Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.0 CrAccepted-AOC | ₹4.0 Cr | L1 | Accepted-AOC AWARDED TO L1 |
| 2 | L2₹6.5 Cr+₹2.5 Cr (61.4%)Rejected-AOC 216 BHARAT NAGAR INDRAPURI BHOPAL MADHYA PRADESH 462021 | BHOPAL | MADHYA PRADESH | 462021 | ₹6.5 Cr+₹2.5 Cr (61.4%) | L2 | Rejected-AOC L2 |
| 3 | L3₹7.9 Cr+₹3.9 Cr (96.7%)Rejected-AOC | ₹7.9 Cr+₹3.9 Cr (96.7%) | L3 | Rejected-AOC L3 |
| 4 | Rejected-Technical PUNE | PUNE | MAHARASHTRA | 410301 | - | - | Rejected-Technical AS PER TENDER DOCUMENT |
| 5 | Rejected-Technical | - | - | Rejected-Technical AS PER TENDER DOCUMENT |
Tender Value
Refer Docs
EMD Value
₹11 L
Closing Date
22 Nov 2019, 11:00 amClosed
R K AVASTHI
DGM ELECTRICAL JAWAHAR VYAPAR BHAWAN, NEW DELHI - 110001
Works of Supply, Installation, Testing, Commissioning of fire sprinkler, Fire detection and Alarm system etc. after dismantling the existing system at Jawahar Vyapar Bhawan,1 Tolstoy Marg, Connaught Place, Delhi.
2019_STC_514166_1
STC/CO/BLD-E/01124/2019
Open Tender
Electrical Works
Works
365 days
NEW DELHI
AS PER TENDER DOCUMENT
12 documents required · 12 mandatory
₹5,000
Yes
THE STATE TRADING CORPORATION OF INDIA LTD.
₹11 L
Yes
24 Feb 2020
31 Oct 2019
22 Nov 2019
31 Oct 2019
22 Nov 2019
31 Oct 2019
31 Oct 2019 - 21 Nov 2019
Amount
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :
Pendent Sprinkler
Upright Sprinkler
Horizontal side wall sprinkler
Concealed sprinkler
Supply, Fixing, testing & commissioning of Extended Throw Side Wall Nozzles/Sprinklers
Providing, installation, testing & commissioning of water curtain nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required:
100mm dia
150mm dia
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of following sizes as required -
150mm dia
100mm dia
80mm dia
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :
25 mm dia.
Providing and fixing C.I. sluice valves (with cap) complete with bolts, nuts, rubber insertions etc. (the tail Piece if Required shall be paid separately)- (For Risers and Terrace) - 150 mm diameter Class II
200 mm diameter Class II
250 mm diameter Class II
300 mm diameter Class II
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
4 way - 150 mm dia M.S. Pipe
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
Supplying, installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required.
150 mm dia
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required.
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.
Structural steel work in single section, fixed with or without connecting plate,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. (For Various Sections and Supports made out of Structural Steel as per Site Requirements)
Supplying, installing, testing and commissioning of Fire authority approved Electrical driven fire pump suitable for automatic/ manual operation consisting of the following: Horizontal/vertical multistage centrifugal fire pump capable of delivering 2850 LPM against a maximum head of 140 M while running at 1450 RPM complete with proper connection to suction and delivery line, and including bypass arrangement for testing of pumps. mechanical seal shall be included for stuffing box. Pump shall have a name plate indicating suction, delivery, head, discharge, stages, RPM and direction of rotation. Pump shall be capable of furnishing not less than 150% of rated capacity at a head not less than 65 % of rated head. The shut off head shall not exceed 120% of rated head. Squirrel cage, induction motor, TEFC type suitable for 415 + 6%V, 3 phase, 50 Hz, AC supply, of suitable HP rating for the above pump with asynchronous speed of 1450 RPM conforming to IP 55 protection & class 'F' insulation. The motor shall conform to IS 325 1978(up to date) with flexible coupling and coupling guard. Common base plate for mounting pump and motor fabricated of mild steel channel as per manufacturer's recommendation with heavy duty Anti Vibration pads as per requirement. Suitable reinforced cement concrete pump foundation as per manufacturer's design including foundation bolts, washers as required. Flexible Coupling and coupling guard for direct coupling of pump and motor. Technical Parameter For Sprinkler Pump Discharge : 2850 LPM Pumping Head Outlet - 140 m (Head) Motor kw - as per manufacturer recommendation Material of construction Casing - CI Impeller - Bronze (Br) RPM - 1450-1500 RPM Rate should included interconnection cables, foundation and foundation bolts.
Diesel Engine Driven Fire Pump ( Location - Plant Room) : Supplying, installing, testing & commissioning of fire authority approved Diesel Engine driven fire pump suitable for automatic/manual operations consisting of the following : Horizontal split casing multistage centrifugal fire pump capable of delivering 2850 LPM against a maximum head of 140 M while running at 1500 RPM complete with proper connection to suction and delivery line, and including bypass arrangement for testing of pumps. mechanical seal shall be included for stuffing box. Pump shall have a name plate indicating suction, delivery, head, discharge, stages, RPM and direction of rotation. Pump shall be capable of furnishing not less than 150% of rated capacity at a head not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head. Heat exchanger water cooled diesel engine of required BHP as per manufacturer at 1500 RPM for the above pump complete with standard accessories & suitable cooling system as described in specifications. Common base plate for mounting pump & engine of required strength manufactured out of M.S. channels as per manufacture's recommendation with heavy duty Anti Vibration pads as per requirement. Flexible Coupling & coupling guard for direct coupling of engine & pump. Suitable reinforced cement concrete pump foundations as per manufacturer design including foundation bolts, washer as required. 1 No. 3 hours capacity day oil storage tank welded steel construction conforming to IS : 2522 fabricated from 3 mm thick M.S. plates. Tank shall be provided with inlet, outlet, overflow, air vent, drain connections, filling connection & magnetic level indicator showing the level of fuel in the tank. Tank shall be mounted on a suitable steel structure (Painted with 2 coats of red oxide paint). Tank shall be provided with epoxy coat from inside & two or more coats of synthetic enamel paint outside over two coats of red oxide primer. Diesel storage tank shall be double skin. 24 volts 180 AH lead acid battery (12 volts - 2 Nos) with boost/Trickle charger for starting the engine automatically complete as required. Technical Parameter For Diesel Engine driven pump: Discharge : 2850 LPM Pumping Head/Pressure: Outlet - 140 m/14 kg/cm2 Material of construction Casing - CI Impeller - Bronze Rate should include inter connecting cables, foundation & foundation bolts.
"Electrical Motor Driven Jockey Pump Location - Plant Room :" Supplying, installing, testing & commissioning of fire authority approved electrically driven Jockey pump suitable for automatic/manual operation consisting of the following: Horizontal/vertical mounted jockey pump having cast iron/SS body, Bronze/S.S. impeller, stainless shaft with mechanical seal capable of delivering 180 LPM against total head as mentioned below while running at 2900 RPM complete. The system shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side including bypass arrangement for testing of working of the pumping set as required. The pump should meet the recommended requirement and must be approved by the local fire authority. Squirrel cage induction motor suitable for 415 + 6%V, 3 phase, 50 Hz, AC supply of suitable HP rating for the above pump with asynchronous speed of 2900 RPM T.E.F.C type connected to pump with flexible coupling and coupling guard . Common base plate for mounting pump and motor fabricated of mild steel channel as per manufacturer's recommendation with heavy duty as per requirement. Suitable reinforced cement concrete pump foundations as per manufacturer's design including foundation bolts, washers as required. Drain pipe with valve (25 mm dia) Rate shall include inter connecting cables, foundation & foundation bolts. Technical Parameter For Jockey Pump : Jockey Pump :- Flow rate : 180 LPM (10.8 m3/hr) Pumping head/Pressure : 140 m/14 kg/cm2 Motor KW : 5.5 KW (Approx.) or As per manufacturer recommendation
Providing, fixing, testing and commissioning of precharged air vessel (size 450 mm dia & 2000mm height) fabricated from 8 mm thick shell & dished end 10 mm thick M.S. Plate for pressurization of hydrant/ sprinkler system complete with adequate pressure switches (as per design / requirement) with valve to operate as per operating sequences including 25 mm dia drain valve, air release valve with ball cock on top, 25 mm dia inlet with isolating valve duly painted from inside and out side complete as required.
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
25 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
200 mm dia
250 mm dia
300 mm dia
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :.
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
PRESSURE GAUGE :
Providing & fixing dial type (100 dia as per pipe size) pressure gauge with isolation ball valve suitable for operating pressure of 10 Kg/cm2 cost shall be of inclusive of Providing any short pieces, nipples, elbows etc as required. having calibration of 0-15 Kg/cm2.
Providing, fixing, testing & commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45°C temperature, working pressure 10 Kg/cm2 and test pressure 15 Kg/cm2 (for Suction and delivery of Fire Fighting Pump).
200 mm dia
100 mm dia
250 mm dia
150 mm dia
80 mm dia
Providing, fixing, testing & commissioning of water flow meter complete with bypass arrangement and all accessories for flow indication, monitoring & testing of fire pumps.
100 mm dia (For working pressure 10.00 Kg/cm2)
Providing, fixing, testing & commissioning of M.S. class 'C' diesel pump exhaust pipe including all fittings like bends, tee, clamps/structural steel support of suitable dia for the engine. The pipe shall be provided with 12 mm thick Supercera Ceramic Fibre rope.
100 mm dia
150 mm dia
Supplying & laying of following 1100 volt grade PVC insulated sheathed XLPE aluminium conductor armoured cables as per specification in cable trays, ducts, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.(For Main Hydrant/Sprinkler Pumps)
3.5 Core 400 Sqmm Alumnium conductor cable
3 core 185 sqmm Alumnium conductor cable
3 core 25 sqmm Alumnium conductor cable
Cable end termination of the following PVC insulated sheathed PVC/XLPE aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium/Cu lugs, double compression glands with earthing facility at both ends of cables etc. complete as required for following dia cables
3.5 Core 400 Sqmm Alumnium conductor cable
3 core 185 sqmm Alumnium conductor cable
3 core 25 sqmm Alumnium conductor cable
Supply and fixing of perforated type GI cable trays of the following sizes as per specifications
150 mm x 40 x 40 x 2 mm thick
300 mm x 40 x 40 x 2 mm thick
SITC of Fire Dorrs With all Accessories & Panic Bars "Supply Installation Testing & Comm of 2 Hrs. ( 120 minutes) Fire Rated G.I- Steel Door with Powder Coating As Per IS-3614 & BS-476 Part 20 & 22. 2 Hrs GI -Steel Fire Rated Door Single/Double shutter door of Pure Polyester (UV Resistant Grade) 120 Micron Grade Powder coated, 120 minutes Fire Rated (for Stability & Integrity) ,Galvanized (Zinc Coated) Steel Door and frame confirming to IS & BS Norms. The Door shall be Provided with all Accesories like Ball Bearing , Vision Galss , Panic Bar / Key , Door Closer , Tower Bolt , The Door Shutter 46 mm shall be made of 20 Gauge thick GI-steel pressed formed to provide fully flush double skin door shell with lock seam joints at style edges or as per manufactures specifications.The internal construction of the door shutter's to be ADHESIVE with Core Bonded Honey -Com Craft with PU Cyanoacrylate and Acrylic Thermosetting Adhesives insulation material to be provided for structural rigidity e.i as per norms. Stability , Integrity, and Insulation for 2 Hrs. Fire Rating. phenolic resin impregnated specially designed honey comb craft paper with suitable internal reinforcement. The door frame made from 18 Gauge GI steel pressed to Single Rebate 100 X 57 mm profile for better structural strength. Frames are to be fixed with fasteners. The gap between the frame & shutter should not exceed 3mm on all side except at the bottom where the gap can go upto a maximum of 10 mm. The frame to be provided with 3 mm thick base plate and duly reinforced; pre-machined for receiving hardware & Hings arrangement & The entire assembly to be prefinished -factory finished heat ovened, powder coated, & made as per approved architectural drawings. The shutter shall be provided with Panic Bar, Vision Panel with Clear fire rated glass with matching beading all around etc. complete as per approved architectural drawing. Approx Size of Single Door 2.1 Mtr x 1.4 Mtr. (Rates shall be Inclusive of Lifting, Minor Civil Works to fix the Door as required and making it good."
Single Leaf Fire Doors
Double Leaf Fire Doors
Providing and Fixing of Standard shaft door to be installed in the shaft size, made of not less than 18 swg MS CRCA sheet having louvers (as required), glass (5 mm thick), and hinges including necessary locking arrangement with Chest handle as required, painting (Powder coated with proper treatment process),including painting (RED Powder coated ) with "FIRE SHAFT " legend.
SingleLeaf Doors (Approx Size - 900 x 1800) FHC Doors
SingleLeaf Doors (Approx Size - 900 x 1800) Electrical Shafts
Ten Loop Panel.
Two Loop Panel.
Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
Supplying, installation, testing & commissioning of addressable phone control module complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
speaker cable Two pair, 2-core, 1.5 sqmm
Supply installation, testing and commissioning of Tube Axial fan confirming to IS-3588 (revised) complete with tube casing in MS/GI standard construction epoxy painted, impeller with adjustable blade angles, bird screen ,gravity louvers, fire retardent double fold moisture and fire proof with flame retardent fabric confirming to IS-206 (revised) fire retardent flexible connection, necessary nut bolts and directly coupled TEFC Sq.cage induction motor (F-class insulation & B-class Temp. rise) suitable for 415V±10%, 50 Hz. 3 phase electric supply complete with required hardware etc.
Basement Exhaust Ventilation Fan Air Qty. = 21000 CFM Static Pressure = 25 mm Wg Proposed Motor = 7.5 KW
Basement Fresh Air Ventilation Fan Air Qty. = 21000 CFM Static Pressure = 20 mm Wg Proposed Motor = 7.5 KW
Lift Well Pressurisation (Terrace) 10th Floor Air Qty. = 13500 CFM Static Pressure = 20mm Wg Proposed Motor = 5.5 KW
Lift Well Pressurisation (Terrace) 17th Floor Air Qty. = 18000 CFM Static Pressure = 20mm Wg Proposed Motor = 7.5 KW
Lift Well Pressurisation (Terrace) 24 Foor Air Qty. = 21000 CFM Static Pressure = 20mm Wg Proposed Motor = 7.5 KW
Lift Lobby Pressurisation (Terrace), 10th Floor Air Qty. = 34000 CFM Static Pressure = 20mm Wg Prposed Motor = 15.0 KW
Lift Lobby Pressurisation (Terrace), 17th Floor Air Qty. = 42000 CFM Static Pressure = 20mm Wg Proposed Motor = 18.5KW
Lift Lobby Pressurisation (Terrace), 24th Floor Air Qty. = 48000 CFM Static Pressure = 20mm Wg Proposed Motor = 18.5KW
Stair Case Pressurisation (Terrace), 10th Floor Air Qty. = 21000 CFM Static Pressure = 20mm Wg Prposed Motor = 7.5 KW
Stair Case Pressurisation (Terrace), 17th Floor Air Qty. = 27000 CFM Static Pressure = 20mm Wg Proposed Motor = 15 KW
Stair Case Pressurisation (Terrace), 24th Floor Air Qty. = 32000 CFM Static Pressure = 20mm Wg Proposed Motor = 15 KW\
Supply and installation of Induced Air Axial Jet fans, balanced to vibration grade of G2.5 as per AMCA 204. Fan shall be complete with GSS casing ( 220 GSM ), Aluminium impeller, Motor Class H, special rated motor certified for 250 Deg C for 2 Hrs - 415/3P/50Hz. Inlet & outlet attenuators each of 2 dia length, inlet & outlet protection net. Deflectors should not be used. Complete assembly shall be certified for 250 Deg C for 2 Hrs. fire rating as per BS EN 12101-3 & the copy of the Fire-test report has to be submitted for the approval.The Locationing of the jet fans has to be done in such a way that the Air velocity at any point on the plane of 1m from the ground level should not be less than 0.25m/s during the normal mode.
Upper basement - 6000 / 12000 CMH
Lower basement - 6000 / 12000 CMH
Supply, installation, balancing and commissioning of factory abricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm sheet
Thickness 0.80 mm sheet
Thickness 1.00 mm sheet
Thickness 1.25 mm sheet
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supply, Fixing and Commissioning of M.S. collar dampers with suitable key operate lever with necessary fittings & support.
Supply, Installation, Testing and Commissioning of Mild Steel louvers with bird screen for fresh air intake.
Supply, Installation, Testing and Commissioning of Mild Steel louvers with bird screen for exhaust air.
Supply and fabrication of angle iron frame, mountings for installation/mounting of fans. The mounting frame work to be fabricated / made out of M.S. channel, angle iron, MS flat, including providing all necessary hardware for completing the installation work, painting with two coats of red oxide primer and pre approved paint.
Electrical Sub Panel - Terrace Level Fans 01 No. - 32 A TP MCB with Conforming to BIS DOL starter, overload relay, start/stop push buttons, ammeter (0-40A) with three CT, on / off / trip indication lights with protection fuse, single phase preventer. MCCB shall be of 25 KA . For upto 7.5 KW Motor duly Synchronized with Fire Fighting Panle for Automatic Starting and Manual Operation Controls & interlocking accessories as Complet with Connection / interconnection required for above switchgears.
Electrical Sub Panel - Terrace Level Fans 01 No. - 63 A TP MCB with Conforming to BIS DOL starter, overload relay, start/stop push buttons, ammeter (0-100A) with three CT, on / off / trip indication lights with protection fuse, single phase preventer. MCCB shall be of 25 KA . For upto 18.5 KW Motor duly Synchronized with Fire Fighting Panle for Automatic Starting and Manual Operation. Controls & interlocking accessories as Complet with Connection / interconnection required for above switchgears.
POWER & CONTROL CABLING Supply, laying, testing and commissioning of power and control cabling, as per Standard specification including end termination as required. Power / Control Cabling ( PVC insulated and PVC sheathed, armoured, Cooper Conductor of 1.1 KV grade on existing cable trays).
4C x 6 Sq mm
4C x 10 Sq mm
2C x 1.5 Sq mm
3C x 2.5 Sq mm
Providing & fixing of weather-Proof Isolator 40A with ELCB for each Outdoor unit.
Providing & fixing of weather-Proof Isolator 63A with ELCB for each Outdoor unit.
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge.
Providing and fixing false ceiling at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595mm of approved texture, design and patterns having NRC (Noise Reduction coefficient) of 0.50 (minimum) as per IS 8225:1987, Light reflectance of 85% (minimum). Non combustible as per BS:476 (part-4), fire performance as per BS:476 (part 6 &7), humidity resistance of 100%, thermal conductivity < 0.043 W/m K as per ASTM 518:1991,in true horizontal level suspended on inter- locking metal T-Grid of hot dipped galvanised iron section of 0.33mm thick (galvanized @ 120 grams per sqm including both sides) comprising of main-T runners of size 24x38 mm of length 3000 mm, cross - T of size 24x32 mm of length 1200 mm and secondary intermediatecross-T ofsize24x32mmoflength600mmtoform grid module of size 600 x 600 mm, suspended from ceiling using galvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 50 mm long, 8 mm outer diameter M-6 dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 85x25x25x2 mm. Galvanised iron perimeter wall angle of size 24x24x0.40 mm of length 3000 mm to be fixed on periphery wall / partition with the help of plastic rawl plugs at 450 mm center to center and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing and as per directions of the Engineer-in-Charge.
12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) : 2011 (Board with BIS certification marks)
Brick work with common burnt clay modular bricks of class designation 7.5 in foundation and plinth in:
Cement mortar 1:4 (1 cement : 4 coarse sand)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:1 / 2:3 (1 Cement: 11⁄2 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size)
1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
Supplying & fixing of ultra/ slim LED exit Lights confirming to IS : 9583-1981 of size 350 mm X 280 mm suitable for operation of 50 Hz , 230 V AC supply with 2 Hours backup self contained dischargable battery (Ni. Cd. Abs Plastic Body surface/ edge light double sided with special application LED signs with LED enclosure made out of 1 mm thick CRCA sheet powder coated with fixing arrangement on wall/cieling complete etc as required.
Providing and fixing of self illuminated / auto glow "EXIT" signs printed on photoluminescent sheet containing self illuminated base chemical, of appropriate size not less than 400 x 150 mm, suspended from ceiling or fixed to the walls with accessories as required and as directed at site.
SITC of ISI marked portable type fire extinguishers of following type complete as per specification and fixed / install as per site condition :
CO2 type 4.5 kg capacity as per IS Code
Water CO2 type of 9 liters capacity as per IS Code
Dry Chemical Powder type of 6 Kg capactiy as per IS Code
For riser main supply
Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way , Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing following rating, double pole, 240 V, isolator/TPN in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A
Supply of 4 pole MCCB, 125A, 36KA
For riser emergency supply
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4 + 12), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A
Supply and installation of 4 pole MCCB,100A,30KA
EXTRA--For all electrical risers in first basement Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
400 A,50KA,FPMCCB
630 A,50KA,FPMCCB
Lift light distribution Panel- lift secondary room Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
4 way (4 + 12), Double door
Single pole
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
400 A,50KA,FPMCCB
250 A,36KA,FPMCCB
100 A,30KA,FPMCCB
For lift operation MCCBs
Supply and installation of 4 pole MCCB,100A,30KA with enclosure.
For lift controlling during operation/repair Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
4 way (4 + 12), Double door
100 A,30KA,FPMCCB
EARTHING
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thickincluding accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
Supplying and laying 25 mm X 5 mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with GI nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced at 50mm)
LIGHTING ARRESTOR
ESE LIGHTNING AIR TERMINAL Supply and installation of Early Streamer Emission (ESE) type Lightning Protection complete with the Stormaster Lightning Air Terminal ‐ Configured as a Spheroid which is comprised of separate electrically isolated 4 panels (stainless steel) surrounding an earthed central finial. The Insulation material used to electrically isolate the panels (stainless steel) is comprised of a base polymer which provides high Ozone & UV resistance with a di‐electric strength of 24‐38 KV/mm. The Stormaster ESE terminal is tested & certified as per NFC 17‐102 with the “Switching Impulse Voltage” of ‐700 KV and “Direct Voltage” of ‐70 KV. The Stormaster ESE terminal is tested & certified by CPRI (Central Power Research Institute), Govt of India for the Impulse current of 45 KA (8/20 micro sec) with 5 positive & 5 negative impulse. (Protection radius = 79 mtrs @ Level 1 / equivalent
Mast Supply and installation of G.I. mast of 5 mtrs height for mounting the terminal & adaptor with the ESE Air Terminal along with supporting guy wires, etc.
Lightning Strike Recorder Supply and installation of Lightning Strike Recorder ‐ 7 digits mechanical display to record the lightning current in an IP 67 enclosure with the minimum sensitivity of 1500A & maximum capacity of 220 KA (8/20 micro second waveform). The recorder shall be of non‐resettable type with the electro‐mechanical display. No LCD screen is used as it may depend upon the battery life to energize the LCD. The lightning strike recorder is duly tested & certified in line with the ese lightning arrester in an international laboratory for an impulse current (8/20 micro sec) of more than 480 KA as per IEC 60‐1:1989 standard. The lightning strike recorder is tested & certified by CPRI (Central Power Research Institute), Govt of India for the Impulse current of 45 KA (8/20 micro sec) with 5 positive & 5 negative impulse.
Chemical Earthing
Supply and fixing of advance chemical gel earthing system of (G.I.) of 3 mtrs long 80 mm dia of outer shell (MS) with the 50mm dia of inner shell (MS) of 80‐100 microns galvanized filled with highly conducting metallic compounds with the permanent sealings at both the ends with the lead terminal of 50x10 mm size at the top. The length of the electrode is 3000 mm excluding the lead terminal and the length of the lead terminal at the top is 100 mm. To ensure the moisture content and electrical conductivity, 50 Kgs of (mixture of Sulphate, Silica, Alumina, Iron Oxide, Titanium Oxide, Calcium Oxide, Potassium Oxide, Chloride, Magnesium Oxide, Sodium Oxide, Zinc Oxide, etc) Resistance Lowering Grounding Minerals. The loss on ignition by mass of the chemical compound is less than 20%. The resistivity of the grounding minerals is less than 0.2 ohm‐mtr with the pH value of 7. The CHEMRODE is duly tested & certified by CPRI (Central Research Institute), Govt of India for a minimum short circuit current of 30 KA rms. The chemical compound is tested and certified by an International accredited, BIS (Bureau of Indian Standards) accredited, ISO 9001 & ISO 14001 certified laboratory. The earthing system manufacturer is an ISO 9001:2008 & ISO 14001:2004 certified organization.
Polyplastic Earth Pit Chamber with Cover Supply and fixing of heavy duty weather proof environment friendly polyplastic earth pit chamber with cover of auto‐locking facility with the following dimensions ‐ 254 mm dia (top), 330 mm dia (bottom) and 260 mm height. 4 knock‐out openings are provided for the easy interconnection of earth strips between the earth pits to form a grid. Supply of 300x300mm C.I. earth pit cover.
Down Conductor Supply of down conductor of 70 sq.mm single core insulated flexible copper cable with necessary accessories, etc
Test Link Joint Supply of weather proof thermoplastic insulated, shock proof, dust & rust proof enclosure of suitable dimension.
Installation,Fixing of Lightning arrester, mast on the roof top (Item No: 1‐6). Fixing of Lightning strike recorder, Test Link joint, Digging and refilling of earth pits (2 separate earth pits) with rod and chemical compound. (Item No:4)
SITC of Aviation obsturction light fixtures with yellow painted die-cast aluminium alloy housing, red coloured polycarbonate dome, including supply of 2 Nos neon light 75 VA Incandescent lamps with all necessary accessories, as required to bemounted at the top with suitable controlling switch. (Item No:4)
Cable/wires for emergency/main circuits
Supply of 35 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable
Supply of 16 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable
Proving and fixing of One No. 2 TR 5 STAR window AC with stabilizer along with providing and FIxing of an anodized Aluminium door ( size 3 ft x 7 ft approx.) partly half-glazed, half panelled along with the frame including door closure , handle, locking arrangement , hinges etc in the Fire control room at Ground floor.
GAS SUPPRESSION SYSTEM Supply, fixing, testing and commissioning of automatic Linear pneumatic Tube Detection based on clean agent (as per technical spec.) System for Electrical Panels (Linear Pnuematic Heat Detection Tube Panel Protection System), consisting of the Mentioned components
2 LB capacity based on clean agent (as per technical spec.) , DLP Assembly with automatic valve, push in connector for tube, clean agent gas , mounting bracket, End of Line adopter and low pressure switch for monitoring system activation.
4 LB capacity based on clean agent (as per technical spec.) , DLP Assembly with automatic valve, push in connector for tube, clean agent , mounting bracket, End of Line adopter and low pressure switch for monitoring system activation.
Linear pneumatic heat Detection Tube with all necessary fittings & supports.
Master Control Unit with Audio Visual Alarm With Wiring to Make Complete System Operational. The Control Panel Should have Provision for integration with Fire Alarm
Any other cost to be incurred for ancillary/ extra / civil/ miscellaneous works necessary to the complete the works mentioned above (lumpsum cost as per tender document)
Cost of dismentled (scrap) materail - will be treated as sell from STC, tax liability will be borne by the bidder (to be subtracted from grand total)
FIRE PROTECTION SYSTEM
Hi-Technocrats Private Limited
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .