible for IBMS.as required.
Supplying, installation, testing & commissioning of repeater panel wih 320
28.2.3 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence Nos 1 113,734.00
switches complete as required. 113,734.00
Supplying, installation, testing & commissioning of intelligent analog addressable
photothermal detector complete with mounting base complete as required. 192,256.00
Supplying, installation, testing & commissioning of intelligent addressable thermal
28.2.9 detector with rate of rise cum fixed tempreature thermistor complete with base as Nos 34 2,866.00
required. 97,444.00
Supplying, installation, testing & commissioning of response indicator on
28.2.5 surface/recessed MS Box having two LED, metallic cover complete with all Nos 59 306.00
connections etc as required. 18,054.00
Supplying, installation, testing & commissioning of addressable manual call point
complete as required. 52,819.00
Supplying, installation, testing & commissioning of addressable fire control module
complete as required. 41,028.00
Digitally signed by ANKIT
Supplying, installation, testing & commissioning of fault isolator complete with base
as required. 27,472.00
Supplying, installing, testing and commissioning approved make Addressable
Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor
module shall monitor potential free contacts. The device shall have an LED which
shall blink in normal state & get steady on activation to monitor the heath status of
the device. Addressing shall be with user friendly rotary decimal switches. Module
shall be supplied with mounting plate from OEM for ease of installation &
maintenance.as required.
Notification Devices
Supplying, installation, testing & commisssioning of intelligent addressable
programmable sounder complete as required.
Fire Fighter Telephone Talk Back -
Supplying, installation, testing & commissioning of fire fighter phone jack complete
as required. 21,957.00
Supplying, installation, testing & commissioning of fire fighter telephone handset
complete as required. 36,096.00
Cables & Conduits
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated
with annealed copper conductor having glass mica fire barrier tape covered by an
extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and
LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
IP Based Public Address System -
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller
with USB, MP3 player (including 6 zone button paging station) with seamless
integration facility with main fire alarm panel for voice evacuation complete as
required. 132,115.00
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt,
25V rms operating at 240 Volt AC Supply complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker
complete as required. 15,375.00
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall
speakers complete as required.
Cables & Conduits
Digitally signed by ANKIT
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with
28.5.2 annealed copper conductor having XLPE insulation, steel wire armouring & Mtrs. 365 192.00
FRLS/HFFR outer sheath complete as required. 70,080.00
Total of Sub-Head - XIII. 36750.00 2387911.00
Digitally signed by ANKIT
NBCC INDIA LIMITED
NAME OF THE WORK :- HOUSING AND URBAN DEVELOPMENT CORPORATION LIMITED, NEW DELHI.
DSR -2025/NS DSR-2025 Amount
Description of items Unit Qty DSR-2025 (Rs.) NS Rate (Rs) NS Amount (Rs)
SUB HEAD - XIV :- IP CCTV SYSTEM .
IP CCTV SYSTEM.
Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG
Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4
DSR-2025- pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-
39.17 568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with
Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at
–5°C ± 1°C and Pulling Force: 11.5Kg etc. complete as required.
Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded.
Must be of 1U height with clear label holders and white label with the panel. 24 Ports Cat-
39.11 6 Patch Panel should have ETL/UL verification program certificate for compliance with Each 2 5278 10,556.00
ANSI/TIA-568.2-D etc. complete as required
Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should
have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc.
complete as required.
39.13.1 Copper Patch Cords of length 1m (3ft) Each 40 173 6,920.00
39.13.2 Copper Patch Cords of length 3m (10ft) Each 40 405 16,200.00
Supplying, Installation, Testing and commissioning of CAT6 Copper Information Outlet
(IO) with face plate of color as per site requirement, should have ETL/UL verification
39.14 program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Each 40 212 8,480.00
Components should be from same OEM to maintain compatibility and interoperability
etc. complete as required.
Digitally signed by ANKIT
Supplying, installation, Testing and commissioning of following capacity 24 port Layer 2
indoor Network Switch having features and specifications etc. as mentioned here under:
At least 24 X RJ-45 Gigabit Ethernet Ports and additional 2 X 10G Base -T with 4 X SFP
Ports with non-blocking architecture by having Switching capacity of min. 168Gbps and
packet forwarding rate of 125Mpps or higher, 16K MAC table. Console Port, USB port,
Stacking support of min. 8 units per stack. Internal dual AC Power supply, STP, RSTP,
MSTP, BPDU Filter, BPDU Restriction, Min. 9K Jumbo Frame, LBD, IGMP Snooping
V1/V2/V3, MLD Snopping V1/V2. IGMP /MLD Groups 1K or more, IPv4/IPv6 Loopback
Interface, 16 L3 IP Interface, Ipv6 ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.1Ǫ, Port
DSR-2025-39.3 based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN, VLAN Trunking, DHCP Snopping, Server,
server screening. RADIUS , TACACS+ Authentication, ǪoS: 802.1P, 8 queues per port, ǪoS
: WRR, Strict+WRR, WRED, 802.1p. ACL: MAC based, IPv4C IPv6, TCP/UDP Port number,
time based ACL, TFTP Client, SNMP V1, v2c, v3, SNMP traps, RMON, DHCP server, relay,
client, LLDP, LLDP-MED, OAM, Dying Gasp, 802.3ah, sflow, RIP, OSPF v2/v3, policy based
route, SSL, SSH. 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45
access ports. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted
Telecom Portal of Department of Telecommunication, Government of India etc. complete
24 port PoE Layer 2 Network Switch with PoE Support of 370W or higher with each
copper port supporting 802.3at PoE+ min.
6MP IP IR Dome Camera.
Supplying Installation Testing and Commissioning of 5/6MP IP IR Dome Camera having
following specifications and features etc :-
1)Type of Camera: Dome Camera 2) Image Sensor: 1/2.8" or better progressive Scan
CMOS get color image even at night condition 3) Signal System: PAL/NTSC 4) Minimum
Illumination: 0.008Lux@ F1.4, AGC ON, 0 lux with IR or better 5) Imaging: 1/3s to
1/30000s Shutter Support, Auto Gain Control , White Balance- Auto, Back Light
Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 6) On Screen
Display: Camera should display Camera title, Date & Time in live & recorded video both.
7) Signal to Noise Ratio: > 50 dB 8) Day & Night: True Day & Night High Performance
Mechanical IR cut filter with auto switch, IR Source Inbuilt IR LED's with effective distance
upto 50 Mtrs integrated IR 30 Mtrs for colour view in night. 9) Video Compression
(Minimum): H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 10) Wide
Dynamic Range: WDR (120dB or more) 11) Digital Noise Reduction: DNR (2D/3D) On/Off
12) Streaming: Triple streaming, configurable 13) Video Streaming & Frame Rates: Triple
streaming , configurable Main stream: 5/6MP @25/30 fps, Sub streams: D1@25/30 fps or
better 14) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness
adjustable through client software or web browser 15) Profile Management: User
configuration import, export 16) Security: User Authentication, Water Marking 17)
Digitally signed by ANKIT
configuration import, export 16) Security: User Authentication, Water Marking 17)
Onboard Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto
512 GB. It should be supplied with minimum 128GB memory Card. 18) Recording
Management: Format SD, overwrite, storage management, video to NAS device, 19) Edge
Analytics : Tripwire, Intrusion, Motion Detection 20) Alarm Trigger : Motion/tampering
detection; network disconnection detection; IP conflict detection; memory card state
detection; memory space detection 21) Alarm Support: It should have 1/1 Alarm In/ Out
Port 22) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for
external Mic. and Speaker (As per site requirement) with G.711U/A/ G.711Mu/ AAC/
G.726 audio compression 23) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP,
HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast, 24)
System Capability: ONVIF 25) VMS: Camera shall support open source VMS 26) Cyber
Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted
execution, Digest, security logs, , account lockout, video encryption, IP/MAC filtering,
HTTPS, trusted upgrade. 27) Ethernet: 1 RJ 45 10/100 Ethernet port 28) Power Input: The
camera should support simultaneous dual power input—12 VDC (via power adapter) and
PoE—to ensure continuous operation in the event of a failure in one power source. 29)
Power Requirement: 12VDC/24VDC/PoE (802.3af)/ePoE 30) Enclosure: IP67 weather
proof, IK10 31) Operating Condition: Ambient Temperature:- (-) 05°C to 50°C, humidity
95% (max) (non-condensing) 32) IR life: 40000 hours or higher 33) Video Bit rate: 32 KBPS -
8 MBPS or better 34) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS as
6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens Dome
6MP IP IR Bullet Camera.
Supplying Installation Testing and Commissioning of 5MP/6 MP IP IR Bullet Camera
DSR-2025-40.6 having following specifications, type of lens and features etc :
1) Type of Camera: Bullet Camera 2) Image Sensor: 1/2.8" or better progressive Scan
CMOS get color image even at night condition 3) Signal System: PAL/NTSC 4) Minimum
Illumination: 0.006Lux@ F1.4, AGC ON, 0 lux with IR or better 5) Imaging: 1/3s to
1/30000s, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone
Privacy Masking, HLC, Digital Watermarking. 6) On Screen Display: Camera should display
Camera title, Date & Time in live & recorded video both. 7) Signal to Noise Ratio: > 50 dB
8) Lens Type & Focus: as given below. 9) Day & Night: True Day & Night High
Performance Mechanical IR cut filter with auto switch, IR Source Inbuilt IR LED's with
effective distance upto 50 Mtrs integrated IR and 30 Mtrs for colour view in night. 10)
Video Compression (Minimum): H.265 or better, Audio:- G.711U/A, G.711Mu, G.726,
AAC, G.723 11) Wide Dynamic Range: WDR (120dB or more) 12) Digital Noise Reduction:
DNR (2D/3D) On/Off 13) Streaming: Triple streaming, configurable 14) Video Streaming &
Frame Rates: Triple streaming , configurable Main stream: 5MP/6MP @25/30 fps, Sub
streams: D1@25/30 fps or better 15) Image Setting: Rotate Mode, saturation, brightness,
contrast, sharpness adjustable through client software or web browser 16) Profile
Management: User configuration import, export 17) Security: User Authentication, Digital
Digitally signed by ANKIT
Management: User configuration import, export 17) Security: User Authentication, Digital
Water Marking 18) Onboard Storage: Camera should support built-in Micro
SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB
memory Card. 19) Recording Management: Format SD, overwrite, storage management,
video to NAS device, 20) Edge Analytics: Tripwire, Intrusion, Motion Detection 21) Alarm
Trigger : Motion/tampering detection; network disconnection detection; IP conflict
detection; memory card state detection; memory space detection 22) Alarm Support: It
should have 1/1 Alarm In/ Out Port 23) Audio Support: It should have 1x Built-In Mic and
1/1 Audio In/ Out Port for external Mic. and Speaker (As per site requirement) with
G.711U/A / G.711Mu/ AAC/ G.726 audio compreesion 24) Network Protocol: SFTP, IPv6,
IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL,
DHCP, SMTP, RTSPS, unicast, 25) System Capability: ONVIF 26) VMS: Camera shall support
open source VMS 27) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration
encryption, trusted execution, Digest, security logs, account lockout, , video encryption,
IP/MAC filtering, HTTPS, trusted upgrade. 28) Ethernet: 1 RJ 45 10/100 Ethernet port 29)
Power Input: The camera should support simultaneous dual power input—12 VDC (via
power adapter) and PoE—to ensure continuous operation in the event of a failure in one
power source. 30) Power Requirement: 12VDC/24V DC/PoE (802.3af)/ePoE 31) Enclosure:
IP67 weather proof, IK10 32) Operating Condition: Ambient Temperature:- (- )05°C to
50°C, humidity 95% (max) (non-condensing) 33) IR life: 40000 hours or higher 34) Video
Bit rate: 32 KBPS - 8 MBPS or better 35) Standards: BIS with ER, STQC Certified, CE, FCC
and RoHS.as required.
6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens outdoor Bullet
Network Video Recorder (NVR) .
Supplying Installation Testing and Commissioning of following Channel Network Video
Recorder (NVR) with camera licenses to record for all channels having specifications and
features etc as mentioned below :
Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses to
record per NVR and to provide a live view, storage and simultaneously Multi-channel
1) playback of all IP camera or more and must be ONVIF with minimum support of 384
incoming Bandwidth.
NVR should support video compressions : H.265 or better, H.264, MJPEG.
Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with
3) G.711U/A, G.711u, PCM, G726 audio compressions.
Intelligent auto power on when power resumes after power outage.
Storage: It should support minimum 8 SATA Slots with 20TB capacity/ Slot and RAID
support of RAID 0/1/5/6/10.
Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS232,
7) Backup Interface : Its should have 4 Nosx USB port (2x USB3.0, 2xUSB2.0)
8) Video Output Ports: 2x HDMI and 2 VGA
Digitally signed by ANKIT
Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external
sensors and output devices like hooter/ Siren etc
Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated
10) mobile number for power failure, HDD failure, vandalism, tempring, network
disconnection and panic
Web & Mobile Application: Web, Mobile app ( For
iPhone, iPad, Android Phone) for alerts and viewing.
Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE,
12) FTP, DDNS, Alarm Server, IP Search, Multicast, Auto Registration, ONVIF (Profile T, Profile
S, Profile G), CGI, SDK and OEM Cloud for remote monitoring without any public IP need.
13) Standards: CE, FCC, RoHS, BIS Certified
14) Power Supply : Should support AC100-240V, 50/60Hz Power supply
15) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-condensing)
The VMS application shall support all the features & functionalities of the offered
VMS should consist Licenses for all channels to record Cameras with General, motion
detection, intelligent, alarm and POS recording modes. VMS should be provided with
Camera Licenses , with no dependency of VMS licenses by binding with the MAC address
of the cameras to achieve the functionality.
The NVR OEM shall be responsible for providing a mobile application compatible with
18) both Android and iOS devices, enabling remote monitoring and playback of cameras/NVR
The OEM must provide its own DDNS server hosted in India, eliminating the need for a
public IP address for remote monitoring over the Internet.
20) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode
It should support Resolution: 32MP; 24MP; 16MP; 12MP; 8MP; 5MP; 4MP; 1080p; 720p;
When alarm recording is enabled and an even occurs, you can click the alarm icon on
22) monitoring page to view the alert details. The snapshot function is supported on
monitoring and playback page
The Network Video Recorder (NVR) shall be configured to send email whenever a system
message is created or an alarm event occurs. The email server shall be a valid SMTP
server. Each recipient email address shall be configured to receive any combination of
critical, warning, or informational messages or alarm notifications. When an alarm
occurs, the email message includes the NVR name, time of alarm and a list of camera that
is configured to record upon alarm
24) It should have Web and GUI interface.
Built-In Artificial Intelligence: NVR should have built-in AI :-- 2 Channel face detection
25) and recognition, - Minimum 4 Channel perimeter protection, - Minimum 8 Channel Smart
Motion Detection
Face Recognition Database Capacity: It should support total Blacklist and Whitelist
capacity of Minimum 20,000 Faces or more with Face Detection speed of 12 face
images/sec and facility to add Name, gender, birthday, address, credential type,
credential No., countries & regions and state to each face image
Digitally signed by ANKIT
Face & Human Attributes Search: Search Pictures/ Video by Gender, age group, glasses,
expressions, face mask, beard, Top color, top type, hat, bag, age, gender and umbrella
ANPR Capability: It should support ANPR Camera with License plate, plate color, vehicle
28) body, vehicle model, vehicle logo, calling, seatbelt, vehicle registration location etc
vehicle attributes.
Alarm Notifications based on: Motion detection, video tampering, video loss, scene
changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter
29) protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd
distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan,
cybersecurity exception
Alarm Notification should be linked with Recording, snapshots, Camera external alarm
output, buzzer, logs, presets and email.
General AI Based Search: Search Pictures by channel, time, event type, target
31) classification (Fall Detection, People Approach Detection, People No. Exception
Detection, People Staying Detection, Violence Detection.
Smart playback function: Should support smart search for the selected area in the video
and smart playback to improve the playback efficiency
VCA (Video Content Analytic): Should support multiple video contented analytics based
on camera analytics
34) Analytics by NVR: Perimeter protection and face recognation
64 Channel Network Video Recorder (NVR) having display split :- Main screen:
Hard Disk Drive .
Supplying, Installation, Testing and Commissioning following capacity Serveillance grade
Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5
inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM,
UKCA, VCCI, CB-Scheme, TUV, UL Certifications
DSR-2025-42.4 LED Display
Supplying, Installation, Testing and Commissioning of following size LED display (LED
monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth
and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or
better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing
angle (H/V): 170°/ 170°, response time less than 12ms, Display control shall be on
monitor screen and programmable with remote (remote shall be supplied with system),
Key Board, Optical Mouse, etc. as required.
42.4.3 55 inch or larger Each 2 82057 164,114.00
Digitally signed by ANKIT
Supplying and fixing of following size Wall Mount Rack having Fixed Structure with
0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical
Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and
bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting
kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power
distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet
of 20 x 1 number, etc. complete as required.
DSR-2025-42.2 PC System.
Supplying Installation Testing Commissioning of Client PC System comprising of PC
Hardware with minimum11th Gen Intel® I7 processor CPU E5-2640 x64 (or better),
compatible with dual and quad core processors minimum 3.1 Ghz and 8GB or higher
RAM, Hard Drive Space of 256 GB SSD or better, Video card and monitor capable of Each 1 90698 90,698.00
1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps
with RJ-45 connector) with 2 GB or higher Graphics card suitable for BMS System
complete etc. as required. .
Sub-Head - XIV 1,749,565.00 -
Digitally signed by ANKIT
NBCC INDIA LIMITED
NAME OF THE WORK :- HOUSING AND URBAN DEVELOPMENT CORPORATION LIMITED, NEW DELHI.
ABSTRACT OF COST
DESCRIPTION COST AS PER DSR AS PER MARKET TOTAL AMOUNT
DESCRIPTION COST AS PER DSR AS PER MARKET TOTAL AMOUNT
2025 (RS.) RATE (RS.) (Rs.)
3.0 SUB HEAD - III:-COPPER REFRIGERANT PIPING . 3,368,470.00 - 3,368,470.00
SUB HEAD - IV:- COMMUNICTION CABLE & DRAIN PIPE. - 2,010,700.00 2,010,700.00
5.0 SUB HEAD - V:- INLINE FAN & AXIL FLOW FAN. - 1,338,512.00 1,338,512.00
SUB HEAD - VI:-DUCTING, GRILLS,DIFFUSER AND 6,586,380.00 51,510.00 6,637,890.00
SUB HEAD-VII - ELECTRICAL WORK & CABLE TRAYS , 458,740.00 841,315.00 1,300,055.00
RACEWAY , JUNCTION BOX.
Digitally signed by ANKIT
NBCC INDIA LIMITED
NAME OF THE WORK :- HOUSING AND URBAN DEVELOPMENT CORPORATION LIMITED, NEW DELHI.
ESTIMATE OF HVAC WORKS
Qty NS Rate (Rs) DSR-2025
2025/NS Description of items Unit DSR-2025 (Rs.) NS Amount (Rs)
SUB HEAD -XV:-HVAC SYSREM ( VRV SYSTEM).
DSR-2025- SUB HEAD -I:-OUTDOOR UNIT .
Supplying, Installation, Testing & Commissioning of Modular type Variable Refrigerant
Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating
having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), minimum
two compressors (with individual separate PCB) for above 14HP modules, microprocessor
based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or
equivalent, vibration Isolators with suitable foundation etc. complete as required. To have
better efficiency condenser fan shall be capable to operate at different speed with
respect to load. The unit shall deliver the rated capacity and in confirmation as per IS
18728:2024 and CPWD Specifications and work even at 50°C ambient temperature
without tripping. The system shall be able to deliver 100% of the rated capacity upto 39
0C. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply
and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready
for use as required. The condenser should be coated with a hydrophilic film to prevent
water accumulation on the surface of the heat exchanger, enhance water dispersion, and
reduce the risk of degradation, thereby improving overall performance and durability. The
Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy
Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per
CPWD specification, connections, inter connections etc. as required. (For capacity <40
kWr ISEER 5.4, Capacity > 40 and <70 ISEER 5.5, Capacity > 70 ISEER 5.6 for ECSBC
For Cooling or Heating or Both.
TOTAL OF SUB HEAD -I 10511050.0
DSR-2025 - SUB HEAD - II:-INDOOR UNIT .
Supplying, Installation, Testing and Commissioning of following minimum capacity 4 way
Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-
filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil
section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill,
necessary supports, vibration Isolation, Corded remote control etc., suitable for operation
on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The Indoor units
must shut down upon receiving a singal from the BMS System/Fire Singnals. The system
shall be capable to adjust air flow as per room requirement in auto mode. The cooling
capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB
temperature. (Make will be same as of Outdoor)
Digitally signed by ANKIT
TOTAL OF SUB HEAD -II 5640330.0
DSR-31.14 SUB HEAD - III:-COPPER REFRIGERANT PIPING .
Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen
testing of following nominal sizes of soft/hard drawn copper refrigerant piping for
VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger
supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular
insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of
19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required.
31.14.1 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm. Meter. 290.0 256.0 74240.0
31.14.2 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm. Meter. 760.0 346.0 262960.0
31.14.3 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm. Meter. 390.0 487.0 189930.0
31.14.4 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm . Meter. 640.0 615.0 393600.0
31.14.5 19.1 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm. Meter. 680.0 739.0 502520.0
31.14.6 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm. Meter. 330.0 904.0 298320.0
31.14.7 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm Meter. 225.0 1068.0 240300.0
31.14.10 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm Meter. 490.0 1286.0 630140.0
31.14.12 41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm Meter. 130.0 1368.0 177840.0
Supplying, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of
31.13 same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs .as required.
TOTAL OF SUB HEAD -III 3368470.0
NS-1 SUB HEAD - IV:- COMMUNICTION CABLE & DRAIN PIPE.
COMMUNICTION CABLE.
Supplying following 1.1kV grade,Communition Cables armoured cables suitable for 415V,
50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS
insulation, galvanised steel armouring (round or flat as mentioned) and with all
NS-1.1 components
4 core, 2.5 sq.asmm.
mentioned in BOQ, specifications and schedule, complete etc. as required.( Meter. 2200.0 664.0 0.0 1460800.0
Supply, installation, testing and commissioning of UPVC condensate drain water piping of
density 20Kg/m³ completewith fittings likeelbows, tees, reducers, bends, flanges, supports
& dulyinsulated with "O" class Closed Cell Elastomeric Nitrile Rubber of specified pipe
NS-1.2 section
mm dia specified
withthickness etc. as required and of following sizes.
6 mm Insulation. Meter. 450.0 360.0 162000.0
NS-1.3 32 mm dia pipe, with 6 mm Insulation. Meter. 770.0 457.0 351890.0
NS-1.4 40 mm dia pipe, with 6 mm Insulation. Meter. 65.0 554.0 36010.0
Total of Sub-Head - IV. - 2,010,700.00
NS-2 SUB HEAD - V:- INLINE FAN & AXIL FLOW FAN.
Accoustically Insulated Box Type Inline Fans
Digitally signed by ANKIT
Supplying, installing, testing and commissioning of INLINE FANS suitable for installing in any
position in vertical or horizontal ducts. The casing shall be double skin, internally
acoustically lined and constructed of galvanised steel. with efficient motor, fire retardent
double layer canvass connection etc complete in all respect & of following capacities. The
NS-2.1 300 CFM (15mm static pressure, single phase) Nos. 5.0 15227.0 76135.0
NS-2.2 400 CFM (15mm static pressure, single phase) Nos. 5.0 18688.0 93440.0
NS-2.3 600 CFM (15mm static pressure, single phase) Nos. 1.0 23533.0 23533.0
NS-3 Axial Flow Fan
Supply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans
with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm
thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy
impeller complete with TEFC Sq. Cage Induction motor IE-3 suitable for 415 volts ±
10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators,
fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird
screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along
with motor shall be high efficient one with fire rated (class H) suitable for withstanding 250
°C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16
m/sec. Fan & Fan motor KW given below are for guideline & actual Dia / KW shall be as per
manufacturer selection based on maximum 16 m/sec outlet velocity.
Axial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA
210 and AMCA 300. Complete Fan shall be tested and approved by CE / UL / EN in
accordance with "Power Ventilators for Smoke Control Systems" for 250 °C for 2 hours.
Manufacturer shall furnish AMCA Test Certificate for air & sound performance along with
UL / EN fire test certificate (Latest) for each fan sourced from that particular factory. The
noise level of axial fan shall be less than 80 dBa at a distance of 3.0 mt from the fan. The
fan shall be low RPM (less than or equal to 1000 RPM) and capacities shall be as follows.
Wattage of motor shall be as per actual selection meeting other technical parameters
6000 CFM (18mm static pressure, Axial Fan, 960 / 1450 RPM, 2.2 Kw Fan Motor or as 165892.0
required, 700 MM Fan Dia) Nos. 2.0 82946.0
10000 CFM (18mm static pressure, Axial Fan, 500 / 960 RPM, 1.5 Kw Fan Motor or as 263012.0
required, 700 MM Fan Dia)
12000 CFM (18mm static pressure, Axial Fan, 500 / 960 RPM, 1.5 Kw Fan Motor or as 282946.0
required, 700 MM Fan Dia)
NS-4 Supply, installation, testing and commissioning of JET FAN as required. Nos. 6.0 72259.0 433554.0
Total of Sub-Head - V. 0.0 1338512.0
DSR-2025- DUCTING, GRILLS,DIFFUSER AND INSULATION .
SUB HEAD - VI:-DUCTING, GRILLS,DIFFUSER AND INSULATION.
Supplying, installation, balancing and commissioning of fabricated at site GSS sheet
metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows,
DSR-30.12.2 splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars
etc as required complete in all respect in confirmation with IS : 655 and approved
drawings and specifications of following sheet thickness complete as required.
Digitally signed by ANKIT
Supplying, installation, testing and commissioning of GI volume control duct damper
DSR-30.13 complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc in sq. m. 140.0 7580.0 1061200.0
confirmation to SMACNA/IS and as per specifications complete etc. as required.
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted
GI volume control damper with enthalpy sensor and necessary control wire for
DSR-30.14 integration within AHU room complete with neoprene rubber gaskets, nuts, bolts, screws
linkages, flanges etc in confirmation to SMACNA/IS and as per specifications complete etc.
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch
DSR-2025- and return air path as and where required of required sizes i/c control wiring,the damper
30.20 shall be motorized and spring return so as to close the damper in the event of power
failure automatically and open the same in case of power being restored. The spring return
Supplying, Fixing, installation, testing and commissioning of powder coated extruded
DSR-30.15 aluminium Supply Air Grills with aluminium volume control dampers in confirmation to sq. m. 50.0 9623.0 481150.0
SMACNA/IS and as per specifications complete etc. as required.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but
DSR-30.16 without volume control dampers complete in confirmation to SMACNA/IS and as per sq. m. 40.0 6285.0 251400.0
specifications complete etc. as required.
Supplying, Fixing, installation, testing and commissioning of supply air diffusers of powder
coated aluminium with aluminium volume control dampers with anti smudge ring &
DSR-30.17 removable core in confirmation to SMACNA/IS and as per specifications complete etc. as sq. m. 50.0 12841.0 642050.0
Supplying, Fixing, installation, testing and commissioning of Return air diffusers of
powder coated aluminium without volume control dampers with anti smudge ring &
removable core in confirmation to SMACNA/IS and as per specifications complete etc. as
Supplying, Fixing, installation, testing and commissioning of thermal insulated flexible
DSR-2025-30.19duct of following sizes duly supported at regular interval as per site requirement etc. in
confirmation to SMACNA/IS and as per specifications complete etc. as required.
Supply, fixing and commissioning of Fresh/ exhaust air louvers with section comprising of 24930.0
NS-5 powder coated Aluminium louvers & bird screen as required or its equivalent sq. m. 30.0 831.0
specifications.
Supply, fixing and commissioning of powder coated extruded aluminium Door Transfer Grill 26580.0
NS-6 complete with nuts, bolts, SS screws etc. complete as required or its equivalent sq. m. 30.0 886.0
specifications.
Digitally signed by ANKIT
Total of Sub-Head - VI. 6586380.0 51510.0
SUB HEAD-VII - ELECTRICAL WORK & CABLE TRAYS , RACEWAY , JUNCTION BOX.
DSR 4.1 Supplying and installing following size of perforated pre-painted M.S. cable trays with
perforation not more than 17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with M.S. suspenders including bolts & nuts, painting
suspenders etc as required.
4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness Metre. 180.0 686.0 123480.0
4.1.3 200 mm width X 50 mm depth X 1.6 mm thickness Metre. 80.0 775.0 62000.0
4.1.4 300 mm width X 50 mm depth X 1.6 mm thickness Metre. 20.0 866.0 17320.0
Hot Dipped Galvanized Iron Cable Tray
DSR 4.6 Supplying and installing following size of perforated Hot DippedGalvanised Iron cable tray
(galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling with G.I.
suspenders including G.I. bolts & nuts, etc. as required.
4.6.2 150 mm width X 50 mm depth X 1.6 mm thickness Metre. 180.0 803.0 144540.0
4.6.4 200 mm width X 50 mm depth X 1.6 mm thickness Metre. 80.0 1062.0 84960.0
4.6.5 300 mm width X 50 mm depth X 1.6 mm thickness Metre. 20.0 1322.0 26440.0
NS-7 Supports, bends, access boxes, tap off boxes and cross over as per site requirement.
(overhead / wall mounted recovery & junction boxes shall be 2.0 mm thick). The
pregalvenised sheet shall be as per IS 277 or BS 2989 having tensile strength of minimum
500 N/sq.m. and minimum zinc coating of 275 GSM & coupler plate.
Supplying, installation, testing & commissioning of Race way made from minimum 2.0 mm
thick GI raceway, factory fabricated, with internal partition of the following sizes including
providing removable double folded cover of 2.0 mm thick , knock out holes and fixing
accessories & coupling, earthing stud for terminating 8 SWG copper earth wire complete
NS- 7.1 100 mm wide x38 mm deep in ceiling/floor Metre. 200.0 616.0 123200.0
NS- 7.2 225 mm wide x38 mm deep in ceiling/floor Metre. 50.0 1100.0 55000.0
NS- 7.3 300 mm wide x38 mm deep in ceiling/floor Metre. 50.0 1391.0 69550.0
NS-8 Supplying, installation, testing & commissioning of floor/ceiling recessed 2 mm thick
pregavanised sheet outlet junction box including providing cover with provision to adjust
overall height, knock outs on four sides to accept raceways of specified sizes and cutouts to
fix required outlets for following size of race ways with painted GI plate ( Colour as
approved Architect/Consultant).
NS-9 ISOLATOR SWITCHES WITH METAL ENCLOSURE.
NS-9.1 Supplying, installation, testing & commissioning of 63ARCCB (300mA),4pole switch for Each 53650.0
VRVOutdoor unitswith sheet metal enclosure, rain protectionetc. as required tosuit
thesitecondition. (Enclosureshall besuitable for out door installation.).Complete as
required as per site conditions.
Digitally signed by ANKIT
Supply, Installation, Testing & commissioning of Main LT Panel. The panel will be totally
enclosed type with, free standing, floor mounted, indoor duty, dust & vermin proof, , front
operated, electrical panel fabricated from 2 mm thick CRCA Sheet as per specifications &
NS-10 drawing laid in this document and will be complete with the main and auxiliary bus bars,
interconnection wiring, earth bus and will be powder coated finish with 70 micronor more
thickness. All the busbar joint shall be protected by clip on type sleeve. The Main LT Panel
shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire
M V PANEL FORHVAC PANEL.
A INCOMER FROM EXISTING MAIN LT PANEL
1 Nos. of 320 A, 4P MOTORISED type MCCB with Ics=Ics=50KA having Mircroprocessor
1 Nos. SPD Type 1
1 Sets - digital multifunction meter (showing harmonics along with all other electrical
1 Sets - 0-500V, digital Voltmeter with selector switch, 3 No. phase indicating LED lamp to
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-400A) Ammeter with ASS with 3 nos. 300/5A CT's
1 Set of 480 A TPN Aluminium Bus Bar with colour coded PVC Sleeves
i) 8 No. 63A 4P MCCB (25 KA)
ii) 4 No. 63A 4P MCCB (25 KA) (SPARE)
NS-10.1 Main LT Panel describe as above Set 1.0 526025.0 526025.0
Total of Sub-Head - VII. 458740.0 841315.0
Digitally signed by ANKIT
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT HUDCO Panchkula.pdf
Tender Document
BOQ-Panchkula.pdf
Tender Document
Drawings- Hudco Office Punchkula.pdf
Tender Document
Technical Specs-HuDCO Panhkula.pdf
Tender Document
NBCC GCC Contracting for Construction Works- 2026.pdf
Tender Document
Technical Circulars upd upto 33.pdf
Tender Document
Make List.pdf
Tender Document
SCC.pdf
Tender Document
Integrity Pact.pdf
Tender Document
Download all tender documents and submit your bid