CHIEF ENGINEER RND SECUNDERABAD
CHIEF ENGINEER RND SECUNDERABAD OPP JUBILEE BUS STATION PICKET SECUNDERABAD 500003
PROVISION AND INSTALLATION OF NEW INTELLIGENT INTEGRATED FIRE DETECTION AND ALARM SYSTEM AT DRDL, HYDERABAD
2026_MES_787135_1
84052
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KANCHANBAGH HYDERABAD
Class B category c(vi)
8 documents required · 8 mandatory
₹2,000
GARRISON ENGINEER I RND KANCHANBAGH
₹3.1 L
Yes
31 Aug 2026
31 Aug 2026
30 Sept 2026
31 Aug 2026
28 Sept 2026
21 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing, programming & commissioning of Computer System, i7 Processor, latest generation, 2.93GHz, 4MB Cache with 16 GB RAM, & 1 TB SSD, 2GB 4K Graphics Card, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 10 OS Professional Enterprise or latest OEM licensed version, Web server software, 100/1000 Mbps NIC for network connection and antivirus software as per specifications. Accessories included 50 Inch UHD 4K LED Screen, Optical Mouse & Key Pad, Windows Licensed software compatible with the above FAS System configuration complete all as specified and directed. | 2 | EACH | - | - |
| 2 | Supply, installation, testing & commissioning of scaleable & upgradeable software for Fire Alarm System with features like 3D vector dynamic graphics with AutoCAD import of plan with Zoom In & Zoom Out facility, Plant Viewer, Trend Viewer, Object Viewer, Report Viewer, Alarm router. The Web-Based Server software shall permit use of Standard Web-Browsers such as Microsoft Internet Explorer, Netscape Navigator, etc. The software shall be capable of integration third-party systems and should supports latest IP technology (IP V4/V6). The Web based software shall include Client License for remote viewing. The software shall have Online Engineering capability i.e. Zero Downtime for software graphics modification. | 1 | EACH | - | - |
| 2.01 | Software should be capable to integrate BMS, Gas Suppression & VESDA Panels Seamlessly complete all as specified and directed.
Software should comply to OPEN Protocols and cyber security complaint like:
- BACnet/IP for HVAC Automation/BMS
- SNMP for UPS & Networking Integration
- Modbus/IP for Energy Monitoring
- IEC61850 for Electrical & Power Integration
- ONVIF for CCTV Integration
- OPC for any other Integration. | - | - | - | - |
| 2.03 | (ii) Complete programming, data base creation, logic programming, device addressing, loop configuration, graphics generation, FAT, SAT testing and commissioning is deemed to be included in the quoted rate. | - | - | - | - |
| 3 | Supplying, installation, testing and commissioning of UL 864 10th edition UL listed and FM approved Analog addressable 2 Loop Fire Alarm Control Panel having the total panel capacity of 252 devices. Each loop shall support 252 addressible devices (126 detector + 126 modules / devices). The panel shall be able to give pin point location of all fire / fault and Isolation conditions of addressable units via the address codes including automatic fault isolation. The panel shall have the capacity of storing upto 10000 events. Further, the panel | 4 | EACH | - | - |
| 3.01 | must be able to automatic AHU trip, fire door monitoring, input / output module programming respective control module whenever any alarm is triggered. The panel should have inbuilt common Alarm, Fault and monitored sounder output. The panel shall have a 2” x 4-3/4” size VGA monochrome LCD display and having maximum 320 (8 x 40) characters in the display with optional 24 zones LED indicators. The panel shall have a built in power supply of 170 Watts and battery charger. Battery charger shall be able to charge the system batteries of upto 33AH capacity or as per IS 2189 / NFPA 72 specified cap battery sizing calculation to be submitted during approval stage with minimum 24 hrs standby plus 30 min | - | - | - | - |
| 3.02 | alarm or as specified in design calculation. The panel shall have the capacity of connecting additional 31 panels or network terminals using network card, with redundancy in the network. The panel shall have the capacity of connecting maximum 16 Remote terminals / 16 remote displays or combined by using. The panel shall be compatible for IBMS system with open protocol BACnet over IP complete all as specified and directed.
Note: All disturbed existing surfaces shall be made good after completion of works. Any damage caused during execution shall be repaired and restored by the contractor at no extra cost. | - | - | - | - |
| 4 | All as per Sl Item No. 3 above but for 1 Loop Panel.
Note: (i) Enclosure shall be IP 54.
(ii) 25% spare loop capacity to be provided. | 5 | EACH | - | - |
| 5 | Supplying, installation, testing & commissioning of UL 864 10th edition UL listed and FM approved Networkable Repeater Panel. The panel shall be able to give pin point location of all fire / fault and Isolation conditions of addressable units via the address codes. The panel shall have the capacity of storing upto 10000 events. Further, the panel must be able to automatically switch ON/OFF respective control module whenever any alarm is triggered. The panel should have inbuilt common alarm, fault and monitored sounder output. The panel shall have a 2” x 4-3/4” size VGA monochrome LCD display and having maximum 320 (8 x 40) characters in the display with optional 24 zones LED indicators. The panel shall have a built in power supply of 170 Watts and battery charger. Battery charger shall | 2 | EACH | - | - |
| 5.01 | be able to charge the system batteries of upto 33AH capacity. The panel shall have the capacity of connecting additional 31 panels or network terminals using network card, with redundancy in the network. The panel shall have the capacity of connecting maximum 16 remote terminals / 16 remote displays complete all as specified and directed. | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.44 MB
84052Tender_1.pdf
Tender Documents • 0.95 MB
BOQ_882144.xls
BOQ • 3.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .