| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 LAccepted-Finance | L1 | Accepted-Finance Lowest | |
| 2 | L2₹9.5 L+₹23,108 (2.49%)Rejected-Finance | L2 | Rejected-Finance 2nd Lowest | |
| 3 | L3₹11.0 L+₹1.7 L (18.2%)Rejected-Finance | L3 | Rejected-Finance 3rd Lowest | |
| 4 | L4₹12.0 L+₹2.7 L (28.7%)Rejected-Finance BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | L4 | Rejected-Finance 4th Lowest | |
| 5 | L5₹17.6 L+₹8.3 L (89.5%)Rejected-Finance | L5 | Rejected-Finance 5th Lowest |
Tender Value
Refer Docs
EMD Value
₹23,322
Closing Date
30 Nov 2019, 5:00 pmClosed
office of the EE KED Writers Buildings
New Building Erstwhile CGA Office 1st. Floor Writers Buildings Kolkata 700 001
Reorientation of existing VRF Air Conditioning System of Lalbazar Police Headquarter Control Room Kolkata.
2019_WBPWD_252970_1
WBPWD/EE-KED/e-NIQ-28/2019-20
Open Tender
A/C ORG
Item Rate
15 days
Lalbazar Police Headquarter
Please refer Tender documents.
6 documents required · 6 mandatory
₹23,322
Yes
5 Feb 2020
14 Nov 2019
3 Dec 2019
14 Nov 2019
30 Nov 2019
16 Nov 2019
Amount
VARIABLE REFRIGERANT FLOW SYSTEM : (Approved Brands –TOSHIBA, MITSUBISHI Heavy, HITACHI)
Supply of Variable Refrigerant Flow modular type air-conditioning system with DIP-IPM Inverter Controlled with step-less modulation complete with indoor & outdoor units, individual remote controller and centralized controller, interconnected refrigerant piping , full charge of R-410 refrigerant gas & oil, control cabling etc.
Supply of Outdoor Unit Supply of Top Discharge Heat Pump Type Outdoor units equipped with highly efficient inverter scroll compressors 85 Steps 15Hz ~ 100Hz. Each Module should have multiple full inverter compressor with special heat exchanger, Steps speed control DC motor condenser fan , auto check function for connection error, auto address setting and in built Double Stage Oil Separation to ensure minimum oil entrachment and proper lubrication. The condensing units should be capable for outside ambient 52˚C.
12 HP Heat Pump Type
Supply of Indoor Unit: Supply of Indoor units address setting and capacity as mentioned below. Multi speed motor, coil section with DX coil. The Indoor Unit Should be fire retardent , i.e the electronic PCB of the Indoor unit should be enclosed in sheet metal box , by which fire will not spread in case of fire . (Approved Brands –TOSHIBA, MITSUBISHI Heavy, HITACHI )
Ceiling Mounted Units : In the Ceiling HAT /Hi-wall/Cassete type : 3.0 /2.5 HP & With Maximum Air Quantity of 1000 CFM - Maximum Sound Pressure level - dB - 40 dB
Multikit (Approved Brands – TOSHIBA , MITSUBISHI Heavy , HITACHI ) Supply of Y-shape Multikit Joints sizes as mentioned below. Multikit is consist of 2 nos copper joints and 2 nos separate insulation suitable for these Joints
REMOTE CONTROLLER : (Approved Brands – TOSHIBA, MITSUBISHI, HITACHI)
Corded Remote (Ceiling Mounted )
Installation of VRF air-conditioning system of following items
Lifting, Shifting, Installation, testing & Commissioning of Top Discharge type Outdoor units as follows : 12 HP Heat Pump Type
Indoor Units : Lifting, Shifting, filter section & Installation, testing and commissioning of Indoor units address setting and capacity as mentioned below. Multi speed motor, coil section with DX coil.
Ceiling Mounted Unit- 3.0 HP/2.5 HP
Remote Controller
Corded Remote (Ceiling Mounted unit)
Commissioning of VRF systems including Nitrogen Flushing etc.
Installation, Testing & Commissioning of Multikit Joints
Providing and fixing rigid PVC piping complete with fittings, supports as STD. & specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation.
25 mm dia
Supply & fixing of control cum distribution wiring of Copper conductor cable of size 2 C X 0.75 Sq. mm along with conduit for looping between indoor & outdoor VRF system & to main Central remote controller system
R410 Gas Charging Top Up
Supply, fabrication and installation of MS Frame duly painted for outdoor unit and IDU units including vibration isolation pad etc.
Refrigerant Piping : Supply, installation, testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13 mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units & specifications, all piping inside the room shall be properly supported with MS hanger.
25.4 mm O.D..(with 19 mm insulation)
22.2 mm O.D..(with 19 mm insulation)
19.1 mm O.D. (with19 mm insulation)
15.9 mm O.D.(with 13mm insulation)
12.7 mm O.D.(with 13mm insulation)
9.5 mm O.D.(with 13mm insulation)
6.4 mm O.D. (with 13mm insulation)
S. R. AIRCON
ELECTRIC REFRIGERATION
NATIONAL AIRCON
HIMAYAN
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .