| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.7 LAccepted-AOC MAIN ROAD RANJHI JABALPUR 482005 M P | JABALPUR | MADHYA PRADESH | 482005 | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹27.0 L+₹91,310 (3.50%)Rejected-Finance MAIN ROAD RANJHI BAZHAR JABALPUR MP PIN 482005 | JABALPUR | MADHYA PRADESH | 482005 | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹38.7 L+₹12.6 L (48.1%)Rejected-Finance 1257 SCHEME NO 5 NEAR HB COLLEGE VIJAY NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
5 May 2022, 6:00 pmClosed
CWE JABALPUR
HQ CWE JABALPUR OPPOSITE SUPPLY DEPOT SADAR JABALPUR 482001
PROVISION OF RING MAIN UNIT(RMU) 11 KVA AND OTHER CONNECTED CABLE WORKS UNDER MES IB AND EME , AND PROVISION OF VCB FOR CONTROLLING OF 11 KVA FEEDER AT RIDGE ROAD HOUSE UNDER GE(WEST) JABALPUR
2022_MES_517464_1
81930/E8
Open Tender
Miscellaneous Works
Item Rate
240 days
JABALPUR
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
GE (West) Jabalpur
₹56,000
Yes
28 May 2022
9 Apr 2022
7 May 2022
9 Apr 2022
5 May 2022
23 Apr 2022
9 Apr 2022 - 22 Apr 2022
Amount
Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, for laying of pipe, cable etc or n. exc.10 Sqm on plan and n. exc. 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in soft/ loose soil complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
Removing surplus excavated spoil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Supply and spreading clean and dry fine sand free from sharp materials (unwashed) laying in trenches around the cable for cushioning in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed ( Note: Punned thickness will be measured for payment).
M&L for 40mm graded stone aggregate for spreading/ loose filling under 11 KV four pole, arround the transformer, substation and other places where directed. Note:- Contractor shall make regular heaps/ stacks for measurement of item before spreading/ filling.
M&L for PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation, filling, mass concrete etc complete all as specified & directed.
Material and labour for providing Plain Cement Concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) for coping of poles including necessary form work and finish the surface even and smooth without using extra cement complete all as specified and directed by Engr in charge.
Dismantling of concrete poles/ struts, any size including stacking & removal from site complete all as directed.
Dismantling of old unserviceable GI earth wire from HT over head lines including removal from site complete all as directed.
Dismantling of old unserviceable ACSR conductors from HT over head lines including removal from site complete all as directed.
Dismantling of existing old cross arms, bracings, supports etc of any section, FI clamps, nuts, bolts, insulators etc. from OH line and checking for re-use & removal of unserviceable cross arms, bracing, supports etc from site complete all as specified and directed.
Dismantling of insulators any size/ type from poles including removal from site complete all as directed.
Dismantling of unserviceable stay assembly carefully including stay wire necessary excavation and earth work in any type of soil, demolition of PCC of any type and removing from site complete all as specified and as directed.
Dismentling of air break gang operated switch vertical/ horizontal mounted incluidng insulators and operating mechanism for repair/ replacement of broken/ worn out components and insulators etc. and removing from site complete all as specified and as directed.
Supply and laying or fixing or passing in trenches/ on pole/ through pipes, 11000 volts (E) grade, XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor of cross sectional area 95 sqmm, 3 core conforming to IS 7098/ (PART-II) 1985 with latest amendments and testing on completion complete all as directed. Make:- Havells or Finolex or Gloster or Plaza or Universal as approved by GE. Note:- Excavation, earth work, sand cushioning and cable protection shall be measured and paid separately under respective items of BOQ.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm and testing on completion complete all as directed. Make:- M SEAL or RAYCHEM or DENSON or CAB SEAL as approved by GE.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm and testing on completion complete all as directed. Make:- M SEAL or RAYCHEM or DENSON or CAB SEAL as approved by GE.
Supply, fixing & connecting battery bank comprising of charging facilities, current transformer,voltmeter, ammeter, connection with Sheet steel enclosure with and including maintenance free lead acid rechargeable battery of 2 Volt, 100AH, 15 Nos connecting with each other with nut, bolts conforming to IS 15549/2005 and IEC 60896 - 21 & 22 for tripping system to HT breaker during fault occurence at 11 KV Sub station including connecting, wiring,cable plug top and making connection from VCB with required copper cable for making connection to VCB with required cable and testing on completion including taking down old unserviceable battery bank complete all as specified and directed. Make - Exide/Amco/Amron/Amar Raja or other equivalent Make as approved by GE
Earthing complete with galvanised steel earth pipe, medium grade, 3000mm long with outer dia 65mm and inner dia 50mm, laid in ground by drilling in the ground with top edge not less than 1.25 metre below ground level and filling the back fill compound complete with all as required and directed, as per Electrical Plate No. 2, with 32x6 mm GI strip as earthing lead up to testing point and making the earth pit of PCC as per sample as required at site and testing after completion complete all as specified and directed. (Note:- GI strip from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rates as quoted by the contractor.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6.0mm thick directly burried in the ground (earth pit not less than 2.25M deep below ground level) with top edge of earth plate not less than 1.50M deep below normal ground level, connected to galvanised iron strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 40mm bore GI pipe medium grade including necessary fittings for protection of earthing strip, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be given 12mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge (0.63 mm) 8 mesh per linear incl 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS deformed bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS/ GI bolts & washers as required and connection from earth test point to earth electrode with same GI earth strip alongwith protection pipe and testing on completion complete all as specified and directed. Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rates as quoted by the contractor.
Supply, Installation, testing and commissioning HT 11 KV, 3 Phase, 50 Hz, 3 wire, totally enclosed, metal clad, prewired, extensible type, indoor type, floor mounted, Horizontal draw out, horizontal isolation type vaccum circuit breaker (VCB) 630 Amp rating, consisting of INCOMER VCB-01 No, Outgoing VCB-01 No and suitable size adopter panel to connect new VCB panel with the existing HT VCB Panel with copper bus bar of appropriate capacity duly insulated, motor operated, spring charged having rupturing capacity 350 MVA , comprising of the followings including provision of suitable foundation and duct under the VCBs for necessary entry for cables with and including the followings:- (A) Incoming VCB, 630 Amps, 350 MVA - 01 No with and including the followings : (a) Housing for circuit breaker carriage - 1 No (b) Vacuum interupter suitable for 630 Amps-set of 03 (c) Mechanical inter lock and automatic safety shutter gear including padlocking arrangement - 1 No (d) Closing & tripping coil suitable for 24 V DC - 01 Set (e) 4 NO + 4 NC Auxiliary switch - 01 Set (f) Mechanical ON/OFF indicator - 01 Set (g) Mechanical spring charge/discharge indicator-01 Set (h) Breaker Position indicator - 01 Set (j) Mechanical operating counter-01 Set (k) Automatic safety shutters - 01 Set (l) Secondry Plug in contacts-01 Set (m) Anti Pumping relay - 01 Set (n) 11 KV Epoxy Resin Cast current transformer of ratio 200-100/50-5+5A, Core I, Class 1.0 with 15 VA burden for metering, core II CL-1.0, 5 P 10 with 15 VA burden for protection, - 03 Nos
(r ) Relay non drawout case type, micro processed based non-direction IDMT - 01 No (s) Master trip relay model No AVAJH-13-01 No (t) Auxilary relay - Model No AVA-23-01 No (u) Trip circuit superision relay model No JRV-911-01 No (w) KWH meter suitable to record unit consumed-01 No (x) R,Y,B indication lamp- 01 Set (xi) Breaker ON/OFF indicating lamps-01 No (xii) Spring charging indication lamp-01 No (xiii) Auto trip indication lamp-01 No (xiv) Trip circuit healthy indication-01 No (xv) Trip/Neutral/Close switch-01 No (xvi) Trip circuit healthy push button-01 No (xvii) MCB for spring charge motor-01 No (xviii) MCB for AC/DC supply-01 Set (xix) Panel space heater with thermostat-01 No (xx) Panel illumination with switch-01 No (xxi) 5 Amps 3 pin socket with switch-01 No (xxii) Copper Bus bar 630 Amps rating with sleeves R, Y. B-01 Set (xxiii) Control fuses, ferules & wiring complete - 01 Set (xxiv) MS cubical with powder coating - 01 Set (h) Rear cable termination, provision for terminating 1x3 core x 95 sqmm XLPE cable -01 No for incoming and side cable termination box arrangement for terminating 1 x 3 core x 95sqmm for outgoing (p) In-built integral earthing
(C ) Adopter Panel, 11 KV with bus bar - 01 No and Modification to existing 11 KV VCB panel 630 Amps, 350 MVA by connecting new VCB Panels with existing VCB panels by providing adopter panel made out of MS sheet, powder coated completely with the same specification as of VCBs cubical with indicator, availability of HT Supply, 630 Amps Copper busbar with suitable size insulators for mounting of Busbar, completely enclosed of suitable length and width, bolted construction duly marked as ADOPTER PANELS complete all as directed and as required at site. (Notes : 1. Before placement of order, contractor will submit GA drawing to GE for approval . On approval of drawing, contractor shall place the order. 2. Pre-dispatch inspection shall be carried out at Manufacturer Premises by Representative of Accepting Officer. cost thereof , if any, is deemed to be included in the unit rate quoted by the contractor )
Supply and laying un-reinforced precast concrete cable covers, Class HV, Type1, flat, size 300mm x 180mm x 40mm complete all as specified and as directed.
Supplying and fixing/ laying of 80mm bore dia GI pipe light grade in trenches/ under roads/ along pole/ wall including all fittings, ISI marked as required for cable protection etc after taking out the old unserviceable pipe complete all as specified and directed.
Drilling (Horizontally) to existing road (maximum 10M wide) suitable for passing GI tubing of dia upto 80mm/ 100mm as required at site complete all as specified and directed. Note:- All necessary T&P required at site for drilling shall be arranged by contractor at his own cost and quoted rate shall be deemed to be included for all these provisions and nothing extra shall be paid on this account.
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc as required with 32x6mm galvanised iron strip complete all as specified and directed.
Supply, installation, commissioning and testing of 12 kV SF6 Ring Main Unit, compact, out door type, 630 Amps, rated capacity 25 kA for 1 sec having 2 vacuum circuit breaker (VCB) insulated in SF6, one load break switch (LBS) insulated in SF6 and one Bus PT panel extensible to right side RMU/ Outdoor, motorised having metering panel and copper bus bar of suitable ampere ratings complete with and including the followings:- Make of RMU:- Schneider or ABB or L&T as approved by GE. Notes: (i) Brief description of this item is "12 kV, SF6 Ring Main Unit complete with 2 Vacuum Circuit Breaker + 1 LBS+ 1 Bus PT Panel (Right side extensible / OUTDOOR). FBX-RE/12-21/ M+CT2T2 /OUTDOOR - MOTORIZED". (ii) As per manufacturers design, cost of making of platform shall be deemed to be included in unit quoted rates. (iii) All necessary arrangements for performance testing of RMU shall be made by contractor without any extra cost to government.
(A) HT COMPARTMENT: VACUUME CIRCUIT BREAKER - Each module (Vaccume circuit breaker) enclosed in SF6 -02 Nos. (a) The function unit shall be consist a three position switch. The three position switch shall fulfil the operation of the disconnector function and the earthing function. The circuit breaker unit T2 shall equped with an over current time release for the protection of distribution transformer. (b) Vacuume circuit breaker shall be of 12kV, 630 Amps, 25 kA for one sec enclosed in SF6. (c) Spring assisted closing with stored energy tripping mechanism for T2-motorised operation with integrated earthing switch. (d ) Having auxiliary contacts on load break switch 1 NO+2 NC & auxiliary contacts on earth switch 1 NO+1 NC - 01 No. (e) Self powered electronic numerical protection relay providing 3 over current & 1 earth fault protection of make Schneider - DPX Relay or make C&S - CSDPR-V2 or equivalent of other make as approved by GE - 01 No. (f) Tape wounded protection CT shall be 100/5, 10P5, 2.5VA - 03 Nos. (g) Tape wounded metering CT shall be 100/5, Class-1.0, 2.5 VA - 03 Nos. (h) Shunt trip Coil - 24 V DC - 01 No. (j) Capacitive voltage indication fixed type (LED display) - 01 No. (k) On/ Off/ TRIP mechanical indication on the front mimic of the panel-01 Set. (l) Cable box for termination of XLPE cable of size 3 core 95 sqmm to 120 sqmm aluminium conductor- 01 No. (m) Cable cover standard - 01 No. (n) Emergency trip push button- 01 No. (o) Set of 12 kV cable termination boots - 1 Set (p) Ammeter of suitable capacity/ class -01 No. (q) Rated frequency - 50/60 Hz
(r ) Rated Power frequency withstand voltage directly earthed -28 kV (s) Level of insulation for the SF6, rated lightening impulse withstand voltage - 75 kV (t) Level of insulation for the SF6, rated power frequency withstand voltage - 28 kV (u) Level of insulation of the sectionalized distance for the cable test energized busbar, maximum AC feeder test voltage - 18 kV (v) Rated current busbar C-R-RE functions - 630 Amps (w) Rated current busbar SB functions - 630 Amps (x) Rated current outgoing feeder- 630 Amps (y) Rated short time current, main electrical circuit for 1 Sec - 25kA (z) Rated short time current, earthing circuit for 1 Sec - 25kA (aa) Rated network load and closed loop breaking current - 630 Amps (ab) Rated no load cable breaking current -160 Amps (ac) Rated breaking current under earth fault conditions - 630 Amps (ad) Rated no-load cable breaking current under earth fault conditions - 277 Amps (B) HT COMPARTMENT: LOAD BREAK SWITCH- C, 12 kV, 25 kA, 630 Amps - EACH MODULE (LBS) enclosed in SF6 -01 No. (a) The switching unit shall be so designed as a three position switch. The three position switch combines the functions of switch disconnector and earthing switch. The switch disconnector as well as the earthing switch shall be equipped with a separate drive unit. (b) Cable switch 11 kV, 630 A, 25 kA for 1 sec - 01 No. (c ) Spring assisted mechanisim for C-manual operation with integrated earthing switch - 01 No. (d) Cable bushing 630 Amps, Standard C-bushings - 01 No.
(e) Aux switch for load break (ON & OFF) - 01 No. (f) Cable Cover standard - 01 No. (g) Capacitive voltage indication fixed type (LED display) - 01 No. (h) On/ Off/ EARTH indication on the front mimic of the panel - 01 Set. (j) Cable box for termination of XLPE cable of size 3 core 95 sqmm to 120 sqmm aluminium conductor- 01 No. (k) Operation counter - 01 No. (l) Cable boot suitable for 11 kV - 01 Set, cable entry shall be provided from front bottom (m) Rated frequency - 50/60 Hz (n ) Rated power frequency withstand voltage directly earthed -28 kV (o) Level of insulation for the SF6, rated lightening impulse withstand voltage - 75 kV (p) Level of insulation for the SF6, rated power frequency withstand voltage - 28 kV (q) Level of insulation of the sectionalized distance for the cable test energized busbar, maximum AC feeder test voltage - 18 kV (r) Rated current busbar C-R-RE functions - 630 Amps (s) Rated current busbar SB functions - 630 Amps (t) Rated current outgoing feeder- 630 Amps (u) Rated short time current, main electrical circuit for 1 sec - 25kA (v) Rated short time current, earthing circuit for 1 sec - 25kA (w) Rated network load and closed loop breaking current - 630 Amps (x) Rated no load cable breaking current - 160 Amps (y) Rated breaking current current under earth fault conditions - 630 Amps (z) Rated no-load cable breaking current under earth fault conditions - 277 Amps
(C) BUS METERING PANEL (a) 03 Single phase PT 11 kV/ RT3/ 110V/RT3, 100 VA, class -1.0 (b) 01 Space heater (c ) RYB indication - one set (d) 01 No. Voltmeter (e) Microprocessor based three phase electronic tamper proof HT energy meter with optical communication port, accuracy class 0.5 rating 3 X 110 V, 1/5 A conforming to IS : 13779. (f) 24 V DC battery and battery charger - 01 Set
(D) Additional equipment to be mounted on each RMUs (a) Manometer - 01 No. (b) Operating Handle - 01 No. (c) Cable clamping provision (standard) - 01 Set (d) Cable testing Plug and Stud - 01 set (e) O&M Manual (f) I&C Manual
(E) The RUM shall also capable for the following : The RMU shall be gas insulated metal enclosed. The high grade steel gas tight tank shall inculde switch devices or circuit breaker, internal copper bus bar, bushings for cable connections, pressure relief device, copper earth bus bar. The drive cabinet shall contains a user friendly control panel with a mimic diagram, In this diagram the drive socket and position indicators for all switch devices are clearly arranged. there is an instrument compartment on top of the drive cabinet and it shall contain short circuit indicators for cable feeders, capacitive voltage detection system, standard Manometer. The auxiliary equipment like trip coils or aux contacts shall be wired to central termination blocks in each feeder . The switching devices shall have separate drive system, which are operated with non interchangable plug-in levers. A complete interrogator interlocking system reliably prevents control errors and ensures high operation convenience. The RMU shall compiled with stndarads IEC 62271-200, IEC 62271-200, IEC 62271-100, pressure of SF 6 gas shall be 1.3 bars at 20 deg C.
Schedule of credit amount of Rs. 41, 070.00 to be deducted during AOC
ELCON
Sachdeva Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .