| 1 | L1₹29.5 LAccepted-AOC BUILDING NO FLAT NO 19 6TH CROSS ROAD SANJEEVINI NAGAR MUDALAPALYA BANGALORE 560072 | BANGALORE | BANGALORE | KARNATAKA | 560072 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹37.4 L+₹6.7 L (21.9%)Rejected-Finance 121004 | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹39.0 L+₹8.3 L (27.0%)Rejected-Finance 704 SILVER DEAL DAFFODIL WING 1 B T KAWADE ROAD PUNE 411 001 | PUNE | PUNE | MAHARASHTRA | 411001 | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹40.9 L+₹10.3 L (33.4%)Rejected-Finance 18 KUSHAL LAYOUT 1ST CROSS KAGGADASAPURA CV RAMAN NAGAR POST BENGALURU 560093 | BENGALURU | BENGALURU URBAN | KARNATAKA | 560093 | L4 | Rejected-Finance NOT BEING LOWEST | |
| 5 | L5₹44.3 L+₹13.7 L (44.6%)Rejected-Finance | L5 | Rejected-Finance NOT BEING LOWEST |
| Sl No | Description | Qty | Unit | RAHUL ENTERPRISES L1 | Neptune Engineers and Builders L2 | M/S - KRUPA ELECTRICALS L3 | GURU ENTERPRISES L7 | Shiva Shakthi Electrical Enterprises L6 | B5BUILDING SOLUTIONS L5 | TECKXPERT ENTERPRISES L4 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches n.exc. 1.5m wide and n.exc. 1.5m in depth for laying cables / poles foundation / stay assembly and getting out in soft / loose soil all as directed by Engineer-in-Charge.. | 293.63 | CUBIC METRE | 400 ₹1,17,452 | 380 ₹1,11,579.4 | 300 ₹88,089 Lowest | 310 ₹91,025.3 | 325 ₹95,429.75 | 310 ₹91,025.3 | 320 ₹93,961.6 |
| 2.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc, 25cm thick all as specified and as directed by Engineer-in-Charge.. | 234.9 | CUBIC METRE | 50 ₹11,745 Lowest | 140 ₹32,886 | 90 ₹21,141 | 100 ₹23,490 | 60 ₹14,094 | 120 ₹28,188 | 105 ₹24,664.5 |
| 3.00 | Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed. | 58.73 | CUBIC METRE | 100 ₹5,873 | 60 ₹3,523.8 Lowest | 100 ₹5,873 | 110 ₹6,460.3 | 60 ₹3,523.8 Lowest | 150 ₹8,809.5 | 140 ₹8,222.2 |
| 4.00 | Supply and spread dry river sand in trenches for cable cushioning all as specified on both top and bottom of cable including ramming all as specified and as directed.
NOTE :-
(a) Punned thickness will be considered for measurement purposes. | 78.98 | CUBIC METRE | 1,050 ₹82,929 Lowest | 3,650 ₹2,88,277 | 1,200 ₹94,776 | 1,180 ₹93,196.4 | 1,400 ₹1,10,572 | 1,350 ₹1,06,623 | 1,600 ₹1,26,368 |
| 5.00 | Supply and lay burnt brick sub class 'B' of standard size best quality locally available laid in trenches for cable protection all as specified and as directed. | 10,000 | EACH | 12 ₹1,20,000 | 11 ₹1,10,000 | 12 ₹1,20,000 | 12.5 ₹1,25,000 | 9 ₹90,000 Lowest | 9 ₹90,000 Lowest | 14 ₹1,40,000 |
| 6.00Material and labour XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (heavy duty) with aluminium conductor, 1100 volts grade cross sectional area of following sizes complete all as directed. NOTE :- (a) The rate is inclusive of testing of cable at site after laying of cables in trenches/walls. (b) The cable may be laid manually and no other means shall be permitted. (c) The quoted rate is inclusive of clamping on walls / pole if required (d) The earthwork will be measured and paid separately | ||||||||||
| 6.01 | (a) 4 Core x 10 sq.mm | 300 | RUNNIG METRE | 210 ₹63,000 | 168 ₹50,400 | 190 ₹57,000 | 210 ₹63,000 | 150 ₹45,000 Lowest | 200 ₹60,000 | 210 ₹63,000 |
| 6.02 | (b) 4 Core x 16 sq.mm | 200 | RUNNIG METRE | 230 ₹46,000 | 171 ₹34,200 | 225 ₹45,000 | 230 ₹46,000 | 170 ₹34,000 Lowest | 270 ₹54,000 | 248 ₹49,600 |
| 6.03 | (c) 3.5 Core x 25 sq.mm | 150 | RUNNIG METRE | 310 ₹46,500 | 230 ₹34,500 | 250 ₹37,500 | 240 ₹36,000 | 215 ₹32,250 Lowest | 340 ₹51,000 | 386 ₹57,900 |
| 6.04 | (d) 3.5 Core x 50 sq.mm | 150 | RUNNIG METRE | 550 ₹82,500 | 379 ₹56,850 | 350 ₹52,500 Lowest | 350 ₹52,500 Lowest | 355 ₹53,250 | 540 ₹81,000 | 498 ₹74,700 |
Tender Value
₹49.5 L
EMD Value
₹99,100
Closing Date
13 Aug 2025, 6:00 pmClosed
LT COL CHANDRAKANT JOSHI
DRDO Complex, CV Raman Nagar PO, Bangalore 560 093
REPLACEMENT OF EXISTING UG CABLES AND REPAIRS TO LT PANELS REPLACEMENT OF SMDB PANELS AND ALLIED CONNECTED WORKS AT DIBT MYSORE UNDER GE I R AND D EAST BANGALORE
2025_MES_713080_1
8622/E8
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
GE I R AND D EAST BANGALORE
CLASS D CATEGORY b(i)
8 documents required · 8 mandatory
₹500
Yes
GE I R AND D EAST BANGALORE
₹99,100
Yes
30 Sept 2025
18 Jul 2025
20 Aug 2025
18 Jul 2025
13 Aug 2025
1 Aug 2025
18 Jul 2025 - 31 Jul 2025
Amount
Excavation in trenches n.exc. 1.5m wide and n.exc. 1.5m in depth for laying cables / poles foundation / stay assembly and getting out in soft / loose soil all as directed by Engineer-in-Charge..
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc, 25cm thick all as specified and as directed by Engineer-in-Charge..
Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed.
Supply and spread dry river sand in trenches for cable cushioning all as specified on both top and bottom of cable including ramming all as specified and as directed. NOTE :- (a) Punned thickness will be considered for measurement purposes.
Supply and lay burnt brick sub class 'B' of standard size best quality locally available laid in trenches for cable protection all as specified and as directed.
Material and labour XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (heavy duty) with aluminium conductor, 1100 volts grade cross sectional area of following sizes complete all as directed. NOTE :- (a) The rate is inclusive of testing of cable at site after laying of cables in trenches/walls. (b) The cable may be laid manually and no other means shall be permitted. (c) The quoted rate is inclusive of clamping on walls / pole if required (d) The earthwork will be measured and paid separately
(a) 4 Core x 10 sq.mm
(b) 4 Core x 16 sq.mm
(c) 3.5 Core x 25 sq.mm
(d) 3.5 Core x 50 sq.mm
(e) 3.5 Core x 70 sq.mm
(f) 3.5 Core x 95 sq.mm
(g) 3.5 Core x 120 sq.mm
(h) 3.5 Core x 185 sq.mm
(j) 3.5 Core x 240 sq.mm
Cutting of road / PCC for laying of UG cables upto a length of 3 mtr complete further laying of cables through GI pipe and filling with PCC and making the surface smooth with the existing surface complete all as specified and directed. NOTE :- (a) The quoted rate is deemed to be inclusive of GI pipe of upto 100 mm bore (b) The cable shall be laid at depth of the same plane as that of the connected earth work (c) The sides of the GI pipe is required to be sealed properly to avoid moisture
Material and labour for detecting LT fault upto 0.433 KV through cable fault locator, finding the fault and excavating the earth at that particular location, removing the existing cable and preparing for fixing new cable joints and re laying of cables in the original position and return filling the earth work to make the surface smooth to mach with the existing surroundings complete all as specified and as directed. NOTE :- (a) Necessary labour for the earth work upto 10 mtr is deemed to be included in the above quoted rate. (b) Necessary LT Joints will be measured under separate item. (c) Contractor has to commence the job within 3 hrs from the job card he has received. On failing which, double the quoted rate will be recovered by the Accepting officer. (d) The quoted rate is deemed to be inclusive of the hiring of cable fault locator.
Supplying and making straight through cable end termination with cold jointing kit complete kit complete with all accessories including lugs suitable upto 95 sq.mm 3.5 core XLPE Aluminium conductor cable of 1.1 KV grade as required complete all as specified and as directed. Make : 3M / JENSON or equivalent
Taking down old serviceable cable of capacity upto 300 sq.mm and keeping it in safe custody and further re-laid in the existing trenches / Walls as directed and specified. NOTE : (a) The rate is inclusive of testing of cable at site after laying of cables in trenches / walls. (b) The cable may be laid manually and no other means shall be permitted. (c) The quoted rate is inclusive of Clamping on walls / pole if required (d) The earthwork will be measured and paid separately
Material and labour for scrapping out old wornout painted surfaces and painting with smoke grey epoxy paint of LT Panels complete all as specified and directed. NOTE :- (a) The quoted rate is deemed to be inclusive of labelling of the MCCBs on the LT Panel as per the existing model. (b) Shutdown for the Particular panel needs to be specified well in advance time (at least a week time)
Material and labour for repairing of the sheet metal enclosure of LT Panel complete through welding, screwing complete all as specified and as directed. NOTE :- (a) The quoted rate is inclusive of replacing of old sheet enclosure of upto 3.15 mm thick with new one as required. (b) Painting work will be measured and paid separately under relevant items.
Material and labour for cleaning of LT Panels, scrapping out mud, replacing of sleeves complete, tightening the lugs, insulating the wornout sleeves of cable / busbar with insulating tape complete including repairing of the sheet metal enclosure of LT Panel complete through welding, screwing complete all as directed and specified. NOTE :- (a) The quoted rate is inclusive of knobs, hinges and other locking arrangements required. (b) The quoted rate is deemed to be excluded the painting of the replaced sheet. (c) The LT Panels needs to be cleaned on every quarterly basis. (d) The quoted rate is inclusive of aluminium / copper lugs required. (e) The quoted rate is inclusive of multi stranded copper cable of upto 10 sq.mm (< 10 RM)
Supply and fix MCCBs with thermal magnetic release and terminal spreaders of following capacities in existing LT Panel including disconnecting and removal of old unserviceable one complete all as specified and as directed. NOTE :- (a) The MCCBs needs to be affixed in the existing mounting arrangement of the LT panel. Any modification required needs to be carried out by the contractor and the quoted rate is deemed to be inclusive of the same. (b) The existing makes of MCCBs in the area are Standard, Havells, Indo Asian, L&T. (c) The quoted rate is deemed to be inclusive of necessary cable links and cable lugs if required for connections.
(a) 4 Pole 400 Amps 36 KA
(b) 4 Pole 250 Amps 36 KA
(c) 4 Pole 200 Amps 36 KA
(d) 4 Pole 100 Amps 36KA
(e) 3 Pole 250 Amps 36 KA
(f) 3 Pole 200 Amps 36 KA
(g) 3 Pole 160 Amps 36 KA
(h) 3 Pole 125 Amps 36 KA
(i) 3 Pole 100 Amps 36 KA
(j) 3 Pole 63 Amps 36 KA
Supply and fix ON-Load Changeover of following capacities complete including removal of old un serviceable ones complete all as specified and as directed by Engineer-in-Charge. NOTE :-: (a) The Changeover needs to be affixed in the existing mounting arrangement of the LT Panel. Any modification required needs to be carried out by the contractor and the quoted rate is deemed to be inclusive of the same. (b) The existing makes of Changeover in the area are Standard, Havells, Indo Asian, L&T. (c) The quoted rate is deemed to be inclusive of necessary cable links and cable lugs if required for connections.
(i) Change over 400 Amps
(ii) Change over 250 Amps
Material and labour for servicing of Air circuit Breaker after disconnecting the cables checking the lever, its tripping mechanism complete and setting the tripping value as directed by Engineer-in-Charge. NOTE :- (a) The quoted rate is deemed to be inclusive of necessary cable links and cable lugs if required for connections.
Material and labour rolled mid steel as in cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of synthetic enamel paint of approved tint complete all as specified and as directed.
Supply and fix rectangular SMC junction box of size 240 x 130 x 110mm, shock proof and rust proof, Rot-proof and termite resistant, cable entry from bottom and/ or sides, 100% weather proof having pole mounting arrangement for street lights / boundary lights complete all as specified and as directed.
Supply and fix rectangular SMC Junction box of size 140 x 140 x 95mm, shockproof and rustproof, Rot-proof and termite resistant Cable entry from bottom and/ or sides, 100% weatherproof having pole mounting arrangement for Garden Light complete all as specified and as directed. NOTE :- (a) The box needs to be affixed in the existing mounting arrangement. Any modification required needs to be carried out by the contractor and the quoted rate is deemed to be inclusive of the same.
Material and labour service wire (copper) 3 core 1.5 sqmm complete all as specified and as directed by Engineer-in-Charge.
Material and labour service wire (copper) 3 core 2.5 sq mm complete all as specified and as directed by Engineer-in-Charge.
Material and labour service wire (copper) 4 core 10 sqmm complete all as specified and as directed by Engineer-in-Charge.
Supply and fix SMDB of capacity upto 250 Amps, double door 4 way - main enclosure (with a provision to mount TP MCCBs as an outgoing) with degree of protection IP-43 complete all as specified and as directed. NOTE :- (a) The quoted rate is deemed to be inclusive of necessary cable links and cable lugs if required for connections. (b) The quoted rate is deemed to be inclusive of necessary brick work and plaster to match with the existing surface complete if required.
Supply and fix SMDB of capacity upto 250 Amps, double door 6 way - main enclosure (with a provision to mount TP MCCBs as an outgoing) with degree of protection IP-43 complete all as specified and as directed. NOTE :- (a) The quoted rate is deemed to be inclusive of necessary cable links and cable lugs if required for connections. (b) The quoted rate is deemed to be inclusive of necessary brick work and plaster to match with the existing surface complete if required.
Supply and fix SMDB of capacity upto 250 Amps, double door 12 way - main enclosure (with a provision to mount TP MCCBs as an outgoing) with degree of protection IP-43 complete all as specified and as directed. NOTE :- (a) The quoted rate is deemed to be inclusive of necessary cable links and cable lugs if required for connections. (b) The quoted rate is deemed to be inclusive of necessary brick work and plaster to match with the existing surface complete if required.
Material and labour Aluminium Bus bar with sleeves (of suitable colour) and of suitable size including removal of old worn out bus bar complete all as specified & as directed. NOTE :- (i) Necessary nut bolt/fasteners & drilling of holes as required deemed to be included in the quoted rate. (ii) For measurement purpose weight of busbar needs to be certified by Engineer-in-Charge at site. The necessary weight measuring equipments needs to be supplied by the contractor as and when directed at site on no cost basis so as to facilitate proper and prompt response.
Supply and fix LT Cable Route indicator made up of MS with dimensions upto 100 mm dia (approx) and embedded letters ".433 KV LT MES" of all as per specified and as directed.
Material and labour for Painting of existing Steel Pole by applying one coat of red oxide primer and two coat of silver metal paint complete all as specified and as directed.
Material and labour for Painting of existing concrete pole by applying two coat of enamel paint (same as existing) complete all as specified and as directed.
Comprehensive maintenance of Automatic Power Factor Correction Panels ( APFC ) at various sub stns of different capacities and comprising of following works :- (i) Repair / maintenance of Contactors, Relays and Capacitors, MCCBs & MCBs provided in the APFC Panel (ii) Calibration of effective management of power factor correction near to unity as per the variation of load in the corresponding transformer in terms of serviceability of MCCB/MCBs, Contactors, Capacitors and Relay and display unit including the following Technical services:- NOTE : (i) The Contractor will responsible for maintaining the power factor near to unity on individual APFC Panels and overhaul the value at main Receiving Stn . Contractor will responsible for, the penalty/ compensation charges which charged by CESC, due to Low Power factor and same amount should be paid by the contractor from his own account. The above quoted rate is inclusive of all regarding to maintain the APFC Panel power factor. (ii ) The Capacitors, Contactors, Relays, MCCB replaced will be measured and Paid separately under relevant items. (iii) Labour charges for dismantling / taking down and replacement / refixing new parts as and when required is deemed to be included in unit rate quoted.
Supply only APFC relay 8 stage make L & T model No. eta CON L8 or equivalent
Supply only capacitor heavy duty type MPP of rating 5 KVAR 440V, 50Hz, AC cylindrical type complete all as specified and as directed. Model : PHICAP
Supply only capacitor heavy duty type MPP of rating 10 KVAR 440V, 50Hz, AC cylindrical type complete all as specified and as directed. Model : PHICAP
Supply only capacitor heavy duty type MPP of rating 20 KVAR 440V, 50Hz, AC cylindrical type complete all as specified and as directed. Model : PHICAP
Supply only MCCB 315 Amps, 4 pole,with adjustable thermal magnetic release, rupturing capacity 36 KA, 415 Volts including taking down unserviceable MCCB complete all as specified and as directed.
Supply only LED indicating Push Button as per existing panels all as specified and directed.
Material and labour Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-31 (9 metres long) complete all as specified and as directed. NOTE :- (i) The quoted rate deemed to be inclusive of painting of pole. (ii) Earthwork will be paid and measured under relevant items
Material and labour for foundation filling and mass concrete for stay/ poles by plain cement concrete 1:4:8 type D2 using 40mm graded stone aggregate complete all as specified and as directed.
Material and labour for coping of pole by plain cement concrete 1:2:4 type B1 using 20mm graded stone aggregate complete all as specified and as directed.
Supply and fix Solar LED light fitting of 20W all in one with Hybrid comprising of smart integrated solar street light with built in mono crystalline panel, Lithium Ferro Phosphate battery, MPPT charge controller and PIR sensor with colour temperature 6000-6500K, 7.0 mtr long Hot Dip galvanised Octagonal pole all as specified and directed by Engineer-in Charge. Make : BAJAJ / HAVELLS / PHILIPS / CROMPTON NOTE : (i) Necessary test , warranty certificates for various components like battery, module, light fitting etc needs to be submitted by the Contractor. (ii) The quoted rate deemed to be inclusive of necessary foundation and coping with necessary cement concrete for erection of pole. (iii) The quoted rate deemed to be inclusive of necessary foundation bolts as suitable required for mounting of pole.
Comprehensive maintenance, servicing and checking the connections and terminal of AMF panel (for 250 KVA DG Set), finding the fault, servicing complete including replacement of unserviceable spares and testing complete for manual and Auto operations all as directed. NOTE :- (a) Necessary spray and other T&P equipments are deemed to be inclusive in the above quoted rate. (b) All the Spares as and when required for replacement are deemed to be included in the above quoted rate (c) Labour charges for dismantling / taking down and replacement / refixing new parts as and when required is deemed to be included in unit rate quoted. (d) The contractor needs to complete the job within a period of 12 Hrs from the time of receiving the complaint from JE (E/M) telephonically failing which a half the quoted rate will be recovered. (e) For the calculation purpose, one job will be measured when contractor fully certified that DG will automatically on / off whenever the power supply from KEB goes off and on.
Comprehensive maintenance, servicing and checking the connections and terminal of AMF panel (for 500 KVA DG Set), finding the fault, servicing complete including replacement of unserviceable spares and testing complete for manual & Auto operations all as directed. NOTE :- (a) Necessary spray and other T&P equipments are deemed to be inclusive in the above quoted rate (b) All the Spares as and when required for replacement are deemed to be included in the above quoted rate (Except power Contactor) (c) Labour charges for dismantling / taking down and replacement / refixing new parts as and when required is deemed to be included in unit rate quoted. (d) The contractor needs to complete the job within a period of 12 Hrs from the time of receiving the complaint from JE (E/M) telephonically failing which a half the quoted rate will be recovered. (e) For the calculation purpose, one job will be measured when contractor fully certified that DG will automatically on / off whenever the power supply from KEB goes off and on.
Neptune Engineers and Builders (BID ID -3381299)
M/S - KRUPA ELECTRICALS (BID ID -3383343)
TECKXPERT ENTERPRISES (BID ID -3384187)
B5BUILDING SOLUTIONS (BID ID -3388570)
Shiva Shakthi Electrical Enterprises (BID ID -3385038)
GURU ENTERPRISES (BID ID -3383572)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .