Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.4 CrAccepted-Finance | ₹17.4 Cr | L1 | Accepted-Finance Accepted |
| 2 | Not Admitted-Finance | - | - | Not Admitted-Finance Others-Bid quoted at L2 position. |
| 3 | Not Admitted-Fee/PreQual/Technical PLOT NO 15 VASUDEV HARI NIVAS DATTATRAY NAGAR BADA BAZAAR TUMSAR TH TUMSAR DIST BHANDRA MAHARASHTRA 441912 | BHANDARA | MAHARASHTRA | 441912 | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 4 | Not Admitted-Fee/PreQual/Technical A 710 NEAR RAMNATH SOLAR BUS STOP TTC INDL AREA MIDC MAHAPE NAVI MUMBAI THANE MAHARASHTRA 400710 UDYAM MH 33 0033944 | THANE | MAHARASHTRA | 400710 | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹17.4 Cr
Closing Date
25 Sept 2024, 4:00 pmClosed
The Secretary (1) (I/C)
Maharashtra Legislature Secretariat, Vidhan Bhavan, Mumbai 32.
Various building protection systems of MEP as per Tender Document
2024_MLS_1087761_1
144/G-2/2024-25
Open Tender
Electrical Works
180 days
Vidhan Bhavan
Please refer Tender documents.
2 documents required · 2 mandatory
₹10,000
23/09/2024
1 Oct 2024
19 Sept 2024
26 Sept 2024
19 Sept 2024
25 Sept 2024
19 Sept 2024
23 Sept 2024
Amount
A. FIRE PUMP ROOM SYSTEM - TOWER AND DOME BUILDING Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. a. 300 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. b. 200 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. c. 150 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. d. 100 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. e. 80 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. f. 50 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. g. 32 mm dia
Painting for heavy "C" class M.S pipe confirming to IS 3589 & IS 1239 in all size.
Pipe Fittings - MS fittings Such as Elbows (Bends), Flanges, Reducers, sockets, 'U' bolts, Chilly Supports, Rods, Clamps, Gaskets, Nut-bolts, Supporting Material, Fastner etc in various sizes. (Note:- 'Aprox. 35% of the cost of Pipe above)
Supplying & Installation of Electric motor driven Multistage fire pumping set suitable for automatic operation consisting as per the below specification & TEFC specification. (a) Vertical / Horizontal side suction / high pressure, centrifugal pump suitable for operation on 415 volts ± 10%, 3 phase, 50 HZ A.C supply. The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and SS-410/431 Shaft with gland type stuffing box. (b) Squirel cage induction motor totally enclosed fan cooled type suitable for 415 Volt (+,- 10%) 3 Phase 50 Hz AC supply of suitable capacity for the above pump with Synchronous speed of 1500 rpm confirming to conforming to IP 55 protection & class F insulation, confirming to IS:325 with flexible coupling and coupling guard, complete as required. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side etc. (c) Common base plate for mounting pump and motor fabricated of suitable MS channel and Coupling guard etc. (d) Suitable RCC pump foundations as per manufacturer's design and Antivibration heavy duty mounting pads with vibration eliminators of approved make. 2850 LPM at Low Head 80 MWC & High Head 120 MWC (Hydrant & Sprinkler Main Pump - 150 HP)
Supplying & Installation Diesel Engine driven Multistage (stand by) fire pumping set suitable for automatic operation and shall be complete with all accessories. (a) The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and SS (304) shaft with mechanical seal. (b) Water cooled, high speed Diesel Engine of suitable B.H.P. running at 1485 RPM . speed including fuel, day oil tank, 12 volts battery with leads, exhaust pipe. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side etc. (c) Common base plate for mounting pump and motor fabricated of suitable MS channel and Coupling guard etc. (d) Suitable RCC pump foundations as per manufacturer's design and Antivibration heavy duty mounting pads with vibration eliminators of approved make. 2850 LPM at Low Head 80 MWC & High Head 120 MWC (Deisel Engine - Standby Pump - 167 BHP)
Supplying & Installation of Vertical / Horizontal centrifugal pump, suitable for operation on 415 volts ± 10%, 3 phase, 50 HP A.C supply. The installation shall be complete with coupling and coupling guard, fire pumps of capacity of 3 LPS/180 M3 / HR at 130 M Head with suitable capacity Motor. (b) Squirrel cage induction motor TEFC type for operation on 415 V, 3 phase 50 HZ AC supply for the above pump with a synchronous speed of 2900 RPM With coupling and coupling guard etc. as required. (c)Common base plate for mounting pump and motor fabricated of suitable MS channel and Coupling guard etc. (d) Suitable RCC pump foundations as per manufacturer's design and Antivibration heavy duty mounting pads with vibration eliminators of approved make.
Supplying & Installation of Rubber Bellow for MSMO Pumps - 150 mm dia.
Supplying & Installation of Rebber Bellow for MSMO Pumps - 80/100 mm dia.
Supplying & Installation of of air vessel (Size 200/300 mm dia & 1000 mm height) fabricated shell from 8 mm thick & dished end 6/8 mm thick M.S. Plate for pressurization of system complete as required.
Supplying & Installation of C.I. 'Y' type strainer including required fitting etc. complete. A. 200 mm dia
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. a. 200 mm dia
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. b. 150 mm dia
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. C. 100 mm dia
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. D. 80 mm dia
Supplying & Installation of Heavy CI Ball type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 200 mm dia
Supplying & Installation of Heavy CI Ball type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. B. 150 mm dia
Supplying & Installation of Heavy CI Ball type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. C. 100 mm dia
Supplying & Installation of Heavy CI Ball type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. D. 80 mm dia
Supplying & Installation of CI Butterfly Valve as per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of CI Butterfly Valve as per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. B .100 mm dia
Supplying & Installation of CI Butterfly Valve as per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. C. 80 mm dia
Supplying & Installation of dial type Pressure Gauge with Isolation cock within Pump Room.
Supplying & Installation of Pressure Switch within Pump Room.
Supplying & Installation of 1.1 KV grade. ISI mark PVC insulated & PVC sheathed aluminium conductor, armoured/ flexible cables of following sizes for the Hydrant Main, Sprinkler Main, Standby, Jockey Pump & Pressure Switch. a. From Main Pumps to Panel (Aluminium Armd) 95 sq. mm X 3.5 C
Supplying & Installation of 1.1 KV grade. ISI mark PVC insulated & PVC sheathed aluminium conductor, armoured/ flexible cables of following sizes for the Hydrant Main, Sprinkler Main, Standby, Jockey Pump & Pressure Switch. b. From Jockey Pumps to Panel (Aluminium Armd) 2.5 sq. mm X 3C
Supplying & Installation of 1.1 KV grade. ISI mark PVC insulated & PVC sheathed aluminium conductor, armoured/ flexible cables of following sizes for the Hydrant Main, Sprinkler Main, Standby, Jockey Pump & Pressure Switch. c. From Pressure Switch to Panel (Aluminium Armd) 1.5 sq. mm X 2C
Supplying & Installation of 1.1 KV grade. ISI mark PVC insulated & PVC sheathed aluminium conductor, armoured/ flexible cables of following sizes for the Hydrant Main, Sprinkler Main, Standby, Jockey Pump & Pressure Switch. d. 400X50, 100X50, 50X50 GI Cable Tray with Cover, Gland Lugs & Earting Patti
Supplying & Installation of Automatic activation Tube base Fire Extinguisher ideal for closed compartment like generators sets, control panels, server cabinets, electrical distribution boards, inverter cabinets, etc.
Supplying & Installation of M.S. structural work fabricated from standard sections (MS rounds, angles, channels etc.) including cutting to size, drilling, welding, including cost of fasteners, U clamps (Heavy Quality) in RCC structural members as directed, including two coats of synthetic paint over one coat of primer etc complete. ( for Pipe Support).
Removing, lifting & Stacking of existing Fire Pump Room System as directed by fire consultant & with help of crane & other required machninary, manpower, tools & tackles etc for complete job.
Excavation in all type of strata at required depth as per dwg & RCC Concrete foundation(M25) along with foundation bolt, levelling the existing pump room floor in M15 grade PCC, dismantling the existing foundation with help tools & tackle (not hammering) , removing the debris out side the work area as directed by fire consultant for all pump sets.
B. COURTYARD FIRE HYDRANT SYSTEM - TOWER AND DOME BUILDING Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. A. 200 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. B. 150 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. C. 100 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. D. 80 mm dia
Painting for heavy "C" class M.S pipe confirming to IS 3589 & IS 1239 in all size.
Pipe Fittings - MS fittings Such as Elbows (Bends), Flanges, Reducers, sockets, 'U' bolts, Chilly Supports, Rods, Clamps, Gaskets, Nut-bolts, Supporting Material, Fastner etc in various sizes. ('Aprox. 35% of the cost of Pipe above)
Supplying & Installation of 4 mm tickness anticorrosive material (rapping coating) with bitumen primer.
Supplying & Installation of SS Courtyard Single Headed Fire Hydrant Valve 63 mm dia as per IS:5290 oblique type (ISI mark) female coupling with conplete fittings like flanges, gaskets, nuts and bolts, washers etc.
Supplying & Installation of SS Courtyard Double Headed Fire Hydrant Valve 63 mm dia as per IS:5290 oblique type (ISI mark) female coupling with conplete fittings like flanges, gaskets, nuts and bolts, washers etc.
Supplying & Installation of SUPER-JET WATER MONITOR – Stand post type : Monitor (waterways 63mm size) made out of C.S. (IS:11428 ) – Seamless pipe, hot dip galvanized, - 75mm N.B. flanged inlet, Flange Dimension: O.D. 200mm, PCD 160mm, four 19mdia holes - Gunmetal swivel joints & S.S ball bearing with brass locking arrangement, - Permitting of 360 degrees horizontal, 80 to -45 degrees vertical traverse, - 32mm bore Aluminum alloy Jet-Nozzle with female threaded inlet suitable for a discharge of 1750 LPM at 7kg/cm2 pressure, - Having Horizontal throw of 53mtr. at 30 deg. angle in still air condition, - bearing IS: 8442 mark.
Supplying & Installation of Canvas hose (ISI mark) 63 mm dia x 15 mtr. In length as per IS with SS M/ F coupling.
Supplying & Installation of SS short size branch pipe nozzle (ISI mark) of 63mm dia.
Supplying & Installation of Hose boxes fabricated from 16 SWG S.S. sheet size (450 X 450 X 200 mm) Single door, locking arrangements, 3/4 mm thick glasses red enamel paint over a coat of red oxide.
Supplying & Installation of Hose boxes fabricated from 16 SWG S.S. sheet size (650 X 450 X 200 mm) double door, locking arrangements, 3/4 mm thick glasses red enamel paint over a coat of red oxide.
Supplying & Installation of Fire Brigade 4-way inlet connection with 63 mm dia SS Male/Female Hydrant conection including all fittings.
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. a. 200 mm dia
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. b. 150 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of M.S. fabricated Stand Post with powder coated for Single Hose Box with necessary fittings
Supplying & Installation of M.S. fabricated Stand Post with powder coated for Double Hose Box with necessary fittings
Removing, lifting & Stacking of existing Courtyard Fire Hydrant System (including under ground pipeline & open pipe line at all level) as directed by fire consultant with help of required manpower , machinery, tools & tackles. including Refinishing the existing dismantlled surfaces like road, foothpath, parking area, landscape with same material. as well as any existing service line damaged during the work same also required to reparing with the same standard material.
Excavation, Backfilling , debries removal from work area, preparing Concrete Pedestal for proper fixing of pipe line & Refinishing the various surfaces with same finish as existing on site (like:- road, parking, foothpath, landscaping , compound wall, core cutting etc.) for installation of proposed Fire Hydrant Pipeline as directed by fire consultant.
C. BASEMENT FIRE SPRINKLER SYSTEM - TOWER AND DOME BUILDING Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. A. 150 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. B. 100 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. C. 80 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. D. 65 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. E. 50 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. F. 40 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. G. 32 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. G. 25 mm dia
Painting for heavy "C" class M.S pipe confirming to IS 3589 & IS 1239 in all size.
Pipe Fittings - MS fittings Such as Elbows (Bends), Flanges, Reducers, sockets, 'U' bolts, Chilly Supports, Rods, Clamps, Gaskets, Nut-bolts, Supporting Material, Fastner etc in various sizes. ('Aprox. 35% of the cost of Pipe above)
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. B. 100 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. C. 80 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. D. 50 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. E. 40 mm dia
Supplying & Installation of GM Drain Valve of 32 mm dia for drain of system.
Supplying & Installation of 15mm SS sprinkler head with quartzoid bulb operate at 68 degree temperature. UL/FM approved complete with socket nipple etc and sprinkler plate based on requirement. A. Pendent / Upright type - 68 degree
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. A. 1000 mm in length
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. B. 1200 mm in length
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. C.1500 mm in length
Supplying & Installation of hard points in MS piping of the required length as per site condition inplace of flexible connectiors wherever it is not possible to install flexible hose.
Supplying & Installation of Alarm Valve, Model H, Size – 150NB, with Constant Pressure Trim along with Gong Bell.
Supplying & Installation of Air release Valve with ball vlave of 25 mm dia for the vertical riser.
Supplying & Installation of 4 mm tickness anticorrosive material (rapping coating) with bitumen primer.
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Removing & Stacking of existing Basement Fire Sprinkler System including all require manpower, equipments, tools & tackles for removing the system as directed by fire consultant
Core cutting & Scaffolding for installation of proposed Basement Fire Sprinkler System as directed by fire consultant
D. FIRE EXTINGUISHERS - TOWER AND DOME BUILDING BASEMENT Supplying & Installation of ABC type fire extinguisher 4 kg capacity, discharge valve, pressure indiating gauge with discharge tube, ISI marked, pressurized with Nitrogen Gas.
Supplying & Installation of ABC type fire extinguisher 6 kg capacity, discharge valve, pressure indiating gauge with discharge tube, ISI marked, pressurized with Nitrogen Gas.
Supplying & Installation of Carbon-di-oxide fire extinguishers of 3 Kg. Capacity consisting of welded M.S cylinderical body, discharge valve, discharge hose, bracket, IS:934.
Supplying & Installation of Carbon-di-oxide fire extinguishers of 4.5 Kg. Capacity consisting of welded M.S cylinderical body, discharge valve, discharge hose, bracket, IS:934.
Supplying & Installation of fire Bucket set (4 bucket with stand).
E. FIRE SIGNAGES - - TOWER AND DOME BUILDING BASEMENT Supplying & Installation of Fire Signages as per fire norms & as directed by fire consultant.
F. INTERNAL FIRE HYDRANT RISER SYSTEM - TOWER BUILDING Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. A. 150 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. B. 100 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. C. 80 mm dia
Painting for heavy "C" class M.S pipe confirming to IS 3589 & IS 1239 in all size.
Pipe Fittings - MS fittings Such as Elbows (Bends), Flanges, Reducers, sockets, 'U' bolts, Chilly Supports, Rods, Clamps, Gaskets, Nut-bolts, Supporting Material, Fastner etc in various sizes. ('Aprox. 35% of the cost of Pipe above)
Supplying & Installation of SS Landing Single Headed Fire Hydrant Valve 63 mm dia as per IS:5290 oblique type (ISI mark) female coupling with conplete fittings like flanges, gaskets, nuts and bolts, washers etc.
Supplying & Installation of Hose reel drums in yellow flurosent manufactured as per IS : 884 made from M.S. 18 SWG sheet and working parts and swinging design with 3/4" rubber hose reel of 30 mtrs. & shut off nozzle with GM Drain Valve of 20 mm Ø on the lower end of the Hose reel.
Supplying & Installation of Canvas hose (ISI mark) 63 mm dia x 15 mtr. In length as per IS with SS M/ F coupling.
Supplying & Installation of SS short size branch pipe nozzle (ISI mark) of 63mm dia.
Supplying & Installation of Hose boxes fabricated from 18 SWG M.S. sheet size (650 X 450 X 200 mm) double door, locking arrangements, 3/4 mm thick glasses red enamel paint over a coat of red oxide.
Supplying & Installation of Fire Brigade 2/3-way inlet connection with 63 mm Ø SS Male Hydrant conection including all fittings to Wet Riser cum Down comer.
Supplying & Installation of Air release Valve with ball vlave of 25 mm dia for the vertical riser.
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. B. 100 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. b. 100 mm dia
Supplying & Installation of Heavy CI Ball type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 100 mm dia
Supplying & Installation of Heavy CI Wafer type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 100 mm dia
Supplying & Installation of C.I. 'Y' type strainer including required fitting etc. complete. A. 100 mm dia
Supplying & Installation of Horizontal Monoblock cetrifugal booster pump having CI casing ,Shaft driven bysuitable HP 2900 rpm motor. A. 900 LPM at 72 MWC (Terrace Booster Pump : 30 HP)
Supplying & Installation of 1.1 KV grade. ISI mark PVC insulated & PVC sheathed aluminium conductor, armoured/ flexible cables of following sizes for the Terrace Booster Pump. A. 3C X 2.5 mm Sq.
Supplying & Installation of DOL Starter / Panel for Terrace Booster Pump.
Removing , lifiting, lowering down & Stacking of existing Internal Fire Hydrant Riser System including scaffolding , required manpower, machinery , tools & tackles etc completed as directed by fire consultant
Civil touchup work (like plastring, painting , refinishing the core cut ) including Core Cutting, scaffolding for proposed fire hydrant riser system as directed by fire consultant
G. INTERNAL FIRE SPRINKLER SYSTEM - TOWER BUILDING:- Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. A. 150 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. B. 100 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. C. 80 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. D. 65 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. E. 50 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. F. 40 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. G. 32 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. H. 25 mm dia
Painting for heavy "C" class M.S pipe confirming to IS 3589 & IS 1239 in all size.
Pipe Fittings - MS fittings Such as Elbows (Bends), Flanges, Reducers, sockets, 'U' bolts, Chilly Supports, Rods, Clamps, Gaskets, Nut-bolts, Supporting Material, Fastner etc in various sizes. ('Aprox. 35% of the cost of Pipe above)
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. B. 100 mm dia
Supplying & Installation of GM Drain Valve of 32 mm dia for drain of system.
Supplying & Installation of 15mm SS sprinkler head with quartzoid bulb operate at 68 degree temperature. UL/FM approved complete with socket nipple etc and sprinkler plate based on requirement. A. Pendent type - 68 degree
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. A. 1000 mm in length
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. B. 1200 mm in length
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. C. 1500 mm in length
Supplying & Installation of hard points in MS piping of the required length as per site condition inplace of flexible connectiors wherever it is not possible to install flexible hose.
Supplying & Installation of Alarm Valve, Model H, Size – 150NB, with Constant Pressure Trim along with Gong Bell.
Supplying & Installation of Air release Valve with ball vlave of 25 mm dia for the vertical riser.
Supplying & Installation of 4 mm tickness anticorrosive material (rapping coating) with bitumen primer.
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Civil touchup work (like plastring, painting, gypsum false ceiling, refinishing the core cut ) including Core Cutting, scaffolding for proposed sprinkler system of tower building as directed by fire consultant
H. FIRE EXTINGUISHERS - TOWER BUILDING Supplying & Installation of ABC type fire extinguisher 6 kg capacity, discharge valve, pressure indiating gauge with discharge tube, ISI marked, pressurized with Nitrogen Gas.
Supplying & Installation of Carbon-di-oxide fire extinguishers of 4.5 Kg. Capacity consisting of welded M.S cylinderical body, discharge valve, discharge hose, bracket, IS:934.
I. FIRE SIGNAGES - TOWER BUILDING Supplying & Installation of Fire Signages as per fire norms & as directed by fire consultant.
J. INTERNAL FIRE HYDRANT RISER SYSTEM - DOME BUILDING Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. A. 150 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. B. 100 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. C. 80 mm dia
Painting for heavy "C" class M.S pipe confirming to IS 3589 & IS 1239 in all size.
Pipe Fittings - MS fittings Such as Elbows (Bends), Flanges, Reducers, sockets, 'U' bolts, Chilly Supports, Rods, Clamps, Gaskets, Nut-bolts, Supporting Material, Fastner etc in various sizes. ('Aprox. 35% of the cost of Pipe above)
Supplying & Installation of SS Landing Single Headed Fire Hydrant Valve 63 mm dia as per IS:5290 oblique type (ISI mark) female coupling with conplete fittings like flanges, gaskets, nuts and bolts, washers etc.
Supplying & Installation of Hose reel drums in yellow flurosent manufactured as per IS : 884 made from M.S. 18 SWG sheet and working parts and swinging design with 3/4" rubber hose of 20 or 30 mtrs. & shut off nozzle with GM Drain Valve of 20 mm Ø on the lower end of the Hose reel.
Supplying & Installation of Canvas hose (ISI mark) 63 mm dia x 15 mtr. In length as per IS with SS M/ F coupling.
Supplying & Installation of SS short size branch pipe nozzle (ISI mark) of 63mm dia.
Supplying & Installation of Hose boxes fabricated from 18 SWG M.S. sheet size (650 X 450 X 200 mm) double door, locking arrangements, 3/4 mm thick glasses red enamel paint over a coat of red oxide.
Supplying & Installation of Fire Brigade 2/3-way inlet connection with 63 mm Ø SS Male Hydrant conection including all fittings to Wet Riser cum Down comer.
Supplying & Installation of Air release Valve with ball vlave of 25 mm dia for the vertical riser.
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. B. 100 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 100 mm dia
Supplying & Installation of Heavy CI Ball type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 100 mm dia
Supplying & Installation of Heavy CI Wafer type NRV as per IS including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 100 mm dia
Supplying & Installation of C.I. 'Y' type strainer including required fitting etc. complete. A. 100 mm dia
Supplying & Installation of Horizontal Monoblock cetrifugal booster pump having CI casing ,Shaft driven bysuitable HP 2900 rpm motor. A. 900 LPM at 72 MWC (Terrace Booster Pump : 30 HP)
Supplying & Installation of 1.1 KV grade. ISI mark PVC insulated & PVC sheathed aluminium conductor, armoured/ flexible cables of following sizes for the Terrace Booster Pump. A. 3C X 2.5 mm Sq.
Supplying & Installation of DOL Starter / Panel for Terrace Booster Pump.
Removing , lifiting, lowering down & Stacking of existing Internal Fire Hydrant Riser System including scaffolding , required manpower, machinery , tools & tackles etc completed as directed by fire consultant
Civil touchup work (like plastring, painting , refinishing the core cut ) including Core Cutting, scaffolding for proposed fire hydrant riser system as directed by fire consultant
K. INTERNAL FIRE SPRINKLER SYSTEM - DOME BUILDING Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. A. 150 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. B. 100 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. C. 80 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. D. 65 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. E. 50 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. F. 40 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. G. 32 mm dia
Supplying & Installation in position heavy "C" class M.S pipe confirming to IS 3589 for size above 150mm and IS 1239 upto size 150mm. H. 25 mm dia
Painting for heavy "C" class M.S pipe confirming to IS 3589 & IS 1239 in all size.
Pipe Fittings - MS fittings Such as Elbows (Bends), Flanges, Reducers, sockets, 'U' bolts, Chilly Supports, Rods, Clamps, Gaskets, Nut-bolts, Supporting Material, Fastner etc in various sizes. Note:- Aprox. 35% of the cost of Pipe above
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. B. 100 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. C. 80 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. D. 50 mm dia
Supplying & Installation of CI Butterfly Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. E. 40 mm dia
Supplying & Installation of GM Drain Valve of 32 mm dia for drain of system.
Supplying & Installation of 15mm SS sprinkler head with quartzoid bulb operate at 68 degree temperature. UL/FM approved complete with socket nipple etc and sprinkler plate based on requirement. A. Pendent type - 68 degree
Supplying & Installation of 15mm SS sprinkler head with quartzoid bulb operate at 68 degree temperature. UL/FM approved complete with socket nipple etc and sprinkler plate based on requirement. B. Extended - Sidewall type - 68 degree
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. B. 1000 mm in length
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. B. 1200 mm in length
Supplying & Installation of SS Non braided flexible droper pipes for sprinkler connection. C. 1500 mm in length
Supplying & Installation of hard points in MS piping of the required length as per site condition inplace of flexible connectiors wherever it is not possible to install flexible hose.
Supplying & Installation of Alarm Valve, Model H, Size – 150NB, with Constant Pressure Trim along with Gong Bell.
Supplying & Installation of Air release Valve with ball vlave of 25 mm dia for the vertical riser.
Supplying & Installation of 4 mm tickness anticorrosive material (rapping coating) with bitumen primer.
Supplying & Installation of Sluice Valve a per IS : 13095 including necessory fittings like flanges, gaskets, nuts and bolts, washers etc. A. 150 mm dia
Civil touchup work (like plastring, painting, gypsum false ceiling, refinishing the core cut ) including Core Cutting, scaffolding for proposed sprinkler system of dome building as directed by fire consultant
L. FIRE EXTINGUISHERS - DOME BUILDING Supplying & Installation of ABC type fire extinguisher 6 kg capacity, discharge valve, pressure indiating gauge with discharge tube, ISI marked, pressurized with Nitrogen Gas.
Supplying & Installation of Carbon-di-oxide fire extinguishers of 4.5 Kg. Capacity consisting of welded M.S cylinderical body, discharge valve, discharge hose, bracket, IS:934.
M. FIRE SIGNAGES - DOME BUILDING Supplying & Installation of Fire Signages as per norms & as directed by consultant.
N. FIRE ALARM SYSTEM - TOWER AND DOME BUILDING FIRE ALARM SYSTEM 'Fire Alarm Panel - 'SITC of Microprocessor based Intelligent Addressable Main Fire Alarm Control Panel with 5 Loop modules and expandable upto 15 loop.Each Loop capable of supporting not less than 250 devices (detectors & modules should be in any combination) ; Loop length up to 1.5 km, 8" Color LCD touch screen display with bright colors to indicate alarms and events, 4 Nos of Integrated Ethernet Ports & 2 Nos of RS 485 for networking, 200 Nos of Soft programmable keys with status indicators for individual triggering of NAC Ouputs, evacuation speaker zones, AHU Modules, Damper switch, Smoke extraction Fans, Lifts.. etc. The FACP shall have the option of Redundancy in the Controller Level & Loop level. The Panel shall support 10000 history logs in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 24 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have seamless integration with EVAC certified Public Address System and shall be complete with all accessories. Panel should not required any specific licensing kit / Dongle / Activation kit.
Repeater Panel - SITC of Active Repeater panel to be connected peer to peer with Main Fire Alarm panel. Accept, Reset functions shall be possible from the repeater panel. The user interface of Repeater Panel shall be identical to the Fire alarm Panel. All other specification shall remain unchanged like FACP. (EN54 &Vds) / (UL&FM) Certification.
VFD Camera - SITC of Video Fire detection camera with inbuilt intelligent Video Analytics and shall detect flames and smoke within an incredibly short time span by analyzing video sequences. The video-based fire detection shall be capable of working under low-light (down to 0 lx with IR illuminator) and detects test fires like TF1, TF2 up to TF8. The camera should detect flame of width 1m at a disctance of 120m, and Smoke of width 1m at a disctance of 84m when set to angle of 45 degree, The VFD Camera shall provide a relay output to transmit alarm signals to fire alarm panel. The VFD should be Vds certified.
Multisensor Detector - SITC of addressable Multisensor detector with a combination of Optical and Thermal including mounting base, auto addressing feauture as required. Detetctor should have 2 inbuilt isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be (EN54 &Vds) / (UL&FM) Certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector).
Smoke Detector - SITC of addressable smoke detector including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be (EN54 &Vds) / (UL&FM) Certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector).
AFC Smoke Detector - SITC of Above Flase ceiling addressable smoke detector with responce indication including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be (EN54 &Vds) / (UL&FM) Certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector).
Heat Detector - SITC of addressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005.Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector).
Beam Detector - SITC of Linear beam detector, 100 mtrs range, Auto-Alignment with motorized detector head, Light Cancellation Technology, Laser assisted alignment, Compensates for natural shifts in alignment from building movement, Contamination Compensation, Optical wavelength - smoke detection: 850nm near infrared (invisible), Integrated laser - laser alignment: 650nm visible. Class IIIa <5mW.
Response Indicator - SITC of Response Indicator with matching screws complete with GI Junction box, Cable lugs at cable end and ferruling.
Manual Call Point - SITC of addessable manual break glass unit ( Double action) with inbuilt isolators as per NFPA 72 style 7 wiring requirements, with flexible network structures & necessary fixing arrangements with key complete as required. Shall be EN 54 / Vds/UL Certification.
Control Relay Module - SITC of Addressable Control Relay Module with inbuilt isolators as per NFPA 72 style 7 wiring requirements & with flexible network structures with a maximun switching current of 1A @ 30V DC. Shall be EN54/ Vds Certification/UL.
Monitor Module - SITC of Addressable Module with one input & one output contacts, with inbuilt isolators & with 2 monitoring features, monitoring of a line with EOL resistor ,Potential free contact monitoring. Shall be EN54 / Vds/UL Certification.
GUI Software - SITC of Fire Command Station including Graphical User Interface Software. The GUI based main network software shall be capable of graphically representing each node being monitored with floor plans and icons depicting the actual locations of the various systems; and / or sensors’ locations. The GUI software shall be located in control room and shall monitor all the blocks panel connected with each other. The software shall provide the facility to Monitor over Fire Network along with the Fire detection signal. The Graphic workstation shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation (failure of any CPU shall not result in failure of Graphic Workstation).
PC Workstation - SITC of core i7 computer, 16 GB RAM, 10TB HD, HDMI output, Gigabit Network card, Microsoft Windows 10/11 Professional (64 bit).
55 inch Display - SITC of 55 inch TV monitor, HD LED display, HDMI, Wall mount, Full HD.
8 Port POE Switch - SITC of 8 port PoE switch with 2 uplink / downlink port.
Media Convertor - SITC of OFC to Cu media convertor, 1Gbps support.
Pigtail - SITC of pigtails for OFC splicing including splicing.
4 U Network Rack - SITC of wall mount 4U network rack with power trip and ventilation fans.
OFC Cable 4C, Ar - SITC of 4 core armoured single mode Optical fibre cable.
Cat 6 Cable - SITC of CAT 6 cable.
25 mm Conduit - SITC of 25mm PVC conduits with all mounting accessories.
HDMI Cable - SITC of 5 mtr HDMI cable
FAS Cable - SITC of 2 c 2.5 SQ.MM Cu arm Cable for communication.
FIRE FIGHTER TELEPHONE TALK BACK SYSTEM System Interface Module - SITC of Fire Fighter's Telephone Panel for two way communication between Remote Fire Fighter & Fire Command Center, supporting upto 32 audio zones, Seamless Integration with fire alarm panel, Power Status, Troubles, Faults monitoring, CE Certified.
Addressable telephone jack - SITC of Addressable Fire Fighter's Telephone Jack for two way communication between Remote Fire Fighter & Fire Command Center, Noise Filter Circuit, CE Certified.
FFT handset - SITC of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center, High impact Plastic , RED in Color, CE Certified.
Handset Storage Cabinet - SITC of Handset storage cabinet, storage capacity upto 5 handsets, Red colour, powder coated, surface or flush mount.
FFT Cable - SITC of 2 c 2.5 SQ.MM Cu arm Cable for cummunication.
FIRE INTEGRATED PUBLIC ADDRESS SYSTEM PA Controller - SITC of 19" Rack Mountable 12 Zones Switcher Console With 8 I/O , . This Unit Can Play, Stop And Play Again Announcement Automatically Across The Each Zone According To The Program Settings For Systematic Evacuation Capable Of Connecting Booster Amplifier. (With All Required Accessories, Equipment’s Required For Connection & Smooth Functioning Of The System Whether It Is Mentioned Or Not) along with suitable call station for 12 zone
PA Router - SITC of 24 zones router, supporting upto 4000W speaker load and 500 W per zone max. 2 control relays, integrable upto 20 routers, Zone status indicator light,
500 X 2 (1000W) watt Booster Amplifier - SITC of 1000 W, total output power at 70.7 Vrms Amplifier with The amplifiers shall be placed in the field on different designated floors with all accessories like cabinet etc required to complete the installation.
6W Ceiling Speakers - SITC of 6W Multi-Tap, Ceiling Mount Speakers. The speakers shall be of same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms.
15W Box Speakers - SITC of 15W Multi-Tap, wall mount Box Speakers. The speakers shall be of same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms.
Call Station - SITC of Call station with soft touch button, 15 freely programmable buttons, Customization via built-in display and keys, Provision for installing emergency button and key switch, EN 54-16 system certification.
24 U Rack - SITC of floor mount 24 U network rack with accessories, power strip, ventilation fans and mounting accessories.
12 U Rack - SITC of wall mount 12 U network rack with accessories, power strip, ventilation fans and mounting accessories.
PA Cable - SITC of 2c x 40/002 mm twin twisted cables multi- standerd shielded insulated straight FRLS armoured cable ( for 12 w speaker ,booster amplifier to centeral mixer amplifier and call center )
Removing, lowering down & Stacking of existing Fire Alarm System of tower & dome building as directed by fire consultant
O. SERVER ROOM PROTECTION SYSTEM 'GAS BASED FIRE SUPPRESSION SYSTEM 80 Ltrs Cylinder - 80ltrs Cylinder with valve & Warning Sign Boards, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised ro 42 bars, Gas rates to be quoted separately, Cylinder to be PESO approved for HUB room.
120 Ltrs Cylinder - 120ltrs Cylinder with valve & Warning Sign Boards, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised ro 42 bars, Gas rates to be quoted separately, Cylinder to be PESO approved for HUB room.
Master Cylinder Accessories - Master Cylinder Accessories Comprising Below items for 120ltrs Cylinder * Pr Gauge + Low Pr Supervisory switch * Electromagnetic Actuator * Pneumatic Actuator * flexible Discharge Hose * Flexible Discharge hose * Manual Pneumatic Actuator * Union 7/16 JIC 1/8
Piping - Supply, Installation, Testing & Commissioning of piping , fittings & supports ,etc ASTM grade A Sch 40 as per the technical specifications with all accessories as required. The cost should consider based on Volume requirements. ISI Mark
Novec 1230 gas - NOVEC 1230 Fire protection fluid, OEM factory fill in Kgs stored in above cylinders @ 25 / 42 bar.
Nozzels - Nozzels.
Gas release panel - "Supply installation Testing & commissioning of 2 zone Gas Release Panel facility to connect Manual Abort / Release switches. The panel shall provide Potential free contacts for first knock, second knock, Trouble / Fault status UL approved. The panel shall be complete with Red Colour housing , Power supply unit , Battery charger & batteries.
Manaul release & abort stations - Manaul release & abort stations along with back box & necessary glass on top with acrylic box.
Integrity test - Room Integrity test for Agent protected room
ANALOGUE WATER LEAK DETECTION SYSTEM WLD panel - Design , Supply , Installation , Testing & Commissioning of Microprocessor based LCD Display control panel
WLD cable - 15 Mtr Length
Panel Interface Module
Clips - Hold down clips with adhesive to fix sensing cable length to be used at corner or every 1 mtr - 100/pck with adhesive
Hooter - Hooter for WLD
Cable - 2 C X 1.5 sq.mm Copper Armoured Cable, PVC insulated , PVC Sheathed layer with Single compression cable Glans, ABS junction Boxes(wherever required), terminals, Ferruling complete.
RODENT REPELLENT SYSTEMS RRS panel - Supply, Installation, Testing and commissioning of Rodent Controller Panel The Master Console shall be able tonic to the 24 Satellite in loops
RRS transducer - Supply, Installation, Testing and commissioning of Tranducer Satellite Stations ( 500 sq.ft )
Junction box - Supply installation of Floor / ceiling Mounted Powder Coated Junction Box complete with Glands and fitting accessories.
Cable - Installation of 14/40 SWG Specially Coated Single Pair armoured cable / Metal conduits.
VESDA SYSTEM VESDA detector - "Supply, Installation, Testing and Commissioning of Conventional Aspirating smoke detector for monitoring of rooms and equipment for earliest possible fire detection. with max of 8 aspiration openings and a max pipe length of 50mtr. Features: - Protected area of max. 400m² for one detector - Three status displays on housing front panel for ""operation"", ""alarm"" and ""malfunction"" - Aspirating Smoke Detectors have a response sensitivity of 0.5%/m to 2%/m light obscuration - Settable in day and night operation - Innovative air flow sensor technology - false alarm suppression - Monitoring of pipe for breakage and obstruction -False alarm suppression - Air stream monitoring with air pressure-dependent equalization FCS-320-TM FAS-420-TM-HB FAS-ASD-FL"
Marking tapes - Supply, installation, testing and commissioning of Marking tapes with Reduction foils as per the detailed specification. - TITANUS AF-BR TITANUS AF-3.2"
Hose and Ceiling Letthrough - Supply and Installation of Hose and Ceiling Letthrough for connecting the above and below false ceiling sampling Points FAS-ASD-AHC (1 No) FAS-ASD-CLT (10 Nos)"
Power supply - Supply and Installation of 24V DC, 2 Amps Power Supply Unit for the Aspiration Detector
Piping - Supply, installation, testing and commissioning of Aspiration Pipes as per the detailed specification for Aspiration Smoke Detection System
Hooter - Supply, Installation, Testing and commissioning of Electronic Hooter with Strobe
I&C - Supply, Installation, Testing and commissioning of Aspiration capillary tube including end caps for above units as per design calculations
FIRE SHAFT_ELECTRICAL SHAFT_FIRE DOOR FIRE SHAFT DOOR Supplying & Installation of FIRE SHAFT DOOR AND FRAME (2400 X 2400) (SINGLE SHEET -GI)FOUR DOOR DOOR- 1.2MM THICKNESS, GI SHEETS FRAME- 1.2MM THICKNESS, GI SHEETS HARDWARE INCLUDE :- PANEL LOCK-4,CONSEALED HANDLE-4, FASTNER-12Qty (8*60), PIN TYPE HINGES- 16, AND VISION GLASS – 300*600-5MM-4, INSTALLATION LOADING,UNLOADING
Supplying & Installation of FIRE SHAFT DOOR AND FRAME (1500 X 2100) (SINGLE SHEET -GI)DOUBLE DOOR DOOR- 1.2MM THICKNESS, GI SHEETS FRAME- 1.2MM THICKNESS, GI SHEETS, HARDWARE INCLUDE :- PANEL LOCK-2,CONSEALED HANDLE-2, FASTNER-8Qty (8*60), PIN TYPE HINGES-8, AND VISION GLASS – 300*600-5MM-2 INSTALLATION LOADING,UNLOADING
Removing , lowering down & Stacking of existing Fire Shaft Door as directed by fire consultant
Civil touchup Work (platering, painting, brickwork for making proper size of door frame) & Refinishing the surface for Fire Shaft Door as directed by fire consultant
ELECTRICAL SHAFT DOOR Supplying & Installation of ELECTRICAL SHAFT DOOR WITH FRAME (1500 X 2100) (SINGLE SHEET -GI) FOUR DOOR DOOR- 1.2 MM THICKNESS, GI SHEETS FRAME- 1.2 MM THICKNESS, GI SHEETS, PANEL LOCK -4, CONSEALED HANDLE-4, FASTNER-12Qty (8*60), PIN TYPE HINGES-16, INSTALLATION,LOADING&UNLOADING ALL INCLUDING
Supplying & Installation of ELECTRICAL SHAFT DOOR WITH FRAME (2400 X 2400) (SINGLE SHEET -GI) FOUR DOOR DOOR- 1.2 MM THICKNESS, GI SHEETS FRAME- 1.2 MM THICKNESS, GI SHEETS, HARDWARE :- PANEL LOCK -4, CONSEALED HANDLE-4, FASTNER-12Qty (8*60), PIN TYPE HINGES-16, INSTALLATION,LOADING&UNLOADING ALL INCLUDING
Remvoing, lowering down & Stacking of existing Electrical Shaft Door as directed by fire consultant
Civil touchup Work (platering, painting, brickwork for making proper size of door frame) & Refinishing the surface for Electrical Shaft Door as directed by fire consultant
FIRE DOOR Supplying & Installation of FIRE DOOR WITH FRAME – 1340 X 2120 MM SINGLE DOOR DOOR- 1 MM THICKNESS, GI SHEETS FRAME- 1.2 MM THICKNESS, GI SHEETS GI SHEET – THICKNESS – 46 MM HARDWARE :- 1. GARG HINGES – 100*75*3MM -2HRS FIRE RATED 2.FASTENER – 8*60 3.DOOR CLOSER – ASSA ABLOY -2HRS FIRE RATED 4.2HRS FIRE RATED GLASS – 300*300-6MM – 5.TRIM HANDLE – 6.PANIC BAR – 7.BUSH 8.NUTS 9.INSTALLING, LOADING & UNLOADING
Supplying & Installation of FIRE DOOR WITH FRAME – 2150 X 2140 MM DOUBLE DOOR DOOR- 1 MM THICKNESS, GI SHEETS FRAME- 1.2 MM THICKNESS, GI SHEETS GI SHEET – THICKNESS – 46 MM HARDWARE :- 1. GARG HINGES – 100*75*3MM -2HRS FIRE RATED 2.FASTENER – 8*60 3.DOOR CLOSER – ASSA ABLOY -2HRS FIRE RATED 4.2HRS FIRE RATED GLASS – 300*300-6MM – 5.TRIM HANDLE – 6.PANIC BAR – 7.BUSH 8.NUTS 9.INSTALLING, LOADING & UNLOADING
Supplying & Installation of FIRE DOOR WITH FRAME – 2740 X 2110 MM DOUBLE DOOR DOOR- 1 MM THICKNESS, GI SHEETS FRAME- 1.2 MM THICKNESS, GI SHEETS GI SHEET – THICKNESS – 46 MM HARDWARE :- 1. GARG HINGES – 100*75*3MM -2HRS FIRE RATED 2.FASTENER – 8*60 3.DOOR CLOSER – ASSA ABLOY -2HRS FIRE RATED 4.2HRS FIRE RATED GLASS – 300*300-6MM – 5.TRIM HANDLE – 6.PANIC BAR – 7.BUSH 8.NUTS 9.INSTALLING, LOADING & UNLOADING
Removing, lowering down & Stacking of existing Fire Door as directed by fire consultant
Civil touchup Work (platering, painting, brickwork for making proper size of door frame) & Refinishing the surface for Fire Door as directed by fire consultant
Q. AMC OF FIRE PROTECTION SYSTEM 1st year AMC - Comprehensive Cost for Annual Maintenance Contract for the period From 1st Jan-2026 to 31st Dec-2026.
2nd year AMC- Comprehensive Cost for Annual Maintenance Contract for the period From 1st Jan-2027 to 31st Dec-2027.
3rd year - Comprehensive Cost for Annual Maintenance Contract for the period From 1st Jan-2028 to 31st Dec-2028.
4th year - Comprehensive Cost for Annual Maintenance Contract for the period From 1st Jan-2029 to 31st Dec-2029.
5th year -Comprehensive Cost for Annual Maintenance Contract for the period From 1st Jan-2030 to 31st Dec-2030.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid