Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹24.9 LAccepted-AOC G 58 KIRAN GARDEN UTTAM NAGAR NEW DELHI 110059 | NEW DELHI | WEST DELHI | DELHI | 110059 | ₹24.9 L Quoted ₹25.9 L | 1 | Accepted-AOC LOWEST |
| 2 | 2₹30.8 L+₹4.9 L (18.9%)Rejected-Finance | ₹30.8 L+₹4.9 L (18.9%) | 2 | Rejected-Finance NOT LOWEST |
| 3 | 3₹33.5 L+₹7.5 L (29.0%)Rejected-Finance 9 8 B THENGUMTHARAVIL MLA ROAD PANANGAD PO KOCHI 682506 | KOCHI | ERNAKULAM | KERALA | 682506 | ₹33.5 L+₹7.5 L (29.0%) | 3 | Rejected-Finance NOT LOWEST |
| 4 | Rejected-Technical 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | - | - | Rejected-Technical NOT ENSLISTED IN APPROPRIATE CATEEGORY |
| Sl No | Description | Qty | Unit | T.I.John and Sons L3 | Sumit Enterprises L1 | YANSHIKA SECURITY SERVICES L2 |
|---|---|---|---|---|---|---|
| 1.00 | Comprehensive monthly maintenance of auto fire alarm system installed in BBJ Hanger & RSS Hangar and ISH in Tech Area at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Materials required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 Nos.
(b) UL Listed intelligent addressable multi-criteria detector with base- 284 Nos.
(c) UL Listed intelligent heat detector - 08 Nos.
(d) Manual call point - 08 Nos.
(e) Control module for hooter - 18 Nos.
(f) zone Monitor module - 28 Nos.
(g) Fault isolator - 12 Nos.
(h) Wall mounted hooter - 18 Nos.
(j) Response indicator - 25 Nos.
(k) IR Flame detector - 28 Nos.
(l) UPS 1 KVA - 02 No. | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 2.00 | Comprehensive monthly maintenance of auto fire alarm system installed in AW 101 Hanger No -I, II & III in Tech Area at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Materials required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No.
(b) UL Listed intelligent addressable multi-criteria detector with base- 192 Nos.
(c) UL Listed intelligent heat detector - 02 Nos.
(d) Manual call point - 18 Nos.
(e) Control module hooter - 05 Nos.
(f) Monitor module - 06 Nos.
(g) Fault isolator - 12 Nos.
(h) Wall mounted hooter - 06 Nos.
(j) Response indicator - 70 Nos.
(k) IR Flame detector - 44 Nos.
(l) UPS 1 KVA - 02 Nos. | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 3.00 | Comprehensive monthly maintenance of auto fire alarm system installed in SES LAB OF 181 FLIGHT, TWIN DSS BLDGS & CARGO TERMINAL in Tech Area at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Material required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No.
(b) UL Listed intelligent addressable multi-criteria detector with base- 59 Nos.
(c) Manual call point - 05 Nos.
(d) Control module for hooter - 05 Nos.
(e) Fault isolator - 04 Nos.
(f) Wall mounted hooter - 07 Nos.
(g) Response indicator - 07 Nos. | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 4.00 | Comprehensive monthly maintenance of auto fire alarm system installed in SIGNAL EXCHANGE BLDG IN Camp area & EDN SECTION in Camp Area at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Materials required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No.
(b) UL Listed intelligent addressable multi-criteria detector with base- 99 Nos.
(c) UL listed intelligent heat detector-02 Nos
(d) Manual call point - 08 Nos.
(e) Control module for hooter - 08 Nos.
(f) Monitor module- 09 Nos
(g) Fault isolator - 06 Nos.
(h) Wall mounted hooter - 08 Nos.
(j) Response indicator - 48 Nos. | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 5.00 | Comprehensive monthly maintenance of auto fire alarm system installed in 41 SQN Simulator Bldg in Tech Area at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Materials required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No.
(b) UL Listed intelligent addressable multi-criteria detector with base- 130 Nos.
(c) UL Listed intelligent heat detector - 04 Nos.
(d) Manual call point - 11 Nos.
(e) Control module for hooter - 06 Nos.
(f) Monitor module - 05 Nos.
(g) Fault isolator - 12 Nos.
(h) Wall mounted hooter - 20 Nos.
(j) Response indicator - 48 Nos.
(k) UPS 1 KVA -02 Nos. | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 6.00 | Comprehensive monthly maintenance of auto fire alarm system installed in AFCNWP CAMP AREA at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Materials required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 01 No.
(b) UL Listed intelligent addressable multi-criteria detector with base- 65 Nos.
(c) UL Listed intelligent heat detector - 06 Nos.
(d) Manual call point - 06 Nos.
(e) Control module for hooter - 06 Nos.
(f) Monitor module - 06 Nos.
(g) Fault isolator - 06 Nos.
(h) Wall mounted hooter - 06 Nos.
(j) Response indicator - 13 Nos. | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 7.00 | Comprehensive monthly maintenance of auto fire alarm system installed in SES SCTION OF CPRU, IT SEC, CFNL LAB IN TECH AREA at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basisof all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Materials required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 03 No.
(b) UL Listed intelligent addressable multi-criteria detector with base- 162 Nos.
(c ) UL listed intelligent heat detector - 02 Nos
(d) Manual call point - 14 Nos.
(e) Control module for Manual call point - 14 Nos.
(f) monitor module - 06 Nos.
(g) Fault isolator - 10 Nos.
(h) Wall mounted hooter - 14 Nos
(j) Response indicator - 72 Nos.
(k) sounder relay - 08 Nos.
(l) UPS 1 KVA - 03 Nos.
(m) central control including 21" colour monitor 21"and its CPU , Key board ,mouse & UPS -01 Set
(n) Repeater panel -01 No | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 8.00 | Comprehensive monthly maintenance of auto fire alarm system installed in ISR LAB,(T),73 RMU(T),WEATHER BUILDING (C), BBJMCF(T) IN TECH AREA at AF Stn Palam. The detail scope of work consists of the following:-
(i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Materials required for replacement will be measured and paid separately under respective items of this schedule.
Note:- The detail of fire equipments required repairs/maintenance are as under:-
(a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 03 No.
(b) UL Listed intelligent addressable multi-criteria detector with base- 102 Nos.
(c) Manual call point - 14 Nos.
(d) Control module for Manual call point - 20 Nos.
(e) monitor module - 06 Nos.
(f) Wall mounted hooter - 4 Nos
(g) sounder relay - 4 Nos.
(h) UPS 1 KVA - 04 Nos. | 11 | Each Month | 5,000 ₹55,000 | 1,900 ₹20,900 Lowest | 2,500 ₹27,500 |
| 9.00 | Supply, installation, testing and commissioning in replacement of Photo electronic type smoke cum heat detector IP67 rated, having removable high performance chamber with twin fire LED's allow 360 degree veiwing, lock mechanism (sensor to base), employ two heat sensing elements with different thermal characteristics to provide a rate of rise dependent response. Electronically addressed, approved by LPCB. Flat FAST addressing technique Flexible (programmed in any sequence), Automatic (stored in EEPROM). (EN-54 approved) conforming to IS-11360 -1985 having dual ionized chamber meant for easy detection of high carbonized fumes by means of light emitting principle complete with base, UL FM LPCB complete all as specified and as directed by Engineer in charge. Make: Ceasefire/siemens/honeybell/Dyagni | 250 | Each | 2,000 ₹5,00,000 | 1,350 ₹3,37,500 Lowest | 1,845 ₹4,61,250 |
| 10.00 | Supply only in replacement of addressable manual call point/pull station single action type with gold plated SPST contacts complete all as specified and directed by Engineer in Charge. Make: Siemens./Honeywell/ceasefire/Agnidy/Notefire | 30 | Each | 3,000 ₹90,000 | 1,300 ₹39,000 Lowest | 2,125 ₹63,750 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
6 Oct 2025, 6:00 pmClosed
GE (AF) PALAM DELHI CANTT 10
E (AF) PALAM DELHI CANTT 10
REPAIR / MAINT OF FIRE FIGHTING, FIRE ALARM AND FIRE DETECTION SYSTEM ALONGWITH CONNECTED WORKS UNDER GE (AF) PALAM, DELHI CANTT-10
2025_MES_729494_1
8025/A/T-52/E8
Open Tender
Civil Works
Item Rate
270 days
GE (AF) PALAM DELHI CANTT 10
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) PALAM DELHI CANTT 10
₹80,000
Yes
17 Dec 2025
4 Sept 2025
14 Oct 2025
4 Sept 2025
6 Oct 2025
22 Sept 2025
Amount
Comprehensive monthly maintenance of auto fire alarm system installed in BBJ Hanger & RSS Hangar and ISH in Tech Area at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 Nos. (b) UL Listed intelligent addressable multi-criteria detector with base- 284 Nos. (c) UL Listed intelligent heat detector - 08 Nos. (d) Manual call point - 08 Nos. (e) Control module for hooter - 18 Nos. (f) zone Monitor module - 28 Nos. (g) Fault isolator - 12 Nos. (h) Wall mounted hooter - 18 Nos. (j) Response indicator - 25 Nos. (k) IR Flame detector - 28 Nos. (l) UPS 1 KVA - 02 No.
Comprehensive monthly maintenance of auto fire alarm system installed in AW 101 Hanger No -I, II & III in Tech Area at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 192 Nos. (c) UL Listed intelligent heat detector - 02 Nos. (d) Manual call point - 18 Nos. (e) Control module hooter - 05 Nos. (f) Monitor module - 06 Nos. (g) Fault isolator - 12 Nos. (h) Wall mounted hooter - 06 Nos. (j) Response indicator - 70 Nos. (k) IR Flame detector - 44 Nos. (l) UPS 1 KVA - 02 Nos.
Comprehensive monthly maintenance of auto fire alarm system installed in SES LAB OF 181 FLIGHT, TWIN DSS BLDGS & CARGO TERMINAL in Tech Area at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Material required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 59 Nos. (c) Manual call point - 05 Nos. (d) Control module for hooter - 05 Nos. (e) Fault isolator - 04 Nos. (f) Wall mounted hooter - 07 Nos. (g) Response indicator - 07 Nos.
Comprehensive monthly maintenance of auto fire alarm system installed in SIGNAL EXCHANGE BLDG IN Camp area & EDN SECTION in Camp Area at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 99 Nos. (c) UL listed intelligent heat detector-02 Nos (d) Manual call point - 08 Nos. (e) Control module for hooter - 08 Nos. (f) Monitor module- 09 Nos (g) Fault isolator - 06 Nos. (h) Wall mounted hooter - 08 Nos. (j) Response indicator - 48 Nos.
Comprehensive monthly maintenance of auto fire alarm system installed in 41 SQN Simulator Bldg in Tech Area at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 02 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 130 Nos. (c) UL Listed intelligent heat detector - 04 Nos. (d) Manual call point - 11 Nos. (e) Control module for hooter - 06 Nos. (f) Monitor module - 05 Nos. (g) Fault isolator - 12 Nos. (h) Wall mounted hooter - 20 Nos. (j) Response indicator - 48 Nos. (k) UPS 1 KVA -02 Nos.
Comprehensive monthly maintenance of auto fire alarm system installed in AFCNWP CAMP AREA at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 01 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 65 Nos. (c) UL Listed intelligent heat detector - 06 Nos. (d) Manual call point - 06 Nos. (e) Control module for hooter - 06 Nos. (f) Monitor module - 06 Nos. (g) Fault isolator - 06 Nos. (h) Wall mounted hooter - 06 Nos. (j) Response indicator - 13 Nos.
Comprehensive monthly maintenance of auto fire alarm system installed in SES SCTION OF CPRU, IT SEC, CFNL LAB IN TECH AREA at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basisof all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 03 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 162 Nos. (c ) UL listed intelligent heat detector - 02 Nos (d) Manual call point - 14 Nos. (e) Control module for Manual call point - 14 Nos. (f) monitor module - 06 Nos. (g) Fault isolator - 10 Nos. (h) Wall mounted hooter - 14 Nos (j) Response indicator - 72 Nos. (k) sounder relay - 08 Nos. (l) UPS 1 KVA - 03 Nos. (m) central control including 21" colour monitor 21"and its CPU , Key board ,mouse & UPS -01 Set (n) Repeater panel -01 No
Comprehensive monthly maintenance of auto fire alarm system installed in ISR LAB,(T),73 RMU(T),WEATHER BUILDING (C), BBJMCF(T) IN TECH AREA at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing on monthly basis of all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (252 device/loop card) - 03 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 102 Nos. (c) Manual call point - 14 Nos. (d) Control module for Manual call point - 20 Nos. (e) monitor module - 06 Nos. (f) Wall mounted hooter - 4 Nos (g) sounder relay - 4 Nos. (h) UPS 1 KVA - 04 Nos.
Supply, installation, testing and commissioning in replacement of Photo electronic type smoke cum heat detector IP67 rated, having removable high performance chamber with twin fire LED's allow 360 degree veiwing, lock mechanism (sensor to base), employ two heat sensing elements with different thermal characteristics to provide a rate of rise dependent response. Electronically addressed, approved by LPCB. Flat FAST addressing technique Flexible (programmed in any sequence), Automatic (stored in EEPROM). (EN-54 approved) conforming to IS-11360 -1985 having dual ionized chamber meant for easy detection of high carbonized fumes by means of light emitting principle complete with base, UL FM LPCB complete all as specified and as directed by Engineer in charge. Make: Ceasefire/siemens/honeybell/Dyagni
Supply only in replacement of addressable manual call point/pull station single action type with gold plated SPST contacts complete all as specified and directed by Engineer in Charge. Make: Siemens./Honeywell/ceasefire/Agnidy/Notefire
Supply & fixing detector complying with and type certified to EN 45 addressable type flame detectors with UV/IR detection capacity complete all as specified and as directed by Engineer- in- Charge. Make:- Ceasefire/Siemens/Honeybell/Apolo
Supply only in replacement of addressable control relay module for manual call point complete all as specified and as directed by Engineer in Charge. Make:- Ceasefire/Siemens/Honeybell/Apolo/Agnidy/Notefire
Supply only in replacement of intelligent addressable monitor module complete all as specified and directed by Engineer in Charge. Make:- Ceasefire/Siemens/Honeybell/Apolo/Agnidy/Notefire
Supply only in replacement of hooter with control module complete all as specified and as directed by Engineer in Charge. Make:- Ceasefire/Siemens/Honeybell/Agnidy/Notefire
M&L for taking out unserviceable Power supply unit Model PSC-12 of Siemens Make from the existing Fire detection control panel and repairing the unit including replacement of unserviceable parts complete and refixing the same in its original position including testing commissioning complete all as specified and as directed.
Supply only in replacement of PCB loop cord suitable for self addressable fire finder system complete all as specified and directed by Engineer in charge. Make:- Seimens
Supply & fixing in replacement of PVC insulated armoured copper conductor cable size 1.5 sqmm 2 core FRLS 1100 volts fixed on wall/celling of the hanger with fixing accessories complete all as specified and directed by Engineer in charge.
S & F in replacement of PVC insulated PVC sheathed copper conductor cable size 1.5 sqmm 2 core FRLS 1100 volts drawn in existing PVC conduit fixed on wall/celling of the bldg complete all as specified and directed by Engineer in charge.
Supply and fixing in replacemnt of PVC conduit medium grade of size 20 mm dia including fixing accessories like saddles, couplers bends tees etc complete all as specified and directed by Engineer in charge.
Supply only in replacement of UPS 1.0 KVA suitable for working on 230 Volts, 50 Hz AC supply complete all as specified and directed by Engineer in charge.
Supply only in replacement of Battery 12 Volts 7 AH dry type complete all as specified and directed by Engineer in charge.
Disconnecting and taking out old unserviceable CPU display unit including PMI of fire finder and supply and fixing new CPU display unit including PMI suitable for self addressable fire finder XLS system complete all as specified and directed by Engineer in charge. Make:- Siemens/ Honey well/Edward
Supply, installation, testing and commissioning of microprocessor based 4 Zone conventional fire alarm control panel robustly designed and easy to operate, fully compliant with and tested to BS EN 54-2 and BS EN 54-4, Compatible for use on BS5839, Part 1, 2002 installation, 2 wire repeaters and ancillary boards, fully programmable using simple menu options, simple, single board construciton, installer friendly, compatible with Hochiki, conventional range of devices, two monitored sounder outputs, 3 Amp power supply, auxiliary power output, The control must be EN 54 approved, complete all as specified and as directed by Engr-in-Charge. Make : Ceasefire/fire protection/siemens/honeybell/Agnidy/Notefire
Supply, installation, testing and commissioning of (multi criteria) type detector with base combination of both heat and smoke detection arrangement of the same make as of fire alarm control panel. Detector should have a third terminal to provide an integral remote indicator output, removable high performance chamber, remote indicator output, wide voltage range (9.5 to 30V d.c) low profile design with one piece outer cover, twin fire LED's allow 360 degree viewing, range of mounting bases, approved by LPCB complete all as specified and as directed by Engr-in-Charge. Make:- Ceasefire/fire Protection/Siemens/Honeybell/Agnidy/Notefire
S & F in replacement coventional Manual Call Point having status LED for Alarming & standby mode,inbuild short circuit isolator, Electronically addressed approved by LPCB as EN54-11: 2001 complete all as specified and directed by Engineer in charge.Ceasefire//LTS/Agnidy/Notefire
Supply & fixing fire alarm control panel complying with BSEN 54 single loop panel of capacity from 99 detectors 200 detectors and module 1 loops networkable surface mounting FACP certified to EN54-2/EN54-4 norms can be Networkable capability of up to 64 Panels with 500 software zones. Large with 8x40 character LCD. The FACP shall be certified as meeting the requirements of EN54-2 and EN54-4 by a suitable, notified body. In order to facilitate re-configuration and system extension, the allocation of addresses to devices shall be independent of their physical arrangement on the loops and Sensitivity adjustment and Drift Compensation. The FACP shall capable analogue addressable wired and wireless sensors & modules Up to 127, plus 127 analogue base sounder / Beacon for total 254 point shall be configured on each addressable loop. The FACP shall have an event log capable of storing the last 500 events that have occurred. Loop powered sounders incorporated as a sensor bases shall be available. The FACP shall have the capability to support sub-addressing of addressable modules. The FACP shall monitor all critical system components and interconnections, internal and external, such that a failure, which would prevent the correct operation of the alarm functions, causes the FAULT indicator to light and a message to be given on the alphanumeric display within 60 seconds of occurrence. The FACP shall support minimum Four access levels,flash EPROM, programmable sounder circuits. The FACP Shall be housed in Ms Powder coated Cabinet, complete with exclusive Notification Circuits, and with Fire, Fault & Auxiliary Relays.The Panel shall support to programmed as a node on a peer to peer network with other Panels. Make:- Notofire
M & L for programming of addressible control panel with suitable equipment as per marking of the fire sensor/flame sensors complete in every respect all as speciified and directed by Engineer in charge.
Supply and fixing fire hydrant landing valve type 'A' (single head outlet) gun metal of 80mm dia landing valve with 63mm dia female outlet complete and 80mm inlet with rubber blank cap and chain as per IS 5290-1983, suitable for brigade hose of 63mm with coupling conforming to IS 903 including taking down the existing one complete all as specified and directed by Engr-in-charge.
Supply and fixing weather proof standard fire hose box made of 18SWG MS sheet 800mmX600mmX250mm with double door with 4mmthick glass and door frame made of 16 gauge including locking arrangement by allen key stove enamelled fire red finish with "fire hose" marked on front and brilliant white inside yard, suitable for housing of and consisting of 2 length RRL, hose pipe conforming to IS 6361979 (type-II) of 63mm dia GM instantaneous male and female (IS:903) and branch pipe ( nozzle) 12.5mm dia (for external hydrant) including taking down the existing one complete all as specified and directed by Engr-in-charge.
Supply, fixing, testing and commissioning of wall mounting swinging type first aid fire hose reel with drum, hanging bracket 30mtr long and 20mm dia high pressure hosereel as per IS 444 with gun metal shutt off nozzle. The hose reel shall be conforming to IS 884-1985. Rate shall including for 25mm dia MS pipe connection from riser to hose reel sockets, nipples, elbows and ball valve (25mm dia), Drum shall be fixed on adjoining wall through anchor fastener/cement concrete hook or MS stand as per site requirement and the rate for fixing/hanging items inthe rate quoted( for internal hydrant and one each an either side of stage) including taking down the existing one complete all as specified and directed by Engr -in-charge.
Supply and fixing in replacement of fire hydrant MS stand post 1.5mtr height single head outlet gunmetal of 80/150mm dia including all necessary surface finish with existing type complete all as specified and directed by Engr-in-charge.
Supply, fixing, testing and commissioning of GM four way, fire brigade inlet to hydrant ring with 63mm dia instantaneous type inlet and 150mm dia flanged outlet conforming to IS 904 with blank cap and chain including taking down the existing one complete all as specified and directed by Engr-in-charge.
Supply, fixing, testing and commissioning of GM two way, fire brigade inlet to hydrant ring with 63mm dia instantaneous type inlet and 150mm dia flanged outlet conforming to IS 904 with blank cap and chain including taking down the existing one complete all as specified and directed by Engr-in-charge.
M&L for Pressure switch in replacement universal type for maintaing pressure in fire fighting line complete all as specified and directed by Engineer in charge.
M & L for pressure gauge in replacement 4 " dial 0-21 KG rating for monitoring pressure in fire fighting line complete all as specified and as directed by Engineer in charge.
Supply, fixing, testing and commissioning in replacement of 150mm dia pipe heavy duty class 'C' MS pipe ISI marked as per IS:1239 with all necessary fittings & fabrication like tees, elbow, flanges, reducer, gaskets, nut and bolts etc welding or screwed joint as required including fixing of pipe with necessary standard clamps structural steel support (chilly make) as required/directed at site including painting of two coats of synthetic enamel paint of post office red color over two coats of red oxide primer including taking down the existing one complete all as specified and directed by Engr-in-charge.
All as per item no. 37 above but size of pipe 80mm complete all as specified and as directed by Engr in charge.
Supply & fixing in replacement of butterfly valve of size 150 mm dia conforming to IS 13095, flanged ends drilled type with steel spindle including nuts, bolts, washers and jointing material complete all as specified and as directed by Engr-in-charge.
Supply & fixing in replacement of butterfly valve of size 100 mm dia conforming to IS 13095, flanged ends drilled type with steel spindle including nuts, bolts, washers and jointing material complete all as specified and as directed by Engr-in-charge.
M&L for cleaning of brick masonary valve chamber of size 900mm x 900mm x 900mm (internal dimensions) with PCC (1:4:8) foundation 150mm thick brick masonary built in CM (1:6), PCC (1:3:6) type C1 (using 20mm graded stone aggregates), coping 50mm thick thick including plastering 15mm thick in CM (1:6) to all internal portion including provision of MS cover with locking arrangement embedded with angle iron of size (40x40x6)mm and painted with two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified and as directed.
M&L for boring holes under road pavement hard standing by trenchless technology using ultra sound technique and necessary machine for accomodating pipe of size 150/80 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.
Material and labour for cutting of hard standing/road upto 0.6 meter depth and thickness of size up to 180 mm suitable for fixing of 150/80 mm bore MS pipe and filling with ready mix cement concrete and making good disturbed surface complete all as specified and as directed.
S&F Fire foam concentrator drum of 200 ltr capacity for producing mechanical foam for fire fighting in and including replacement of existing plastic/PVC pipe, nozzle/fixing mechanism complete all as specified and as directed by Engineer in charge.
S&F in replacement of 63mm dia15mtr long controlled percolating rubberised fabric hose reel conforming to IS: 8423 (type A) including gun metal male and female instantaneous coupling bound and rivetted to hose pipe with 1.5mm dia steel complete in all respect, hose BSI marked, conforming to IS : 636 type II and complete male female coupling conforming to IS :903 complete all as specified and directed by Engr-in-charge.
M&L for taking out motor and Servicing of induction motor 75 HP coupled with fire pump complete including oiling, burnt winding replacement, greasing, replacement of wornout rubber packing, wornout nuts and washers etc including testing to the entire satisfaction of Engineer in charge.
M&L for taking out motor and Servicing of induction motor upto15 HP coupled with fire pump complete including oiling, burnt winding replacement, greasing replacement of wornout rubber packing wornout nuts and washers etc including testing to the entire satisfaction of Engineer in charge.
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr depth and n.exc 1.5 mtr wide for laying of pipes/cables etc and getting out all as specified and directed by Engineer in charge.
M&L for returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soft/loose soil complete all as specified and directed by Engineer in charge.
Removing excavated material not exceeding 50mtr and depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified and as directed by the Engineer-In-Charge
Supply and fixing branch pipe nozzle 63mm dia inlet with 20mm dia.complete all as specfied and directed.
Comprehensive monthly maintenance of fire fighting system installed in BBJ Hanger, RSS Hanger, ISH bld, CPRU, C flight-1, C-flight-2, C-flight-3, JMC in Technical Area at AF Stn Palam. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing if required all the equipments of fire detection system. (ii) Operational test of all the equipment of fire hydrant system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out skilled and qualified authorised Rep. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Materials required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire equipments required repairs/maintenance and AMC are as under:- (a) Fire hydrant (b) Hose reel drum (c) Hose pipe. (d) Branch pipe (e) Three way/Four way Fire valve (f) Pressure testing in pipe (g) 200ltr Fire foam with drum. (h) And other connected items in the bldgs completed
M&L for painting MS pipes using spray machine along with arrow marking as per existing colour complete all as specified and as directed. Make : Berger/Asian paints etc.
S&F in replacement of Cast iron sluice valve with cast iron wheel stainless steel spindle water quality conforming IS - 14846 class PN - 1.6 short bodies ISI marked as and when required of the following size including taking out unserviceable sluice valves all as specified & directed by Engg-in-Charge:-- (a) 150 mm dia
(b) 80 mm dia
(c) 200 mm dia
M&L for painting of equipments installed at fire fighting pump house like electic motor with pump with base frame, connected pipelines, sluice valve, Non return valve and all other items complete all as specified and directed by Engineer-in-charge.
S&F cast iron non return valve of size 50mm as per IS:5312, Part-I with by pass arrangement both end flanged and drilled holes with suitable 3mm thick rubber insertion, bolt and nuts including taking out the unserviceable valve all as specified and directed by Engineer-in-Charge.
S&F in replacement of coupling for connecting of MS pipes including replacement of nuts and bolts for proper connection as per existing size of pipes and making good for proper functioning complete all specified and directed by Engineer-in -charge.
Supply & fixing in replacement of butterfly valve of size 80 mm dia conforming to IS 13095, flanged ends drilled type with steel spindle including nuts, bolts, washers and jointing material complete all as specified and directed by Engr-in-charge.
S&F Fire foam concentrator drum of 20 ltr capacity for producing mechanical foam for fire fighting in and including replacement of existing plastic/PVC pipe, nozzle/fixing mechanism all as specified and directed by Engineer in charge.
S&F ML-3 contactor 2 N0+NC TP contactor as per existing at the site complete all as specified and as directed by Engineer in charge.
S&F VSP-2,115 V AC as per existing at the site complete all as specified and as directed by Engineer in charge.
S&F MCCB of capacity 100Amps 415V 25 KA complete all as specifed and as directed by Engineer in charge.
S&F Direct online starter 3 phase for maximum motor capacity output of 415V 10 HP relay range 9-15 Amps complete all as specified and as directed by Engineer in charge.
S&F MCB TPN 32 Amps complete all as specified and directed by Engineer in charge.
Supply and fixing adaptor of 12V for RO capacity 50 LPH complete all as specified and as directed by engineer in charge. Make:- Kent/Aquaguard/Livpure.
Supply and fixing in replacement of carbon filter, prefilter UV fillers of RO capacity upto 50 LPH complete all as specified and as directed by engineer in charge. Make:- Kent/Aquaguard/Livpure.
M&L for AMC of RO (existing make) of capacity upto 50 LPH which include quarterly visit, repair, inspection, cleaning, servicing, replacement of all type filters, pipe, motor & membrane etc complete in all respect rectifying at the site complete all as specified and as directed by Engineer in charge.
Supply fire extinguisher of dry powder portable type of capacity 6 kg and fixing on wall with clamp complete all as specified and as directed by Engineer in charge. Make-Agni/Eco fire/Cease fire
Supply fire extinguisher of carbon dioxide portable type of capacity 6 kg and fixing on wall with clamp complete all as specified and as directed by Engineer in charge. Make-Agni/Eco fire/cease fire
Supply fire extinguisher of water/foam portable type of capacity 6 kg and fixing on wall with clamp complete all as specified and as directed by Engineer in charge. Make-Agni/Eco fire/cease fire
Material & Labour for cleaning internal portion of static water Tank upto 20000 Gallons water storage sump including following processs:- (a) Mechanised removal of all remaining dirty water by high capacity submersible pump set (b) Removal of sludge by Vacuum operated German pump (c) Cleaning of walls, ceiling and bottom of tank by German made high pressure rotary jet 120 bar pressure. (d) Removal of all dirty particles by industrial wet vacuum cleaner leaving tha tank 99.9% physically cleaned. (e) Sterilization of tank atmosphere byEco-friendly bio-degradable and highly effective against all pathogens. (f) Sterilization of tank atmosphere by industrial UV radiator leaving tha tank completely sterilized by specilized method complete all as specified and as directed by Engr-in-Charge. Note: The item rate includes the cost of weather proof painting work to write (a) date of cleaning (b) Next due date of cleaning
Supply and fixing in replacement of unserviceable display board for showing details of fire fightening pump house with location and showing schematic diagram as provided by Engineer-in-charge made out of PVC sheet Box of size 1.5mtrX1mtrX20cm including angle frame and GI sheet cover to the frame and fixing of 2 Nos LED tube light fittings 20 watts, connecting electrical supply to the frame with copper wire two core 1.5 Sqmm from nearby electric source including round steel pole minium 12 feet long of suitable dia for erection on ground with PCC complete all as specified and as directed by Engineer-in-charge.
Taking out centrifugal pump and motor set of capacity 7.5 HP from the existing location to the authorised workshop for repair including detecting the fault complete all as specified and as directed by Engineer-in-charge.
M&L for rewinding of motor of capacity 7.5 HP taken out from Ser No-76 with copper winding including testing and refixing the same at the existing location complete all as specified and as directed by Engineer-in-charge.
M&L for replacemnt of bearing for Ser No-76 including testing and refixing the same at the existing location complete all as specified and as directed by Engineer-in-charge.
M&L for replacemnt of shaft for Ser No-76 including testing and refixing the same at the existing location complete all as specified and as directed by Engineer-in-charge.
M&L for quarterly periodical, preventive and comprehensive maintenacne of capacity (69 KW/ 92 HP 800RPM) DG sets installed in fire fighting pump house at AF Stn Palam consisting of the following:- (a) Checking of total system for proper functioning (b) Checking opf engine oil, Fan Belts, Hose Pipes, Fuel pipes and filters. (c) Checking of Foundation Bolts, Ante-vibration Pads, Oil and Water Safety devices. (d) Cleaning of fuel tank, checking of distilled water in batteries, checking of coolent concentrate and petrollium jelly on battery termials. (e) Checking of battery charging system, RPM of DG set, Volt meter, Ammeter etc for their proper functioning. complete all as specified and as directed by Engineer-in-charge.
Suppy and fixing in replacement of battery of capacity 12V complete all as specified and as directed by Engineer-in-charge.
Supply and fix B check kit for Ser No-80 complete all as specified and as directed by Engineer-in-charge.
Supply and fixing fir overhaulling and calibration of fuel injection pump including setting the tapped and replacement of seal if required excluding gear pump suitable for Ser No-80 complete all as specified and as directed by Engineer-in-charge.
Taking down radiator assembly from Ser No-80 and cleaning including brazing of water tubes if found leakage during cleaning. The radiator shall be cleaned throughly and remove scale deposists by suitable cleaning material. The radiator shall be tested for leakage by means of injecting pressure. The complete DG set housing/ block shall also be de-carbonized/cleaned by means of suitable cleaning material and re-fixing the same and testing after completion complete all as specified and as directed by Engineer-in-charge.
Supply and replacement /topping up engine oil multi grade 15W/40 complete all as specified and as directed by Engineer-in-charge.
Supply and filling coolant concentrate for DG set complete all as specified and as directed by Engineer-in-charge.
Supply and filling Distilled water for DG set complete all as specified and as directed by Engineer-in-charge.
YANSHIKA SECURITY SERVICES (BID ID -3438652)
T.I.John and Sons (BID ID -3432727)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .