Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.6 LAccepted-AOC 14 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹4.3 L+₹72,210 (20.3%)Rejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L2 | Rejected-Finance 1st. lowest | |
| 3 | L3₹4.4 L+₹83,174 (23.4%)Rejected-Finance | L3 | Rejected-Finance 2nd. lowest |
Tender Value
Refer Docs
EMD Value
₹8,000
Closing Date
28 Jun 2023, 5:00 pmClosed
AE AHESD
Assembly House Electrical Sub Division West Bengal Legislative Assembly South Annex Building G. Floor Kolkata 700 001
SITC of LT Cubical type floor mounted panel and S and F of cable tray and laying of cable for North Annex and Administrative Building at Assembly House Kolkata
2023_WBPWD_543652_1
eNIQ No. - 02 /WBPWD/AE/AHESD of 2023-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
10 days
Assembly House
Please refer Tender documents.
6 documents required · 6 mandatory
₹8,000
19 May 2025
22 Jun 2023
1 Jul 2023
22 Jun 2023
28 Jun 2023
23 Jun 2023
Amount
Supply & Delivery of LT Cubical type floor mounted panel board with Multi Compartment : one for incoming, one for busbar and one for outgoing MCCBs made with 14 SWG CRCA Sheet. The panel board should have proper cable alley both side with cable entry at bottom and outgoing from top with Seimens type locking arrangement and detachable Gland Plate. The board should be painted with powder coated paint. The Panel board consisting the following : Incoming : (A) 415V FP 400A MCCB with spreader terminal & extended rotary handle (Make : L&T) - 1 No. Busbar : (A) 500V Gr. 630A 4 Nos. tinned Cu Bar for Phases & Neutral - 1 Set Outgoing : (A) 415V FP 125A MCCB with spreader terminal & extended rotary handle (Make : L&T) - 4 Nos. Metering : (A) 0-630A Digital Ammeter - 1 Nos. (B) 0-500V Digital Voltmeter - 1 Nos. (C) CT of ratio 400/5A - 3 Nos. (D) LED Indicating lamps with control fuse - 3 Nos. (E) 6A TP MCB - 1 No. (F) Danger Board - 1 No. All inter connections form incoming to busbar and busber to outgoings are to be connected with suitable size of Cu bars & wire as per direction of EIC (Including all Taxes & duties)
S&F 3" x 1½" MS iron channel with MS Clamp Stopper grouted on floor/wall to support the LT Panel incl. nut, bolt & washer as per direction of EIC
Instn. of the service panel with all necy. arrangements as per direction of EIC (Including all Taxes & duties)
Supply, fabrication and eraction of supporting cable ladder post using 80 mm GI pipe of 6 mtr. long incl. 1.5 mtr. below ground level with base plate and fixing plate on the top of the post made of 250x250x8mm thick with necessary holes and nut bolt washer for supporting the ladder arrangement, having 450x450x200 mm thick CC (4:2:1) base block incl. CC (6:3:1) muffing 030 mts dia and 0.30 mts above ground level and 3mm thick neat cemented finish as per direction of EIC (Including all Taxes & duties)
Supply,Fabricating and fixing of special type cable ladder arrangement having width 350 mm made of 2 nos. 50x6 MS angle iron and 50x6 strip @ 200mm for holding the two adjacent angles maintaing sufficient spacing between them and providing necessary arrangement for fixing and supporting cable tray on the post and wall brackets as per direction of EIC (Including all Taxes & duties)
S&F specially fabricated "L" shaped 50x50x6 mm MS angle bracket for supporting the cable tray on wall. the length of bracket 600 x 450 mm having 600mm length having drilled holes & fustern on wall, strong enough to withstand the load of total cable tray setup having cables laid through the tray and providing cross arm as per direction of EIC (Including all Taxes & duties)
Supply & fixing of 300X50X1.25mm (18SWG) perforated GI cable tray with perforation not more than 17.5% on the MS angle ladder incl S&F necessary Stainless Steel bolts & nuts,.
PWD Sche. Item: D-14/34(a): Supply & fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl S&F G.I. connector, 6mm dia MS suspender bolts & nuts, steel fastener etc as required of the following size incl. Al painting of MS support. With 25x25x3mm angle iron support 300X50X1.25mm (18SWG)
PWD Sche. Item: D-15/34(b): Supply & fixing of 300X50X1.25mm (18SWG) perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two nos., suspenders & 25X25X3mm angle iron for supporting the bend incl. S&F G.I. connector, 6mm dia MS suspender, bolts & nuts, steel festener etc as required of the following size incl. Al painting of MS support.
Dismantling of plastered wall aproximately 400 mm wide and at least 100 mm high for the cable tray work incl. cutting rods & cement concrete works & removing rubbish, earth etc. from the working site & deposit the same beyond the compound & cleaning the site in all respect as per direction of EIC
Supplying and delivery of 4 core x 300 sq. mm. 1.1kV grade Aluminium Armoured Power Cable. (Make: Havells)
PWD Sche. Item: F-3/4(c): Laying of one cable upto 300 sqmm through existing covered masonry trnch incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand
PWD Sche. Item: F-4/7: Supplying and fixing of 4 core x 300 sq. mm. compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables.
PWD Sche. Item: F-5/8(a): Finishing of the following XLPE/PVC insulated armoured cable ends by soldering with cable sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc. 4 core x 300 sq. mm..
S. A. ENTERPRISE
JAYBEECO
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .