Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.2 LAccepted-AOC BYE PASS DALHOUSIE ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹27.9 L+₹61,726 (2.26%)Rejected-AOC 1ST FLOOR GURJEET MARKET DHANGU ROAD | L2 | Rejected-AOC 2nd lowest | |
| 3 | L3₹29.0 L+₹1.7 L (6.08%)Rejected-AOC VILL BUNGDAL DADHANI P O BADHANI DISTT PATHANKOT PIN 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L3 | Rejected-AOC 3rd lowest | |
| 4 | L4₹29.6 L+₹2.3 L (8.33%)Rejected-AOC 451 NEAR RADHA KRISHAN MANDIR VPO MAMUN PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L4 | Rejected-AOC 4th lowest | |
| 5 | L5₹30.8 L+₹3.5 L (12.9%)Rejected-AOC | L5 | Rejected-AOC 5th lowest |
| Sl No | Description | Qty | Unit | Vijay Kumar Contractor and Engineers L2 | M/S V K TRADERS L5 | KULBHUSHAN AGGARWAL L6 | M/S CANTILEVER ENGINEERS L3 | RD Engineers L4 | M/S GULATI ENGINEERING WORKS L1 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply& fixing in replacement, commissioning and testing of LT panel factory made, powdered coated, CPRI approved, floor outdoor type, double door, cubical panel of suitable size, dust & vermin proof fabricated out of 3.15mm thick CRCA sheet suitable for 440 Volts, 3 phase, 4 wire, 50 cycle per second, weather proof, fabricated on 50x50x4 mm thick MS angle iron frame complete, AC supply comprising of capacity 500 Amp (4 strip) aluminium bus bar for phase and neutral mounted on post insulators, MCB DP 63 Amps-4 Nos, MCB TPN 63 Amps-1 Nos wiring the panel with suitable size PVC insulated and sheathed copper cable complete including painting internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer and making good all distrubed surfaces of floor/ wall using RCC/ PCC work as required at site complete all as required at site or directed. Panel including the following accessories :-
(i) Incoming MCCB 320 Amps, FP, 415 V, 36 KA thermal magnetic release - 1 No
(ii) Outgoing MCCB, 250 Amps, FP, 415 V, 25 KA thermal magnetic release - 02 Nos
(iii) Outgoing MCCB, 100 Amps, FP, 415 V, 25 KA thermal magnetic release - 01 No
(iv) Digital voltmeter (0-500) volt with selector switch - 1 No
(v) Digital Ammeter with CTs (0-800) Amps with selector switch - 1 No
(v) Indicator Lamp - 01 set of three
Note - Unit rate include for making all electric connection. | 1 | Each | 1,20,000 ₹1,20,000 | 1,28,600 ₹1,28,600 | 1,50,000 ₹1,50,000 | 1,20,000 ₹1,20,000 | 80,000 ₹80,000 Lowest | 1,10,000 ₹1,10,000 |
| 2.00 | All as per item No 1 here in above but bus bar capacity 380 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 250 Amps, FP, 415 V, 36 KA - 1 No
(ii) Outgoing MCCB, 160 Amps, FP, 415 V, 25 KA - 02 Nos
(iii) Outgoing MCCB, 160 Amps, FP, 415 V, 16 KA - 01 No | 1 | Each | 99,000 ₹99,000 | 1,06,862 ₹1,06,862 | 1,27,000 ₹1,27,000 | 1,20,000 ₹1,20,000 | 85,000 ₹85,000 Lowest | 1,00,000 ₹1,00,000 |
| 3.00 | All as per item No 1 here in above but bus bar capacity 600 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 400 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 200 Amps, FP, 415 V, 25 KA - 02 Nos
(iii) Outgoing MCCB, 160 Amps, FP, 415 V, 25 KA - 02 Nos
(iv) Outgoing MCCB, 100 Amps, FP, 415 V, 25 KA - 01 No
(iv) Outgoing MCCB, 63 Amps, FP, 415 V, 16 KA - 01 No | 1 | Each | 1,50,000 ₹1,50,000 | 1,74,573 ₹1,74,573 | 2,05,000 ₹2,05,000 | 1,40,000 ₹1,40,000 | 85,000 ₹85,000 Lowest | 1,25,000 ₹1,25,000 |
| 4.00 | All as per item No 1 here in above but bus bar capacity 380 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 250 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 160 Amps, FP, 415 V, 25 KA - 01 No
(iii) Outgoing MCCB, 100 Amps, FP, 415 V, 16 KA - 04 No | 1 | Each | 1,10,000 ₹1,10,000 | 1,15,906 ₹1,15,906 | 1,37,000 ₹1,37,000 | 1,21,000 ₹1,21,000 | 8,500 ₹8,500 Lowest | 90,000 ₹90,000 |
| 5.00 | All as per item No 1 here in above but bus bar capacity 300 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 200 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 125 Amps, FP, 415 V, 16 KA - 01 No
(iii) Outgoing MCCB, 100 Amps, FP, 415 V, 16 KA - 02 Nos
(iv) On load change over switch front operated 415 volts 4 pole 200 Amps rating euro load - 01 No | 1 | Each | 1,08,000 ₹1,08,000 | 10,885 ₹10,885 Lowest | 1,29,000 ₹1,29,000 | 1,20,000 ₹1,20,000 | 85,000 ₹85,000 | 95,000 ₹95,000 |
| 6.00 | All as per item No 1 here in above but bus bar capacity 200 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 100 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 63 Amps, FP, 415 V, 16 KA - 02 Nos
(iii) On load change over switch front operated 415 volts 4 pole 200 Amps rating euro load - 01 No | 1 | Each | 80,000 ₹80,000 | 80,325 ₹80,325 | 95,000 ₹95,000 | 75,000 ₹75,000 Lowest | 80,000 ₹80,000 | 85,000 ₹85,000 |
| 7.00 | All as per item No 1 here in above but bus bar capacity 300 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 200 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 125 Amps, FP, 415 V, 16 KA - 02 Nos | 1 | Each | 75,000 ₹75,000 | 73,780 ₹73,780 | 87,500 ₹87,500 | 70,000 ₹70,000 Lowest | 84,500 ₹84,500 | 75,000 ₹75,000 |
| 8.00 | Disconnecting and taking out LT cable up to 25 Sqmm 2/3.5/4 core from trenches/cable duct/through wall/pole carefully complete all as specified and directed.
Note: Earth work, sand, bricks will be measured and paid separately. | 1,460 | RM | 5 ₹7,300 Lowest | 20 ₹29,200 | 10 ₹14,600 | 5 ₹7,300 Lowest | 8 ₹11,680 | 10 ₹14,600 |
| 9.00 | All as per item No 8 but for LT cable 35 to 70 Sqmm 3.5 core. | 500 | RM | 5 ₹2,500 Lowest | 20 ₹10,000 | 10 ₹5,000 | 7 ₹3,500 | 10 ₹5,000 | 20 ₹10,000 |
| 10.00 | All as per item No 8 but for LT cable 95 to 240 Sqmm 3.5 core. | 583 | RM | 5 ₹2,915 Lowest | 20 ₹11,660 | 10 ₹5,830 | 7 ₹4,081 | 10 ₹5,830 | 20 ₹11,660 |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
4 Mar 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Garrison Engineer (N) Mamun
Garrison Engineer (N) Mamun PIN-145001
REPAIR/ MAINT OF LT OH LINES, UG LINES, PANELS, VCBs ETC AT D-1B ZONE UNDER AGE E/M-I OF GE (N) MAMUN
2026_MES_752252_1
GE(N)/M-88/2025-26
Open Tender
Civil Works
Item Rate
180 days
Garrison Engineer (N) Mamun
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Garrison Engineer (N) Mamun
₹60,000
30 Mar 2026
11 Feb 2026
11 Mar 2026
11 Feb 2026
4 Mar 2026
25 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply& fixing in replacement, commissioning and testing of LT panel factory made, powdered coated, CPRI approved, floor outdoor type, double door, cubical panel of suitable size, dust & vermin proof fabricated out of 3.15mm thick CRCA sheet suitable for 440 Volts, 3 phase, 4 wire, 50 cycle per second, weather proof, fabricated on 50x50x4 mm thick MS angle iron frame complete, AC supply comprising of capacity 500 Amp (4 strip) aluminium bus bar for phase and neutral mounted on post insulators, MCB DP 63 Amps-4 Nos, MCB TPN 63 Amps-1 Nos wiring the panel with suitable size PVC insulated and sheathed copper cable complete including painting internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer and making good all distrubed surfaces of floor/ wall using RCC/ PCC work as required at site complete all as required at site or directed. Panel including the following accessories :-
(i) Incoming MCCB 320 Amps, FP, 415 V, 36 KA thermal magnetic release - 1 No
(ii) Outgoing MCCB, 250 Amps, FP, 415 V, 25 KA thermal magnetic release - 02 Nos
(iii) Outgoing MCCB, 100 Amps, FP, 415 V, 25 KA thermal magnetic release - 01 No
(iv) Digital voltmeter (0-500) volt with selector switch - 1 No
(v) Digital Ammeter with CTs (0-800) Amps with selector switch - 1 No
(v) Indicator Lamp - 01 set of three
Note - Unit rate include for making all electric connection. | 1 | Each | - | - |
| 2 | All as per item No 1 here in above but bus bar capacity 380 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 250 Amps, FP, 415 V, 36 KA - 1 No
(ii) Outgoing MCCB, 160 Amps, FP, 415 V, 25 KA - 02 Nos
(iii) Outgoing MCCB, 160 Amps, FP, 415 V, 16 KA - 01 No | 1 | Each | - | - |
| 3 | All as per item No 1 here in above but bus bar capacity 600 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 400 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 200 Amps, FP, 415 V, 25 KA - 02 Nos
(iii) Outgoing MCCB, 160 Amps, FP, 415 V, 25 KA - 02 Nos
(iv) Outgoing MCCB, 100 Amps, FP, 415 V, 25 KA - 01 No
(iv) Outgoing MCCB, 63 Amps, FP, 415 V, 16 KA - 01 No | 1 | Each | - | - |
| 4 | All as per item No 1 here in above but bus bar capacity 380 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 250 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 160 Amps, FP, 415 V, 25 KA - 01 No
(iii) Outgoing MCCB, 100 Amps, FP, 415 V, 16 KA - 04 No | 1 | Each | - | - |
| 5 | All as per item No 1 here in above but bus bar capacity 300 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 200 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 125 Amps, FP, 415 V, 16 KA - 01 No
(iii) Outgoing MCCB, 100 Amps, FP, 415 V, 16 KA - 02 Nos
(iv) On load change over switch front operated 415 volts 4 pole 200 Amps rating euro load - 01 No | 1 | Each | - | - |
| 6 | All as per item No 1 here in above but bus bar capacity 200 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 100 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 63 Amps, FP, 415 V, 16 KA - 02 Nos
(iii) On load change over switch front operated 415 volts 4 pole 200 Amps rating euro load - 01 No | 1 | Each | - | - |
| 7 | All as per item No 1 here in above but bus bar capacity 300 Amps and comprises of the following incoming and outgoing:-
(i) Incoming MCCB 200 Amps, FP, 415 V, 36 KA - 01 No
(ii) Outgoing MCCB, 125 Amps, FP, 415 V, 16 KA - 02 Nos | 1 | Each | - | - |
| 8 | Disconnecting and taking out LT cable up to 25 Sqmm 2/3.5/4 core from trenches/cable duct/through wall/pole carefully complete all as specified and directed.
Note: Earth work, sand, bricks will be measured and paid separately. | 1,460 | RM | - | - |
| 9 | All as per item No 8 but for LT cable 35 to 70 Sqmm 3.5 core. | 500 | RM | - | - |
| 10 | All as per item No 8 but for LT cable 95 to 240 Sqmm 3.5 core. | 583 | RM | - | - |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.45 MB
BOQ_842551.xls
BOQ • 0.33 MB
tender88.pdf
Tender Documents • 1.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .