SITC of Fire Detection and Alarm System at Nursing Training School both Old and New Building and Nursing Superintendent Office within the campus of IPGMER SSKM Hospital Kolkata
2024_WBPWD_705246_1
WBPWD/EE-I/KSHED/Q20/24-25
Open Tender
FIRE FIGHTING ORG
Item Rate
90 days
SSKM Hospital Kolkata
Please refer Tender documents.
3 documents required · 3 mandatory
₹27,992
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
4 Apr 2025
2 Jul 2024
5 Aug 2024
2 Jul 2024
2 Aug 2024
8 Jul 2024
8 Jul 2024
Amount
Supply, Installation,Testing & Commisioning of Intelligent Addressable multisensor detector (VDS/UL approved) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base as required. (Approval standards:VdS & EN54 Standard; ( Make: Siemens Cerberus Pro / Honeywell / Bosch / Carrier)
Supply, Installation,Testing & Commissioning of Addressable Manual Call Point ( VDS / UL approved ) soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. ( Make: Siemens Cerberus Pro / Honeywell / Bosch / Carrier)
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter (sound output of minimum 90 db) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL approved) approved. ( Make: Siemens Cerberus Pro / Honeywell / Bosch / Carrier) With specific external module as required.
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL approved) having 2 Nos. red coloured LED lamps including connections etc ( Make: Siemens Cerberus Pro / Honeywell / Bosch / Carrier)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex / Polycab / RR kabel) with 20 mm NB PVC rigid conduit pipe (Make: Precision) on the surface of the wall.
Supply, Installation, Testing & Commissioning of Addressable transponder / Monitor Modules ( VDS / UL approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. ( Make: Siemens Cerberus Pro / Honeywell / Bosch / Carrier)
Supply, Installation, Testing & Commisioning of Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm control panel ( VDS / UL approved ) suitable for the devices as stated in the previous items of this estimate along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer (if required), Loop cards, LCD unit to indicate Fire/Fault Signal with adress & analog output, complete in all respect, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working & then be capable of operating the system for 30 minutes during Emergency condition with integral battery charger complete in all respect as required.
The FACP ( VDS / UL approved )shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 bus. The FACP shall have provision for interfacing with the public address system, remote computer & BMS interface. the system must be preloaded with licensed software ( Make: Siemens Cerberus Pro / Honeywell / Bosch / Carrier)
single loop panel
2 (two) loop panel
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Polycab/Finolex/RR Kabel) of the following sizes in the flexible polythene pipe and by the prelaid GI fish wire and making necy. connection as required - 3 x 22/0.3 (1.5 sqmm) for interconnection between detector & respose indicator
TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done.
TERMS & CONDITIONS :- The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liabibility Period 1 (One) year
Make & model of each and every material to be approved by EIC
Computer Gallery
Creative Projects
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .