Executive Engineer, BMD, PHE, Dte
Office of the Executive Engineer. Bankura Mechanical Division. P.H.E. Dte. Ailakundi, PO Kenduadihi, Bankura 722102.
Servicing and Testing of 33 KV VCB Panel, 6.6 KV VCB Panel and LT panels with all other switch gear equipments and 4000kva and 1000 kva transformer under DEJURI Water Treatement Plant Under Bankura Mechanical Division, PHE Dte.
2024_PHED_779084_7
WBPHED/EE/BMD/NIeT-13 OF 2024-2025
Open Tender
MECHANICAL
Item Rate
60 days
Bankura
Please refer Tender documents.
5 documents required · 5 mandatory
₹24,000
Yes
5 Mar 2025
13 Dec 2024
30 Dec 2024
13 Dec 2024
27 Dec 2024
13 Dec 2024
Amount
Servicing & Testing of 33 KV VCB Panel as per Direction of EIC
Servicing & Testing of 6.6 KV VCB Panel as per Direction of EIC
Servicing & Testing of 6.6 KV VCU Soft Starter Panel as per Direction of EIC
Servicing & Testing of HT Capacitor Bank Panel as per Direction of EIC
Servicing, Tightness Checking, OTI, WTI, Buchholz Checking of 4000 KVA, 33/6.6 KV OLTC Transformer as per Direction of EIC
Servicing Tightness Checking, OTI, WTI, Buchholz Checking of 1000 KVA, 6.6/0.433 KV OLTC Transformer as per Direction of EIC
i). Servicing & Testing of 1600 A. PCC Panel With 4 Nos. 1600 A. & 1 No. 800 A. ACB as per Direction of EIC
Servicing & Testing of 800 A. LT Panel With 3 Nos. 800 A. ACB as per Direction of EIC
Servicing & Testing of 315 A. Sludge Handling System MCC Panel as per Direction of EIC
Servicing & Testing of 315 A. Sludge Handling System MCC Panel ii). Servicing & Testing of 415/380-420 V, 3 Phase 50 KVA 2 Nos. Lighting Transformer iii)Cleaning & Servicing of Valve Actuator Panel as per Direction of EIC
Servicing of LT Capacitor Bank Panel (2 Nos. 120 KVAR & 2 Nos. 40 KVAR) as per Direction of EIC
. Servicing & Testing of 280 KW FCMA Soft Starter Panel as per Direction of EIC
Servicing & Checking of Waste Water Panel as per Direction of EIC
All kinds of Gaskets & Oil seals supply for 4000 KVA, 33 / 6.6 KV oil type transformer as per Direction of EIC
Charges for gasket changes for 4000 KVA, 33 / 6.6 KV oil type Transformer by disconnecting of all HT and LT terminals, draining transformer oil, opening of top cover, arresting of any oil leakage by changing of gasket and oil seal respectively various gasket portion like top cover, inspection cover, tap switch, conservator tank, radiators, buchholz, drain valve (as where required) and HT-LT bushing portion as per Direction of EIC
All kinds of Gaskets & Oil seals supply for 1000 KVA, 6.6 / 0.433 KV oil type transformer as per Direction of EIC
Charges for gasket changes for 1000 KVA, 6.6 / 0.433 KV oil type Transformer by disconnecting of all HT and LT terminals, draining transformer oil, opening of top cover, arresting of any oil leakage by changing of gasket and oil seal respectively various gasket portion like top cover, inspection cover, tap switch, conservator tank, radiators, buchholz, drain valve (as where required) and HT-LT bushing portion as per Direction of EIC
Dehydration & Filtration of Transformer Oil by heat run process for improvement of IR Value (BDV minimum 60KV/mnt) by the hiring of Filtering Machine as per direction of E.I.C [33 KV Transformer – {3425+850(OLTC) = 4275} X 2 = 8550] [11 KV Transformer – {1280+300(OLTC) = 1580} X 2 = 3160] as per Direction of EIC
Painting of of the 4000KVA Transformer by the ready mixed primer of approved make, and brand incl. preparation of surface by sand paper, cleaning etc. for receiving two coat of superior quality synthetic anamal paint after applying one coat of red lead chromate primer as per direction of EIC. Painting wil be done by the spray paiting machine
Painting of of the 1000KVA Transformer by the ready mixed primer of approved make, and brand incl. preparation of surface by sand paper, cleaning etc. for receiving two coat of superior quality synthetic anamal paint after applying one coat of red lead chromate primer as per direction of EIC Painting wil be done by the spray paiting machine
Transportation charge for carrying of transformer oil for top up of Existing transformer and avr by hiring proper vehicls including labour charges for Loading and unloading from Bankura BMD store to Dejuri WTP water supply scheme as per direction of EIC
Hiring charges for Testing Equipments BDV Testing Kit etc from Kolkata to Dejuri WTP as per Direction of EIC
Add: 18% GST
Add: 1% Cess
JAGANNATH ENTERPRISE (BID ID -5917622)
M/S.S.S.ENTERPRISE (BID ID -5921387)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .