Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.9 LAccepted-Finance | L1 | Accepted-Finance Accepted as 1st Lowest Bidder for the execution of subjected work | |
| 2 | L2₹13.0 L+₹5,619 (0.43%)Accepted-Finance | L2 | Accepted-Finance Accepted as 2nd Lowest Bidder for the execution of subjected work | |
| 3 | L3₹13.5 L+₹53,637 (4.14%)Accepted-Finance | L3 | Accepted-Finance Accepted as 3rd Lowest Bidder for the execution of subjected work | |
| 4 | L4₹13.6 L+₹63,048 (4.87%)Accepted-Finance | L4 | Accepted-Finance Accepted as 4th Lowest Bidder for the execution of subjected work | |
| 5 | L5₹14.4 L+₹1.4 L (10.9%)Accepted-Finance | L5 | Accepted-Finance Accepted as 5th Lowest Bidder for the execution of subjected work |
Tender Value
₹15.1 L
EMD Value
₹30,200
Closing Date
8 Sept 2023, 4:30 pmClosed
Executive Engineer, KPDCL, ED2nd,Rajbagh
Office of the Executive Engineer, KPDCL, ED2nd,Rajbagh, Srinagar
Creation of Dedicated 250 kVA, 11/0.433 KV Pole Mounted Sub-Station alongwith laying of HT/LT network at Shri Moti Lal Saqi (Memorial) Govt. Degree College, Hyderpora Campus, Srinagar - Sub-Division Baghat - (on SITC Basis)
2023_PDD_227258_1
ED-II/10 of 2023-24 Dated 19/08/23
Open Tender
Electrical Works
Turn-key
40 days
Govt. Degree College, Hyderpora Campus
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
Yes
Ex. Engineer,KPDCL, ED2nd Credited to MH0801 Power
₹30,200
Yes
5 Oct 2023
23 Aug 2023
9 Sept 2023
23 Aug 2023
8 Sept 2023
24 Aug 2023
23 Aug 2023 - 24 Aug 2023
Amount
Supply, Installation, Testing and Commissioning of 250 kVA, 11/0.433 KV 3-phase Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2 Pre Ammendement, (Copper Wound), and with LV Cable Box having detachable Aluminium Gland plate.Transformer should have arrangement for vertical Take off. The Job shall also include loading, carriage and unloading upto site. All test certificates as mandated as per amendment 4 to IS-1180 (Part-I) : 2014 are to be provided by the bidder “Prior to installation of 250 kVA (Copper Wound) DT – [Energy Level 1 as per Amendment 4 to IS:1180 (Part -1) : 2014 (i.e Energy Level-2 Pre-amendment)] at site, the same shall be got tested at any Regd. SSI unit, Srinagar at the cost of bidder.”
Supply and Erection of ST Pole 9 mtr. long (ST-410 SP33) with Galvanized Channel Iron Earthing Arrangement (as per Drawing CE/P&P/Dwg/2022-STP-E0001 attached) including its loading from factory unit, carriage and unloading upto site. (Poles shall be got tested at the cost of bidder prior to its delivery at site for erection)
Supply and Erection of ST Pole 8 mtr. long (ST-410 SP15) with Galvanized Channel Iron Earthing Arrangement (as per Drawing CE/P&P/Dwg/2022-STP-E0001 attached) including its loading from factory unit, carriage and unloading upto site. (Poles shall be got tested at the cost of bidder prior to its delivery at site for erection)
Supply, Laying, Testing and Commissioning of 0.03 ACSR Conductor
Supply, Laying, Testing and Commissioning of 0.05 ACSR Conductor
Supply, Installation, Testing and Commissioning of Gapless Surge Arrestor, 9 kV, 10 kA, LA with polymer housing, Stn. Type (as per drawings)
Supply, Installation, Testing and Commissioning of 11 KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type (strictly as per drawing attached) including earthing of GO switch Handle
Supply, Installation, Testing and Commissioning of 11 KV Horn Gap Fuse Set 3 Phase 200 Amp (strictly as per drawing attached)
Supply, Laying, Testing and Commissioning of 300 mm sq Single Phase Cable, 1.1 KV Grade, un-armoured XLPE Insulated Stranded Conductor FRLS type
Providing, Fabrication and Fixing of GI Channel/Angle/Flat (Dimensions as per Sub-Station drawing attached)
Providing, Fabrication and Fixing of Galvanized V Cross-Arms duly fabricated of size 75x40x6mm Channel Iron Cross Arm with 04 No. (50x50x6mm) welded flat iron plates (as per Drg. No. CE/P&P/DRG/2022/11KVL001) including Pole Top Bracket fabricated out of a) 65x65x6mm (385 mm length), b) ISLC 75x40x6mm (65 mm long), c) MS Flat 02 No. (262 mm length each) and necessary Pole Clamps
Providing and Laying of Earthing of substation Complete with all accessories --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. Interconnection of 3 earthing pipes by 50x6 mm GI Flat. GI Strip of size 25 mm x 3 mm for neutral earthing (Two distinct connections) / connection of transformer body and LA. Earth pits to be refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover besides 8 SWG GI Wire connections for Transformer body, MCCB Box (2 distinct connections) and earthing terminal of Poles (Description as per Approved Drawing)
Providing and Fixing of MCCB TPN 400 Amp (having breaking capacity of 35 kA) wih Enclosure with proper clamping and earthing arrangement
Providing and Fixing of Galvanized Nuts and bolts with washers
Providing and Fixing of Aluminium Lugs 300 sq mm
Providing and Fixing of Aluminium Solderless clamps for 250 kVA Transformer
Providing and Fixing of Wedge Connectors / PG Clamps
Providing and Fixing of 11 KV Polymer Pin Insulator 12 kV, 5 kN, Lighting Impulse 75 kV Positive and 80 kV Negative, creepage distance 320 mm
Providing and Fixing of 11 KV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80 kV Negative, creepage distance 320mm (with fiting)
Providing and Fixing of GI Pole collars 50x8 mm (Back Clamps Dimensions as per Approved Drawing attached) for D.O/Fuse/Operating handle/AB Switch/Belting Angles etc
Providing and Fixing of Danger Plates (11 KV and 440 V) with Clamps
Providing and Fixing of Anticlimbing Device using GI Barbed wire with end Clamps (2 kg Barbed wire per job/pole with 2 GI clamps with GI nuts/bolts and washers)
Providing and Fixing of GI Muki Clamp of 50x8 mm galvanized flat iron having end inner dia 18 mm for Shackle Insulators suitable for ST Pole with back clamp and galvanized nuts and bolts
Providing and Fixing of 16 kN Polymer Shackle Insulators
Providing and Fixing of LT Spacers
Providing and Earthing of ST Poles 9 mtr/ 8 mtr long Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Providing and Laying of Cement Bottoming of ST Pole 9 mtr long in the ratio 1:2:4 mix as per approved drawing (0.5cum/pole)
Providing and Laying of Cement Bottoming of ST Pole 8 mtr long in the ratio 1:2:4 mix as per approved drawings (0.45cum/pole)
Providing and Painting of ST Poles 9 mtr long with 1 coat of red oxide and 2 coat of aluminium paint
Providing and Painting of ST Poles 8 mtr long with 1 coat of red oxide and 2 coat of aluminium paint
Supply, Installation, Testing and Commissioning of HT Tri-Vector Metering unit Complete with CT/PT units and with all accessories/modem. PT 11 KV/ 110 V, Class of Accuracy 0.5 S, VA 15 and CTR 20/5, Class of Accuracy 0.5 S, VA 15, STC 70.3 kVA for 3 Sec including Insepction, testing and GI make stand (2.5ft above ground) with proper grouting (Refer all Details provided in Tender Document for 11 KV HT Metering Unit)
Providing/Submission of Both Pre and Post Work Execution Geo-Tagged Coloured Photographs of subjected work on A4 sized photopaper (1 pic per page)
M/S INTERNATIONAL STORES
KAPH TECH CONSULTANCY (P) Ltd.
M/S R R ELECTRICAL SERVICES
M/S AISHA ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .