Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.5 CrAdmitted-Finance VOLTAS HOUSE B 2ND FLOOR T B KADAM MARG CHINCHPOKLI MUMBAI 400 033 | MUMBAI | MUMBAI | MAHARASHTRA | 400033 | ₹5.5 Cr | L1 | Admitted-Finance |
| 2 | L2₹5.9 Cr+₹41.9 L (7.66%)Admitted-Finance | ₹5.9 Cr+₹41.9 L (7.66%) | L2 | Admitted-Finance |
| 3 | L3₹6.1 Cr+₹60.9 L (11.2%)Admitted-Finance | ₹6.1 Cr+₹60.9 L (11.2%) | L3 | Admitted-Finance |
| 4 | L4₹6.3 Cr+₹84.9 L (15.5%)Admitted-Finance 10TH FLOOR UNIT 2 TECHNIPLEX 2 VEER SAVARKAR FLYOVER S V ROAD GOREGOAN WEST MUMBAI 400 062 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400062 | ₹6.3 Cr+₹84.9 L (15.5%) | L4 | Admitted-Finance |
| 5 | L5₹6.4 Cr+₹90.6 L (16.6%)Admitted-Finance 404 ITL TWIN TOWERS PLOT NO B 9 NETAJI SUBHASH PLACE PITAMPURA NEW DELHI | NORTH WEST | DELHI | 110034 | ₹6.4 Cr+₹90.6 L (16.6%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | BRITE INDUSTRIES L2 | INGENIOUS INDUSTRIES L6 | WEATHER COOL SALES PVT LTD L3 | HV AIRCONDITIONING SYSTEMS PVT. LTD. L5 | VAV Airconditioning L4 | VOLTALIMITED L1 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00SECTION-01- HIGH SIDE EQUIPMENT | |||||||||
| 2.00CHW SYSTEM | |||||||||
| 3.00SITC OF AIR Cooled Screw Chillers With VFD/Screw compressors | |||||||||
| 4.00Supply, Testing & Commissioning of factory manufactured and run tested, with Multiple screw compressors Multiple Circuit Air cooled with VFD/EC Fans , liquid chilling package, complete in all respect as per specifications, as required for successful commissioning and operation. Refrigerant used shall be Environment friendly. All chillers shall be factory tested at design conditions at 100%, 75%, 50% and 25% load. The chiller shall be complete with all accessories.The chiller should be equipped with 50 mm external deflecction spring isolators. Motor shall be suitable for 415±10% 50 cycles. 3 phase AC supply. The Chiller needs to be AHRI/Eurovent Certified.Copper Tube & Aluminium Fin type condenser coated with Anti-corrosive coating (Min. 2000 Hr Salt Spray Tested), Flooded/DX Evaporator with ASME stamping in accordance with ASME standards, complete with relief valve, filters, safety switch, receiver (if required), purge (if required) & pressure relief valves. Chiller Package complete with Evaporator, Compressors, Air Cooled Condenser, Electronic expansion valves, shut-off valves, insulation of cold/hot surfaces, flanges etc as per OEM standards exceeding is subject to approval from consultant. | |||||||||
| 5.00All chillers will have adapter boxes with flexible copper wire / cables and suitable link for termination of Copper Cables. 19mm Insulation of Nitrile Rubber (Class O) with factory/site laminated black glass cloth of 7mil thickness for Evaporator. Flow switch / sensor and interconnecting cable between flow switch / sensor and chiller microprocessor shall be included. Chiller shall have BMS interface card to replicate all chiller parameter over BMS terminal.Unit Mounted VFD starter panel (as per below line items). Overload relays, timers, single phasing preventors etc and other necessary safeties to be included. The noise level should not exceed 82 dBA @1m in free field conditions. | |||||||||
| 6.00Quoted price of chiller to include the following: | |||||||||
| 7.00supply, Installation,Testing & commissioning of the chillers at site after the equipments have been installed in the plantroom. | |||||||||
| 8.00Vibration isolators (spring isolators)-from chiller manufacturer only | |||||||||
| 9.00Rigid Grooved Coupling/matching flanges (each set of Rigid Grooved Coupling consist of couplings for Chilled Water in and out) | |||||||||
| 10.00Chiller to be provided with an additional tin plated copper busbar with bi-metal insertion strips at connection point suitable for aluminum cables to copper busbar connection. | |||||||||
Tender Value
₹6.9 Cr
EMD Value
₹13.9 L
Closing Date
9 Sept 2025, 3:00 pmClosed
Director TMC
Office of Engineering services, Second Floor,Khanolkar Shodhika , ACTREC Kharghar Node, Navi Mumbai - 410210
Supply,Installation,Testing and Commissioning of high side HVAC system for SSPCC Building at ACTREC
2025_TMC_871832_1
ET-35/SITC of High Side HVAC System/2025
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
180 days
ACTREC, Kharghar
As per Tender Document
2 documents required · 2 mandatory
₹0
₹13.9 L
ACTREC,Kharghar
19 Jan 2026
4 Aug 2025
10 Sept 2025
4 Aug 2025
9 Sept 2025
4 Aug 2025
4 Aug 2025 - 11 Aug 2025
12 Aug 2025
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SECTION-01- HIGH SIDE EQUIPMENT | - | - | - | - |
| 2 | CHW SYSTEM | - | - | - | - |
| 3 | SITC OF AIR Cooled Screw Chillers With VFD/Screw compressors | - | - | - | - |
| 4 | Supply, Testing & Commissioning of factory manufactured and run tested, with Multiple screw compressors Multiple Circuit Air cooled with VFD/EC Fans , liquid chilling package, complete in all respect as per specifications, as required for successful commissioning and operation. Refrigerant used shall be Environment friendly. All chillers shall be factory tested at design conditions at 100%, 75%, 50% and 25% load. The chiller shall be complete with all accessories.The chiller should be equipped with 50 mm external deflecction spring isolators. Motor shall be suitable for 415±10% 50 cycles. 3 phase AC supply. The Chiller needs to be AHRI/Eurovent Certified.Copper Tube & Aluminium Fin type condenser coated with Anti-corrosive coating (Min. 2000 Hr Salt Spray Tested), Flooded/DX Evaporator with ASME stamping in accordance with ASME standards, complete with relief valve, filters, safety switch, receiver (if required), purge (if required) & pressure relief valves. Chiller Package complete with Evaporator, Compressors, Air Cooled Condenser, Electronic expansion valves, shut-off valves, insulation of cold/hot surfaces, flanges etc as per OEM standards exceeding is subject to approval from consultant. | - | - | - | - |
| 5 | All chillers will have adapter boxes with flexible copper wire / cables and suitable link for termination of Copper Cables. 19mm Insulation of Nitrile Rubber (Class O) with factory/site laminated black glass cloth of 7mil thickness for Evaporator. Flow switch / sensor and interconnecting cable between flow switch / sensor and chiller microprocessor shall be included. Chiller shall have BMS interface card to replicate all chiller parameter over BMS terminal.Unit Mounted VFD starter panel (as per below line items). Overload relays, timers, single phasing preventors etc and other necessary safeties to be included. The noise level should not exceed 82 dBA @1m in free field conditions. | - | - | - | - |
| 6 | Quoted price of chiller to include the following: | - | - | - | - |
| 7 | supply, Installation,Testing & commissioning of the chillers at site after the equipments have been installed in the
plantroom. | - | - | - | - |
| 8 | Vibration isolators (spring isolators)-from chiller manufacturer only | - | - | - | - |
| 9 | Rigid Grooved Coupling/matching flanges (each set of Rigid Grooved Coupling consist of couplings for
Chilled Water in and out) | - | - | - | - |
| 10 | Chiller to be provided with an additional tin plated copper busbar with bi-metal insertion strips at
connection point suitable for aluminum cables to copper busbar connection. | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
BOQ_916477.xls
BOQ • 0.44 MB
AnnexureForm.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .