Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.3 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹29.4 L+₹4.0 L (15.8%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹37.5 L+₹12.1 L (47.6%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹38.6 L+₹13.2 L (51.9%)Rejected-Finance | L4 | Rejected-Finance L4 | |
| 5 | Rejected-Technical | - | Rejected-Technical tender revoked GE/J-72/22-23, MRO not deposited |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
11 Mar 2023, 6:00 pmClosed
GE JAIPUR
Garrison Engineer, Military Engineer Services, Khatipura road, Jaipur 302012
REPAIR/MAINT OF INTERNAL ELECTRIFICATION WORK IN ZONE II B AREA AND REPAIR / MAINT OF ELECTRIC LT CABLE AND INDOOR TYPE PANELS AT SWC HQ BUILDING UNDER AGE E/M OF GE JAIPUR
2023_MES_578072_1
GE/J-73/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
JAIPUR
As per NIT
5 documents required · 5 mandatory
₹500
GE JAIPUR
₹94,000
Yes
28 Mar 2023
31 Jan 2023
13 Mar 2023
31 Jan 2023
11 Mar 2023
25 Feb 2023
31 Jan 2023 - 13 Feb 2023
Amount
Taking down carefully aluminum or copper point wiring including PVC casing caping or concealed conduit for (light, fan, socket, bell or power) including fixture and fittings such as switches, ceiling rose, regulators, sockets, light fittings etc and making good disturbed surfaces complete all as specified and directed
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 1.5 Sqmm (Phase-Red, Neutral-Black) and earth continuity conductor 1.5 Sqmm (Green) drawn into and including concealed rigid non metallic PVC condiut medium grade not less than 20mm dia ISI marked ivory colour with all conduit fittings/fixing accessories and unwelded sunken galvanised pressed steel terminal boxes of thickness not less than 1.0 mm covered with 3 mm thick phenoic laminated white sheet cover for mounting switches, scokets, fan regulators as required for one light point controlled by one switch complete all as specified and directed
All as per item No. 2.00 here-in-before but one fan point controlled by one switch.
All as per item No. 02 above but one light point controlled by two, two way switch.
All as per item No. 02 here-in-before but one socket outlet 6 amp controlled by one switch on the same board with other switches.
All as per item No. 02 here-in-before but one socket outlet 6 amp controlled by one switch on indepdendent board.
All as per item No. 02 here-in-before but one bell point controlled by one bell push.
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 4.0 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 4.0 sqmm (Green) drawn into and including concealed conduit and terminated in and including modular metal flush boxes for mounting modular cover plate & frame for one socket point 16 Amps controlled by one switch complete all as specified and directed
M&L for point wiring with 1100 volts grade PVC insulatd FRLS multistranded copper conductor cable 1.5 Sqmm (Phase-Red, Neutral-Black) and earth continuity conductor 1.5 Sqmm (Green) drawn into and including PVC casing-capping not less than 32x16 mm ISI marked ivory colour with all fittings/fixing accessories and unwelded sunken galvnised pressed steel terminal boxes of thickness not less than 1.0 mm covered with 3mm thick phenlic laminated white sheet cover/ PVC gang box for mounting sheet cover for mounting switches, sockets, fan regulators one light point controlled by one switch complete all as specified and directed
All as per item No. 9 here-in-before but one fan point controlled by one switch.
All as per item No. 9 here-in-before but one light point controlled by two, two way switch.
All as per item No. 9 here-in-before but one socket outlet 6 amp controlled by one switch on the same board with other switches.
All as per item No. 9 here-in-before but one socket outlet 6 amp controlled by one switch on indepdendent board.
All as per item No. 9 here-in-before but one bell point controlled by one bell push.
M&L for point wiring with 1100 volts grade PVC insulatd FRLS multistranded copper conductor cable 4.0 Sqmm (Phase-Red, Neutral-Black) and earth continuity conductor 4.0 Sqmm (Green) drawn into and including PVC casing-capping not less than 32x16mm ISI marked ivory colour with all fittings/fixing accessories and unwelded sunken galvnised pressed steel terminal boxes of thickness not less than 1.0mm covered with 3mm thick phenlic laminated white sheet cover / PVC Gang box for mounting sheet cover for mounting switches, sockets for one 16 Amps socket outlet point controlled by one switch on independent board.
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 1.5 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 1.5 sqmm (Green) drawn into and including concealed rigid non metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all conduit fittings / fixing accessories and sunken modular GI metal boxes not less than 1.0 mm thick and white modular mounting cover plates with frame for mounting modular switches, sockets, fan regulators etc as required for the following:- One light point/ fan point controlled by one switch.
All as per item No. 16 here-in-before but one socket outlet 6 amp controlled by one switch on the same board with other switches.
All as per item No. 16 here-in-before but one socket outlet 6 amp controlled by one switch on indepdendent board.
All as per item No. 16 here-in-before but one bell point controlled by one bell push.
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 4 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 4 sqmm (Green) drawn into and including concealed rigid non metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all conduit fittings / fixing accessories and sunken modular GI metal boxes not less than 1.0 mm thick and white modular mounting plates with frame for mounting modular switches, sockets as required for 3 pin 16 amps socket outlet point controlled by one switch.
S&F angle holder, insulated polycarbonate body with back plate complete.
S&F switch piano flush button single pole one way 6 Amp complete.
S&F switch piano flush button single pole one way 16 Amp complete.
S&F flush type, 6 Amp, single pole, two way complete.
S&F bell push, flush type, 6 Amps 240 volts complete.
S&F socket outlet, 2-in-1, 3 pin 6 & 16 Amps flush type compete.
S&F socket outlet, 2-in-1, 3 pin 6 Amps flush type compete.
S&F hum free stepped type fan regulator, 120 - 280 volts of 100 watts capacity (socket type) including connection complete all as specified and as directed.
S&F in repair switch piano flush button single pole one way 6 Amp complete.
S&F in repair switch piano flush button single pole one way 16 Amp complete.
S&F in repair flush type, 6 Amp, single pole, two way complete.
S&F in repair bell push, flush type, 6 Amps 240 volts complete.
S&F in repair socket outlet, 2-in-1, 3 pin 6 & 16 Amps flush type compete.
S&F in repair socket outlet, 2-in-1, 3 pin 6 Amps flush type compete.
S&F in repair hum free stepped type fan regulator, 120 - 280 volts of 100 watts capacity (socket type) including connection complete all as specified and as directed.
S&F modular fan regulator 120 watts, 2-module AC 230 Volts.
S&F in repair modular fan regulator 120 watts, 2-module AC 230 Volts.
S&F wire less door bell AC 240 volts, single pole complete.
S&F door bell AC 240 volts, single pole complete.
S&F ceiling rose 3 plates polycarbonate body complete.
S&F modular switch one way 6 amp 1 module complete all as specified and directed
Supplying and fixing modular socket 6/16 - 2/3 pin combined 2 module complete all as specified and directed
Supplying and fixing in repair modular socket 6/16 - 2/3 pin combined 2 module conmplete all as specified and directed
Supplying and fixing modular switch one way 16 amp 1 module complete all as specified and directed
S&F modular socket 6/16 Amps, 2/3pin combined 2 module AC 230 volts complete all as specified and directed
S&F Modular 2 way 6 Amp switch 1 Module complete all as specified and directed
S&F repair modular socket 6 Amps, 2/3 pin combined 2 module AC 230 volts complete all as specified and directed
S&F repair modular switch 1 way 16 Amps, 230 volts, 1 module complete all as specified and directed
S&F repair Modular 2 way 6 Amp switch 1 Module complete all as specified and directed
Supplying and fixing in repair modular socket 6 amp 2/3 pin combined 2 module complete all as specified and directed
S&F modular blanking plate 1 module complete all as specified and directed
S&F modular whiter cover plate with frame 3 module complete all as specified and directed
S&F modular whiter cover plate with frame 4 module.
S&F modular whiter cover plate with frame 6 module.
S&F modular whiter cover plate with frame 8 module.
S & F in repair plastic surface boxes 3 moduler for fixing modular switch and socket
S & F in repair plastic surface boxes 4 moduler for fixing modular switch and socket
S & F in repair plastic surface boxes 6 moduler for fixing modular switch and socket
S & F in repair plastic surface boxes 8 moduler for fixing modular switch and socket
Taking down carefully sub main wiring with PVC casing capping/PVC surface conduit and making good disturbed surfaces complete all as specified and directed
M&L for submain wiring with two runs of single core PVC insulated and unsheathed, multistranded FRLS copper conductor of size 6.00 sqmm, LT cable, 1100 volts grade and one run of 6 sqmm single core, multistrand copper conductor (green) as earth continuity conductor drawn into 20 mm dia concealed conduit complete all as specified and directed. NOTE: Two runs of 6 sqmm cable, one run of 6 sqmm cable along with conduit including acessories shall be measured as one running metre of submain wiring.
All as per item No. 61 above but 2x10 Sqmm + 1x10 Sqmm earth in 25mm dia conduit.
S&F in repair MCBs of 'C' series single pole 6 to 32 Amps having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs complete all as specified and directed
S&F in repair MCBs of 'C' series SPN 10 to 32 Amps having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs complete all as specified and directed
S&F in repair MCBs of 'C' series four pole 63 Amps having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs complete.
S&F in repair MCCB four pole, 125 Amps, 16 KA thermally adjustable between 70 to 100% including 4 spreader link set of same make as that of MCCB for connection, required lugs as required.
S&F in repair LED batten (1.2M) made of CRCA sheet housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficacy of 115 lumen per watt and total power consumption not more than 20 watt including driver. It has a rated system life time of 50000 burning hours at L70 and should have a color temperature of 6500K, CRI>80, THD<10% and PF>0.95 complete all as specified and directed
S&F in recess mounted LED panel of round shaped, cap 12 W, Long life 25000 burning hours including making connection complete all as specified and directed
S&F in repair recess mounted LED panel of size 2'x2', through replacing old fluorescent light with LED lights 04 nos in each panel 32 W, Long life 25000 burning hours including making connection complete all as specified and directed
S&F in repair LED fixture 10 watt (0.6 m long) having lumen output 100 lumens per watt including connection complete all as specified and directed
S&F in repair LED bulk head fitting 9 watt IP 66 & IK 09 with pressure die cast aluminium housing & polycarbonate diffuser duly pre wired connection with 0.75 Sqmm PVC insulated & sheathed three core flexible multi stranded copper conductor cable complete all as specified and directed
Supply and fixing in repairs energy efficient recessed mounted LED luminaire suitable for 2'x2' grid ceiling with fullglow fully diffused diffuser and lumen output of 3600 lumens having constant current electronic driver of 36 watt duly connected with 0.5 sqmm white colour PVC insulated & sheathed three core flexible multi stranded copper conductor cable complete all as specified and directed
Supply and fixing in repairs energy efficient recessed mounted LED luminaire suitable for 180 mm dia ceiling with flat diffuser and lumen output of 115 lumens per watt of 18 watt having constant current electronic driver duly connected with 0.5 sqmm white colour PVC insulated & sheathed three core flexible multi stranded copper conductor cable as required PF not lessthen 0.95 ITHD lesthen or equaal 10% opreting voltage 140-270 Volt complete all as specified and directed
Supply and fixing in repair LED based Bollard 10 Watt with MS pipe housing with glare free PMHA Difuser , IP 65 hight of light 1 mtr including Mortar Base and connetion wire of suitabe size complete all as specified and directed
M&L for pipe in pipe chemical earthing with GI pipe electrode 3.0 m long having outer pipe dia 80 mm & inner pipe dia 50 mm duly filled with highly conductive and anti corrosive compound of required quantity having chemical composition Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% burried in ground by digging a bore of 150 mm dia surrounded by soil friendly backfill compound non soluble in water including connection with galvanised earth strip 32 x 6 mm, making PCC pit of size 0.3 m x 0.3 m x 0.3 m (inner size) in mix 1:3:6 type C1 with RCC 1:2:4 type B-1, 40 mm thick cover reinforced with 8 mm dia MS bars 3 Nos both ways with lifting hook made out of 8 mm dia bar and testing on completion to achieve value not more than 2.0 ohm complete all as specified and directed. (Note - GI strip size 32x6 mm upto 7.5 m included in the item).
Taking down MCB distribution boards with incoming and outgoing controls any make any capacity after disconnecting complete all as specified and directed
S&F MCB distribution board, tripple pole and neutral, powder coated CRCA steel sheet, suitable for MCCB incomer upto 160 Amps, 4 way 415 volts, degree of protection IP 43, IK-09 with reversible double door, recess mounted, having 250 Amps insulated tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces complete all as specified and directed
S&F in repair single pole and neutral enclosure with a two pin and earth plug and socket complete with one Double pole MCB 20 Amps complete all as specified and directed
S&F MCB distribution board, powder coated, CRCA steel sheet, degree of protection IP 43, IK-09 with reversible double door, recess mounted , having insulated 100 Amps tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required with SPN, 240 volts, 4 ways complete all as specified and directed
All as per item No 79 above but SPN, 240 volts, 8 ways.
All as per item No 79 above but SPN, 240 volts, 12 ways.
All as per item No 79 above but TPN 415 volts, 4 ways.
S&F in repair exhaust fan of sweep 200 mm made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding complete all as directed
S&F in repair exhaust fan of sweep 250 mm made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding complete all as directed
S&F in repair exhaust fan of sweep 300 mm made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding complete all as directed
Supply, installation, testing and commissioning of LT panel board fabricated out of 2mm thick stainless steel (SS 316) with copper bus bar 4 pole equal of capacity in colour code R, Y & B, 200 Amps 415 Volts indoor type wall mounted of size not less than 750mmx650mmx250mm, installed on procelain insulators with bus bar chamber. The panel shall be dust and vermin proof, protection class IP 42 class, front opening & compartmental type with approach for cable entry and for easy maintenance duly internally wired with FRLS, PVC insualated stranded copper conductor cable of 1.0 Sqmm including LED indicator for R, Y & B and comprising of the following :- Incoming : One number MCCB 125 Amps 4 pole 16 KA 415 Volts, 70-100%, 50 Hz Make Legrand /Hager/Schneider. Outgoing : (a) MCB DP 40 Amps 'C' series 10 KA AC 240 volts-05 Nos. (b) Fixing only old serviceable Single phase tamper proof meter with optical port 10 to 60 Amps-04 Nos.
Supply and fixing in repair PVC insulated Copper wire of 6 Sqmm twin core wire at wall/in trench or complete all as specified and directed
Excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep for foundation of poles/stay/cable etc including getting out in any type of soil complete all as specified and directed.
Returning filling in (soil) including spreading levelling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed
Removal of excavated soil to a distance n.exc 50 m and depositing where directed at a level not exc 1.5 mtr above the ground level/starting point complete all as specified and directed
M&L Sand cushioning to the under ground electric cable complete all as specified considering 19.75 of SSR part -I complete all as specified and directed
M&L Sub Class 'B' brick covering protection to the eletric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified and directed
Material and labour for servicing of Bus Bar system 16 ways including cutting/disconnecting burn out connection and taking out from PCC/Cement Mortar wall and refixing to existing connecting /reassebling Bus bar including providing thimbles/ lugs, upto 2 meter copper wire of 2.5sqmm and making good surface by to match the surface complete all as specified and directed
Dismantling and taking out UG cable any size unserviceable items fixed in any position and removal from site, complete all as specified and directed
S&F 1100 volt grade heavy duty XLPE cable with PVC insulated aluminum conductor served with inner sheathing of PVC tape armoured with galvanized steel strip or wire and overall PVC sheathed of size 16 Sqmm nominal cross section 4 core laid in trenches, fixed to pole or passing through pipes including all necessary clamps, nuts, bolts washers complete all as specified and directed.
All as per Item No. 95 above but of size 25 Sqmm nominal cross section 4 core.
All as per Item No. 95 above but of size 35 Sqmm nominal cross section 3.5 core.
All as per Item No. 95 above but of size 50 Sqmm nominal cross section 3.5 core
All as per Item No. 95 above but of size 70 Sqmm nominal cross section 3.5 core
All as per Item No. 95 above but of size 95 Sqmm nominal cross section 3.5 core
All as per Item No. 95 above but of size 120 Sqmm nominal cross section 3.5 core
All as per Item No. 95 above but of size 150 Sqmm nominal cross section 3.5 core.
All as per Item No. 95 above but of size 185 Sqmm nominal cross section 3.5 core.
All as per Item No. 95 above but of size 240 Sqmm nominal cross section 3.5 core.
S & F in replacement molded case circuit breaker (MCCB) front operated switch disconector wirh extenderd shaft and IP 65 FP 400 Amps 36 KA rupturing capacity 415 volts including all fitment assesuries , lugs and suitable size nut and bolt , drilling work as per required and electric connection, as per existing make and shape complete all as directed.
All as per Item No. 105 above but IP 65 FP 160 Amps 36 KA.
All as per Item No. 105 above but IP 65 FP 100 Amps 36 KA.
All as per Item No. 105 above but IP 65 FP 63 Amps 36 KA.
S & F in replacement molded case circuit breaker (MCCB) IP 65 TP 160 Amps 36 KA rupturing capacity 415 Volt incl all fitment assesuries , lugs and suitable size nut and bolt , drilling work as per required and electric connection,as per existing make and shape complete all as directed.
All as per Item No. 109 above but IP 65 TP 250 Amps 36 KA
S & F in replacement On Load change over switch front operated switch disconector with extenderd shaft and IP 65 FP 400 Amps 36 KA rupturing capacity 415 Volt incl all fitment assesuries , lugs and suitable size nut and bolt , drilling work as per required and electric connection,as per existing make and shape complete all as specified and directed
S & F in repair Butterfly Valve of 80 mm bore complete
S & F in repair Butterfly Valve of 50 mm bore complete .
S & F in repair Ball Valve of 32 mm bore complete .
S & F in repair Fire brigade inlet connection 2 way -
S & F in repair Fire brigade inlet connection 4 way -
S & F in repairs Sprinkler glass bulb type (Standard response) as Per IS:15105/TAC guidelines 79 degree temperature rating pendent type
S & F in repairs Sprinkler flexible pipe 1.5 mtr long
S & F in repairs MS ERW Pipe of 32 mm bore complete
S & F in repairs MS ERW Pipe of 50 mm bore complete
S & F in repairs MS ERW Pipe of 80 mm bore complete
Supply and fixing in replacement of LED indicator lamp Red , Yellow and Blue including wire and lugs etc complete all as specified and directed
M&L for earthing with galvanized steel earth plate electrode 600mmx 600mmx6mm thick buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level) with the top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth strip 32x6mm, by means of steel bolts, nuts, check nuts and washers all as shown in electrical plate No. 03 of SSR Part -I connected to earthing point , PCC pit in mix 1:3:6 type C1 with PCC 1:2:4 type B-1, 40mm thick cover, watering arrangement with funnel and wire mesh and 20mm bore medium grade G.I. watering pipe, common salt and charcoal filling, necessary excavation and earh work including testing on completion.
S&F in repair single pointed air termination aluminium rod 12mm dia 300 mm long including nuts & bolts for fixing air termination rod to pole/ pipe duly insulated by providing appropriate insulator complete all as specified and directed
M&L in replacement test point terminal block made of gun metal or phosphorpous bronze size 75x75x25 mm drilled and screwed including 3 nos 8 mm dia 25 mm long hex. head screw complete all as specified and directed by EIC.
Supply and fix in replacement aluminum strip 25x3.15mm as roof conductor or down conductor or along the pole/pipe complete with saddles/ insulators made out of porcelain or fibere and fixing screws all as required at site and directed.
Supply & fix in Replacement GI strip 32x6mm, buried in ground or fixed to wall etc for loop earthing complete all as specified and directed
Supply ,installation , testing and commissioning of LT panel board fabricated out of 2 mm thich powder coated CRC sheet with copper bus bar 4 pole equal of capacity in colour code R,Y & B1000 Amps 415 Volts indoor type floor mounted angle Iron Size not less then 1.5 mtr x 1.5 m x 0.3M installed on porcelain insulators with bus bar chamber. the panel shall be dust and vermin proof, protection class IP 42 class front opening & compartmental type with approach for cable entry and for easy maintinancce duly internally wired with FRLS , PVC insulated standerd copper cable of 2.0 Sqmm including LED indicator R,Y,B 3 Phase volt meter digital type and comprising of the following : Incoming MCCB 400 Amps 4 pole 36 Ka 415 Volts 70 to 100 % , 50 Hz Out going MCCB 250 Amps 4 Pole 36 KA 415 Volts 70 -100% , 50 HZ ----05 Nos
Supply and installed of 3 Phase Automatic Phase Sequence corrector of 50 Amp load capacity Complete
Supply and installed of 3 Phase Automatic Phase Sequence corrector of 20 Amp load capacity Complete
Supply and fixing of seprator and connector as per existing shape and size all as spesified and directed
S& F in repair integral LED flood light 100 W 3000 K (WW) warm white with driver inside a PDC housing philips Cat part No CVP 182 LED 100 W CW FG S1 PSU GR or equivalent to Havells/CG as approved by GE
S&F bollard LED garden light 8 watt 1 Mtr hight complete with required earth work, including fasteners, nuts, bolts, washers, copper connecting cable & PCC (1:2:4) type B 1 using 20 mm graded stone aggregate (size 0.40 m x 0.30 m x 0.45 m) complete. Make Haveels Cat part No; CONENXGBLS8WLED857PSYMTOPCM or equivelent to philips/bajaj as approved by GE
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box, cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 03 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Aluminium bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC platform incl necessary earth and PCC work all as per manufacturer instructions and as directed.
Schedule of Credit
M/S TRADE LINKERS
SHREE BHAGWATI ENTERPRISES
M/S Anil Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .