Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹26.4 LAccepted-AOC 34 1 12 2F SAINIK VIHAR DEORI ROAD AGRA UP 282007 | AGRA | UTTAR PRADESH | 282007 | 1 | Accepted-AOC Being lowest | |
| 2 | 2₹27.8 L+₹1.1 L (4.27%)Rejected-Finance D 662 WZ 1598 R 1 NANGAL RAYA NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | 2 | Rejected-Finance Not being lowest | |
| 3 | 3₹31.9 L+₹5.2 L (19.5%)Rejected-Finance | 3 | Rejected-Finance Not being lowest |
Tender Value
₹30.1 L
EMD Value
₹60,240
Closing Date
6 Aug 2020, 6:00 pmClosed
HQ CWE Agra
112 Taj Road Agra Cantt
REPAIR MAINTENANCE OF HIGH BAY LIGHT, DBs, INTERNAL WIRING, LIGHTENING CONDUCTOR AND EARTHING OF COD UNDER GE (WEST) AGRA
2020_MES_359625_1
84179/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Agra
MES contractors enlisted in Class
D and cat b(i) for unenlisted contractors meeting the enlistment criteria corresponding to value class and category of work
8 documents required · 8 mandatory
₹500
GE West Agra
₹60,240
Yes
25 Aug 2020
9 Jul 2020
12 Aug 2020
9 Jul 2020
6 Aug 2020
23 Jul 2020
9 Jul 2020 - 16 Jul 2020
Amount
Taking down carefully existing unserviceable copper / aluminum point wiring of any description & in any position with and including taking out existing unserviceable conduits or battens of any description with sunken boxes/junction boxes and all fitting, accessories & fixtures such as switches, ceiling roses, pendants, regulators, socket, light fittings, lamp holders etc but excluding light fittings and making good the disturbed surface of walls, floors, ceiling etc to match with the existing surfaces complete all as specified and directed.
Taking down carefully sub main wiring / service connections of any size including batten / conduit and making good the disturbed surfaces of wall / floor complete all as specified and directed.
Material and labour for point wiring for one light point or one fan or bell point controlled by one switch with using 1.5 Sqmm (nominal area) stranded copper conductor, single core, PVC insulated & unsheathed cable, 1100 volts grade in and including concealed PVC conduit (Medium grade) of suitable size all as directed with using new sunken type pressed steel box / terminal boxes for mounting fittings/junction boxes not less than 1.6mm thick duly painted with two coats of black bituminous paint over a coat of red oxide primer with 3mm thick bakelitelaminated sheet, and including all accessories and using 1.5 Sqmm (nominal area) stranded copper conductor single core conductor, PVC insulated & unsheathed cable as in earth wire connected to common earth dolly complete all as specified and directed.
All as per Srl item No. 3 here in above but point wiring for 5 pin switch socket outlet, 5 Amps on same board with other switches complete all as specified and directed.
All as per Srl item No 3 here in above but point wiring for 5 pin switch socket outlet, 5/6 Amps on independent board.omplete all as specified and directed.
All as per Srl item No 03 here in above but point wiring for one six pin socket outlet, 15 & 5 Amps (independent) controlled by one switch with using 2.5 Sqmm (nominal area) stranded copper conductor complete all as specified and directed. Notes for item 3 to item 6 here in below : (i) The quoted rates shall be deemed to be inclusive for cutting chases in brick walls/pillars etc. for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of point wiring at RCC Columns/Beams/Ceilings shall be in surface conduit of suitable size fixed on surface with using PVC rawl plugs and provision of covering sunken boards/terminal boxes / junction boxes of any shape and size with 3mm thick bakelitelaminated sheet fixed with suitable GI screws and cup washers) (ii) Fittings like switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A' (iii) The size of conduits shall be determined on permissible No. of runs of wires as specified in SSR Part-I (2009) clause 19.125 (B). However minimum size of conduit shall be 20mm dia (Medium grade)
Supplying & fixing for piano switch flush type, 5/6 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed. Cat Part No.38058 of make Anchor or equivalent model of specified make as approved by GE
Supplying & fixing for socket outlet, five pin, 5/6 Amps, flush type, 230 volts AC circuit complete all as specified & directed . Cat Part No.38320 of make Anchor or equivalent model of specified make as approved by GE
Supplying & fixing for piano switch flush type, 20 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed. Cat Part No.39991 of make Anchor or equivalent model of specified make as approved by GE
Supplying & fixing for socket outlet, multipurpose, three pin, 15/16 Amps & three pin 5 Amps controlled by one switch , flush type, 230 volts AC circuit complete all as specified & directed. Cat Part No.39994 of make Anchor or equivalent model of specified make as approved by GE
Supplying & fixing for ceiling rose surface bakelite 62.5 x 25 mm size, three terminals, complete all as specified & directed. Cat Part No.39072 of make Anchor or equivalent model in specified make as approved by GE.
Supplying & fixing for lamp holder, insulated body with back plate suitable for batten fitting complete all as specified & directed. Cat Part No.39797/39800 of make Anchor or equivalent model in specified make as approved by GE.
Supply and fixing rotory stepped type electronic fan regulator mini flush type 100 watt 230 volts complete all as specified & directed.Cat part No.38284 / 38660 of make Anchor or equivalent model in specified make as approved by GE
Supplying & fixing in replacement modular switch,one module single pole one way 6 Amps, 230 volts AC circuit complete all as specified & directed. Make :- Legrand / Crabtree as per sample at site as approved by GE.
Supplying & fixing in replacement modular socket outlet, double module 6 Amps, 2/3 pin, 230 volts AC circuit complete all as specified & directed. Make :- Legrand / Crabtree as per sample at site as approved by GE.
Supplying & fixing in replacement modular switch,1 module single pole one way 16 Amps, 230 volts AC circuit complete all as specified & directed. Make :- Legrand / Crabtree as per sample at site as approved by GE.
Supplying & fixing in replacement modular socket outlet, 2 module 6-16 Amps, 2/3 pin, 230 volts AC circuit complete all as specified & directed. Make - Legrand / Crabtree as per sample at site as approved by GE.
Supply & fixing in replacement modular bell push,1 module single pole 6 Amps, 230 volts AC circuit complete all as specified and directed. Make :- Legrand / Crabtree as per sample at site as approved by GE.
Supplying & fixing in replacement modular ceiling fan regulator,electronic, step type single module, suitable for ceiling fans of any capacity, pre-wired 230 volts AC 50Hz supply 120 Watt complete all as specified & directed. Make - Legrand / Crabtree as per sample at site as approved by GE.
Disconnecting and taking down old unserviceable sheet metal enclouser any size any type including MCB etc complete and Supply, fixing, connecting & testing sheet metal single pole and neutral enclosure with metal clad (two pin and earth) plug top and socket complete with and including one No MCB ( 'C' series), SP, 20 Amps, 240 Volts, having breaking capacity 10 KA complete all as specified and directed.
Supply and fixing in replacement modular GI flush box 1/2 module as per site requirement with and including fixed on walls in CM 1:4 and making good the disturbed surfaces of walls match as per existing complete all as specified and directed. Make :-Legrand /Crabtree as per sample at site as approved by GE.
All as per item No.21 above but modular metal flush box of 3 module complete all as specified and directed.
All as per item No.21 above but modular metal flush box of 4 module complete all as specified and directed.
All as per item No.21 above but modular metal flush box of 6 module complete all as specified and directed.
All as per item No.21 above but modular metal flush box of 8 module complete all as specified and directed.
All as per item No.21 above but modular metal flush box of 12 module complete all as specified and directed.
Supply anf fix in replacement modular white cover plate with frame 1 module for mounting modular switches, sockets and regulators etc complete all as specified and directed. Make :- Legrand / Crabtree as per sample at site as approved by GE.
All as per item No.27 above but modular white cover plate with frame 2 module complete all as specified and directed.
All as per item No.27 above but modular white cover plate with frame 3 module complete all as specified and directed.
All as per item No.27 above but modular white cover plate with frame 4 module complete all as specified and directed.
All as per item No.27 above but modular white cover plate with frame 6 module complete all as specified and directed.
All as per item No.27 above but modular white cover plate with frame 8 module complete all as specified and directed.
All as per item No.27 above but modular white cover plate with frame 2 x 6 module complete all as specified and directed.
M&L for sub main wiring using two single core PVC insulated, unsheathed stranded copper conductor cable of size 10 Sqmm of voltage rating upto and including 1100 Volts drawn in and including concealed PVC conduit (Medium grade) of dia not less than 20 mm with standard accessories along-with one run of PVC(green colour) insulated , unsheathed, stranded copper conductor of size 10 Sqmm as earth continuity conductor connected to earth dolly complete all as specified and directed
M&L for sub main wiring using two single core PVC insulated, unsheathed stranded copper conductor cable of size 6 Sqmm of voltage rating upto and including 1100 Volts drawn in and including concealed PVC conduit (Medium grade) of dia not less than 20 mm with standard accessories along-with one run of PVC(green colour) insulated , unsheathed, stranded copper conductor of size 6 Sqmm as earth continuity conductor connected to earth dolly complete all as specified and directed.
M&L for sub main wiring using two single core PVC insulated, unsheathed stranded copper conductor cable of size 4 Sqmm of voltage rating upto and including 1100 Volts drawn in and including concealed PVC conduit (Medium grade) of dia not less than 20mm with standard accessories along-with one run of PVC(green colour) insulated , unsheathed, stranded copper conductor of size 4 Sqmm as earth continuity conductor connected to earth dolly complete all as specified and directed. Notes for item no 34 to 36 :- (i) Two run of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit. (ii) The quoted rates shall be deemed to be inclusive for cutting chases in brick walls/pillars etc. for concealing the conduits to required depth & making good the disturbed surface in cement sand mortar 1:4 including finishing the surface to match with the existing surface. The portion of sub main wiring at ceiling/RCC surfaces shall be in surface conduit of suitable size fixed on ceiling/RCC surfaces with using PVC rawl plugs)
Disconnecting and taking down old unserviceable distribution boards any size any type including MCB TPN/SPN/SP etc and making good the disturbed surfaces to the existing surfaces complete all as specified and directed.
Supply, fixing, connecting & testing factory made, epoxy powder coated, distribution board (sheet metal encloser) , triple pole and neutral, 4 ways, (Vertical DB's) ,with metal door and fixed flush to wall and suitable for universal mounting with having copper bus bars of capacity 200 Amps rating, of suitable size , for double door and suitable for using MCCB, 4 Pole as incomer and SP MCBs as out going, conforming to IS : 13032 complete all as specified & directed, ( Note: Switchgears shall be measured and paid for separately under appropriate item of Sch ‘A’.
Supply, fixing, connecting & testing factory made, epoxy powder coated, distribution board (sheet metal encloser) , singe pole and neutral, 8 ways, (Horizontal DB's) ,with metal door and fixed flush to wall and suitable for universal mounting with having copper bus bars of capacity 200 Amps rating, of suitable size , for double door and suitable for using MCB, SPN as incomer and MCBs SP as out going, conforming to IS : 13032 complete all as specified & directed, ( Note: MCBs shall be measured and paid for separately under appropriate item of Sch ‘A’.
Supplying & fixing MCCB 63 Amps, 4 pole, 415 volts, AC supply having ultimate breaking capacity Icu 16 KA and Ics= 100% of Icu with adjustable 70% to 100% and thermal magnetic release complete all as specified and directed.
Supplying & fixing MCB TPN, 63 Amps (`C’ series ) having breaking capacity 10 KA, 415 volt complete all as specified and directed.
Supplying & fixing MCB SPN, 32 Amps (`C’ series ) having breaking capacity 10 KA, 240 volt complete all as specified and directed.
Supplying & fixing MCB single pole, 2 Amps (`C’ series ) having short circuit rating10 KA, 240 volt complete all as specified and directed.
Supplying & fixing MCB single pole, 6 Amps (`C’ series ) having short circuit rating10 KA, 240 volt complete all as specified and directed.
Supplying & fixing MCB SP single pole, 16 Amps (`C’ series ) having short circuit rating10 KA, 240 volt complete all as specified and directed.
S&F in replacement LED battan surface / wall mounted with specially designed powder coated aluminum housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired upto terminal block, power consumption < 20W, luminaire lumens > 2000 lms, system efficiency of > 120 lumens / W, LED of make : Nichia / Cree / Everlite / Eclison / OSRAM / Lumiled, with LED binding as per ANSJ Bin C78377A, Ingress protection IP 20, colour rendering index CRI > 80, temp range 0 to 45 ºC, driver efficiency > 85%, power facor > 0.95 THD < 20% as per IEC 61000-3-2, colour temp - 6500 K Surge protection 2.5 KV, 50000 burning hrs (min) as per L 70 criteria, two stages isolated constant current operated driver with range 150 - 270 VAC and safety extra low voltage safe level < 60 VDC as per IEC standard with LM 70 & 80 certification complete all as specified Make :- Wipro Model No.LL20-281 - XXX-65AL1 or equivalent of philips / Balaj / Havells
S&F in replacement LED security with aluminium pressure die cast housing, high purity PC fresneldiffuser with silicon gaskets for IP-65 protection, power consumption <30 W and system efficiency > 100lm /W, in built electronic driver prewired upto terminal block with driver efficiency >85% power factor > 0.95, suitable for external pole upto 35mm LED Make :- Nichia / Cree / Osram, CRI > 70, ambient temperature range 0-450c, THD < 10% colour temperature 5700 K, surge protection cm 3.5 KV 50000 burning hour as per L70 criteria, multi stage constant current constant voltage operated driver with range 150-270 V AC and safety extra low voltage safe level <60V DC as per IEC standard including GI pipe medium grade ISI mark of size 32 mm dia length not less than 1.5 mtrs bending to shape for fixing light and nuts, bolts, clamp as required to fix to wall complete all as specified and directed. Cat part No.LR02-331-XXX-57-XX or equivalent of Philips / Bajaj.
Supplying & fixing in replacement 2 ft x 2 ft recess mounted full panel LED luminaire with white powder coated housing acting as heat sink andframe in CRCA sheet, high efficiency LED grade diffuser, in built electronic driver duly wired upto terminal block, power consumption < 36W, luminaire lumen > 3500 lm and system efficiency > 120 lm/w, CR> 80, LED make: Nichia/Cree/Osram/ Lumined with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class 1, colour temp - 5700k, ingress protection IP20, Driver efficiency > 85%, 50000 burning hours (min) as per L70 criteria, ambient temp 0 to 500C, power factor > 0.95 THD <10%, surge protection in CM-3KV, two stage isolated constant current operated driver with range 150-270V AC and safety extra low voltage safe level <60V DC as per IEC standard, with LM79 & LM 80 certification complete all as specified & directed. Cat part No : CRC010R038HP57GL1 of make Wipro or equivalent model of make Phillips/General Electric / Trilux as approved by GE.
Supply & fixing in replacement ultra 18 watt LED PL-L-4 pin high efficency suitable for installation in existing 2G 11 lamp holders complete all as specified and directed. Cat part No.PHOTONULTRAPLL419TL18WLED865SPC of make Havells or equivalent model in specified make as approved by GE.
Supply & fixing in replacement 8/9 watt Led PL-L-2 pin high efficency suitable for instalation in existing G24/G23 lamp holders complete all as specified & directed. Cat part No.SSK-PL-8w-N of make Syska or equivalent model in specified make as approved by GE.
Supplying, laying, jointing & testing in repairs XLPE insulated PVC sheathed (heavy duty) armoured cable with aluminium conductor for working voltage upto 1100 volts size 6 Sqmm 2 core conforming to IS 7098 Part-I or IS 1554 Part-I. complete all as specified and directed.
Supplying, laying, jointing & testing in repairs XLPE insulated PVC sheathed (heavy duty) armoured cable with aluminium conductor for working voltage upto 1100 volts size 10 Sqmm 2 core conforming to IS 7098 Part-I or IS 1554 Part-I. complete all as specified and directed.
Excavation in trenches in soft / loose soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. including removing of cable, protection covers/ bricks complete all as specified and directed Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and protection cover/Bricks . (ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations
Returning, filling in excavated soil including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed and tested complete all as specified and directed .
Removal of surplus excavated soils to a distance not exceeding 50 M and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
M&L for old size sub class `B` bricks, kiln burnt, as in cable protection laid flat with axis of brick perpendicular to the axis of the cable complete all as specified and directed .
Material & labour for sand filling with clean dry find sand unwashed including gently punning around under ground cables in trenches/ducts for cable protection with layers of sand ( 8 cm deep before laying cable and 15 cm after laying cable ) complete all as specified and directed at site.
Supply & fix in replacement New generation, post-top, IP 65 protection, energy saving envirmental friendly long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source for 35 watt LED luminaire with and including internally prewired, reflector cover, electronic driver, connector block, and all accessories and connecting the same to electric source with & including twin twisted copper flexible wire of size 0.75 Sqmm , with all accessories for fixing arrangements suitable for fixing of light fitting on 76mm dia pole on gate pillar complete all as specified & directed. Cat part No: RUBYPT35WLED757PSYMTOPC model RUBY(CLEAR) of make Havells or equivalent model of make Philips / Bajaj / Crompton Greaves as approved by GE.
S&F in replacement rugged LED midbay / highway LEDlight fittings of capacity 100 watts, 13000 lm with black colour, powder coated aluminium heat sink for efficient heat dissipation and high purity anodized reflector with electro chemically anodized matt finish inside, the effective glass optics for maximum illumination radious of aluminium reflector not less than 240 mm dia outer peripherals. Driver and accessories prewired power consumption less than 100 w, with luminaire lumen 13000 lm, colour temperature not less than 6600 k, ingress protection IP-65 ten high lumen output minimum 130 lm / watts complete all as specified and directed up to hanger height of 11 meter. Cat part No.LH09-132-060-50-V6 of make Wipro or equvialent model in specified make as approved by GE
S&F in replacement rugged LED midbay / highway LED light fittings of capacity 65 watts, powder coated aluminium heat sink for efficient heat dissipation and high purity anodized reflector with electro chemically anodized matt finish inside, the effective glass optics for maximum illumination radious of aluminium reflector not less than 240 mm dia outer peripherals. Driver and accessories prewired power consumption less than 65 w, with luminaire lumen >8000 lm, colour temperature not less than 6600 k, ingress protection IP-65 teh high lumen output minimum 130 lm / watts complete all as specified and directed up to hanger height of 11 meter. Cat part No.LH09-851-060-50-V6 of make Wipro or equvialent model in specified make as approved by GE. Note for item No 59 and 60 :- The specialised ladder having requirment up 11 meter hanger height shall be arranged by the contractor without any extra cost from the department.
S&F in replacement of Air termination, single pointed rod 25 mm dia and 1800 mm long of GI on Hanger at height upto 11 mtr complete all as specified and directed.
S&F in replacement of GI strip 32 x 6 mm with saddles porcelain insulators and fixing screws etc on roof / wall and connecting from earth pit the lightning rods point on hanger at height upto 11 mtr etc complete all as specified and directed.
S&F in replacement test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25 mm, drilled screwed including 3 Nos, 8 mm dia, 25 mm long complete all as specified and directed.
S&F in replacement aluminium strip 25 x 3 mm with saddle porcelain insulator and fixing screws etc on roof / wall and connecting from earth pit the lightning rods point on hanger at height upto 11 mtr etc complete all as specified and directed.
Taking down aluminium GI strip any type & any size complete & refixing the same aluminium / GI strip on same location with saddles & insulators, screws etc for roof conductors and down conductors on hanger at height upto 11 mtr complete all as specified and directed. Note for item No.61 to 65 :- The specialized ladder having requirement upto 11.0 mtr hanger height shall be arranged by contractor without any extra cost.
M&L for earthing complete with galvanized earth plate electrode 600 x 600 x 3.15mm thick burried directly in ground vertically to a depth not less than 3.00 M below normal ground level ) with top edge of the plate not less than 2.25 M below normal ground level connected to and including galvanized steel Strip of size 25 x 4 mm as earth lead soldered and riveted to earth plate by means of nuts, bolts, check nuts & washers, of galvanized iron or steel with connected to pole test point and testing on completion including 40 mm GI light grade pipe for earth lead protection from earth point to earth plate, including provn adequate quantity of charcoal dust mixed with 35 % common salt to a packed thickness of not less than 15 cm in alternate layers of charcoal and salt on all sides of earth plate with 20mm bore medium grade GI Pipe for watering,GI check nut, funnel and wire mesh with and including all necessary excavation & earth work in any type of soil, returning filling in, removal of surplus soil to a distance 50 metre,,PCC 1:2:3 type C-1 as in earth pit, 40 mm thick RCC cover using cement concrete 1:2:4 type B-0 reinforced with & including 6 mm dia mild steel TMT bar @ 75 mm c/c Both way with suitable handle for lifting arrangement & including form work complete all as specified and shown in electrical plate No 3 of MES SSR Part I 2009 and as directed. NOTES:- (i) On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone at without any extra cost by contractor. (ii) GI strip and protection light grade GI pipe (50 ECC grade) upto 7.5 mtr shall be deemed to be in the rates.
M&L for earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit / pipe or fixedto poles or any other indicated situation for loop earthing etc as required of size 25 x 4 mm galvanized iron or steel strip complete all as specified and directed.
Supplying and fixing of GI tubing, 40 mm bore, light grade as in sleeving/protection of cable etc laid in trenches/floor or fixed on pole / wall etc. with and including suitable size of MS clamp and nut, bolt ,washer etc complete all as specified and directed
Shiva Enterprises
M/S OMKAR SINGH YADAV
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .