Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.8 CrAccepted-AOC 548 C 259 CHANDRODAYA NAGAR DEOPUR PARA LUCKNOW 226017 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226017 | ₹2.8 Cr Quoted ₹3.0 Cr | L1 | Accepted-AOC lowest bidder |
| 2 | L2₹3.0 Cr+₹3.8 L (1.28%)Rejected-Finance SHALABH HOUSE 490 PURANI TEHSIL ROORKEE DISTT HARIDWAR | HARIDWAR | UTTARAKHAND | 247656 | ₹3.0 Cr+₹3.8 L (1.28%) | L2 | Rejected-Finance Other than L1 |
| 3 | L3₹3.0 Cr+₹8.1 L (2.73%)Rejected-Finance CHANDAN NAGAR OPP IOCL PERTROL PUMP RAMPUR ROAD BAREILLY UP 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | ₹3.0 Cr+₹8.1 L (2.73%) | L3 | Rejected-Finance Other than L1 |
| 4 | L4₹3.2 Cr+₹26.2 L (8.87%)Rejected-Finance 274 A 5TH LANE NISHATGANJ LUCKNOW UP PIN 226007 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226007 | ₹3.2 Cr+₹26.2 L (8.87%) | L4 | Rejected-Finance Other than L1 |
| 5 | L5₹3.3 Cr+₹30.2 L (10.2%)Rejected-Finance 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | ₹3.3 Cr+₹30.2 L (10.2%) | L5 | Rejected-Finance Other than L1 |
Tender Value
₹3.5 Cr
EMD Value
₹4.2 L
Closing Date
27 Jun 2022, 6:00 pmClosed
CE Lucknow Zone Lucknow
HQ CE Lucknow Zone, 17, cariappa marg, Lucknow 226002
PROVN OF CONVERSION OF OH LINES TO UG CABLE AND IMPROVEMENT OF EXTERNAL ELECTRIFICATION AT VARANASI CANTT
2022_MES_525878_1
CELZ/VAR/T-07 of 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Varanasi
As per tender Documents
8 documents required · 8 mandatory
₹2,000
GE (East) Allahabad
₹4.2 L
27 Aug 2022
24 May 2022
29 Jun 2022
24 May 2022
27 Jun 2022
14 Jun 2022
Amount
M&L for taking down old unserviceable aluminium over head conductor including cross arms and insulators of any type/size from existing LT/HT poles and deposting to MES store yard complete all as specified and directed.
Dismantling cross arms of M.S. channel or angle sections etc. complete and setting aside within 50m complete all as specified and directed.
Dismantling insulators any type, any size complete all as specified and directed.
Dismantling stay assembly complete complete all as specified and directed. (demolition of concrete, etc. and excavation measured separately)
Dismantling steel poles/ struts, any size transporting to store and within 50 metres stacking complete all as specified and directed.
Taking down old unserviceable UG cable of any size complete all as specified and directed.
Supply, laying and testing cable with cable gland, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of sizes 25 sq mm 4 core complete all as specified and directed.
-ditto-- all as per item No 7 of above but size 50 sq mm 3½ core
-ditto-- all as per item No 7 of above but size 70 sq mm 3½ core
-ditto-- all as per item No 7 of above but size 120 sq mm 3½ core
-ditto-- all as per item No 7 of above but size 150 sq mm 3½ core
-ditto-- all as per item No 7 of above but size 240 sq 3½ core
-ditto-- all as per item No 7 of above but size 10 sq mm 4 core
M&L for excavation in trenches soft/loose soil n exc 1.5 m wide and n exc1.5m in depth and getting out including filling bottom surface to required level or slope for laying of pipes/cables etc. complete all as spcified and directed .
M&L for returning, filling in, including spreading, leveling, watering and well rammings in layers not exceeding 25 cm in soft /loose soil complete all as specified and directed
M&L for removing of surplus excavated soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 m above the starting point in soft /loose soil complete all as specified and directed.
Supply and laying dry local sand for sand cushioning for protecting under ground cable (8 cm below and 15 cm after laying cable) laying in trenches including punning the sand upto 18 cm thick and consolided complete all as specified and directed.
Supplying and laying reinforced precast concrete cable cover ISI marked, class LV, type 1 flat with peak, size 250mm x 150mm x 40mm complete all as specified and directed.
Supplying and laying reinforced precast concrete cable cover ISI marked, class HV, type 1 flat with peak, size 300mm x 180mm x 40mm complete all as specified and directed.
Supply and fixing GI pipe 80 mm,light grade ISI marked including all fittingssuch as bends,Tees,sockets etc fixed on walls/poles or laid in trenches under road crossing/hard standing including taking down old/unserviceble existing pipe complete all as specified and directed.
Supply and fixing GI pipe 50 mm,light grade ISI marked including all fittingssuch as bends,Tees,sockets etc fixed on walls/poles or laid in trenches under road crossing/hard standing including taking down old/unserviceble existing pipe complete all as specified and directed.
Supply and fixing GI pipe 40 mm,light grade ISI marked including all fittingssuch as bends,Tees,sockets etc fixed on walls/poles or laid in trenches under road crossing/hard standing including taking down old/unserviceble existing pipe complete all as specified and directed.
Supply , installation and testing of factory made,CPRI Approved cubical outdoor (Kiosk) type feeder pillar box double door, 415 volt, 4 wire, AC 50 Hz, made out of 3.15 mm thick CRCA sheet , weather and vermin proof apoxy powder coated bothside(interior & exterior)front openable with locking arrangement for outdoor mounting with having degree of protection as per IP-56 complete factory lock two earth terminal suitable cable gland for all incoming and outgoing and removable neutral link, connecting strip/solid conductor brought out to cable chamber brass/copper nut, bolts/washer etc including grouting of feeder pillar box 60 cm above ground level including suitable size angle iron stand made up of 65 x 65 x 6 mm welded on all the four corner embedded in PCC 1:2:4, type B-1 (using 20 mm graded crushed stone aggregate) upto 30 cm including excavation and earth work complete with following asseccories :- (a) Aluminium insulatd busbar high conductivity 300 Amp rated 3 phase including neutral bus bar 300 Amp complete - 01 No. Incoming :- (b) MCCB 4 pole 250 Amp, 415 Volt, breaking capacity 36 KA, 50 HZ with thermal magnetic release - 01 No. Outgoing :- (c) MCCB 4 pole 63 Amps breaking capacity 10KA, 50 HZ - 08 Nos. (d) Digital multifunction meter M 4410 with CT - 01 No. (e) Indicating light LED type RYB - 01 Set. (f) Heavy duty connector 4 pole 63 amp breaking capacity 10KA, 50 HZ - 08 Nos.
Supply , installation and testing of factory made,CPRI Approved cubical outdoor (Kiosk) type feeder pillar box 415 volt, 4 wire, AC 50 Hz, made out of 3.15 mm thick CRCA sheet , weather and vermin proof powder coating finish bothside(interior & exterior) for outdoor mounting with having degree of protection as per IP-56 complete factory lock two earth terminal suitable cable gland for all incoming and outgoing and removable neutral link, connecting strip/solid conductor brought out to cable chamber brass/copper nut, bolts/washer etc including grouting of feeder pillar box 60 cm above ground level including suitable size angle iron stand made up of 65 x 65 x 6 mm welded on all the four corner embedded in PCC 1:2:4, type B-1 (using 20 mm graded crushed stone aggregate) upto 30 cm including excavation and earth work complete with following asseccories (For street lighting) :- (a) Aluminium insulatd busbar high conductivity 200 Amp rated 3 phase including neutral bus bar complete - 01 No. Incoming :- (b) MCCB 4 pole 160 Amp, 415 Volt, breaking capacity 25 KA, 50 HZ with thermal magnetic release - 01 No. Outgoing :- (c) MCCB 4 pole 63 Amps breaking capacity 10KA, 50 HZ - 02 Nos. (d) MCB 2 - pole 40 Amps breaking capacity 10KA, 50 HZ - 3 Nos. (e) 3 phase 415V Programmable astronomical timer switch with heavy duty contactor 3 pole 32 A-01 (f) Indicating light LED type RYB - 01 Set. (g) Heavy duty polymer/porselene connector 40 A block 03 Way - 3 Nos (h) Heavy duty polymer/porselene connector 4 pole 63 Amp block 03 Way - 2 Nos (j) Digital multifunction meter M 4410 with CT - 01 No.
Supply , installation and testing of factory made, CPRI Approved cubical outdoor (Kiosk) type feeder pillar box double door, 415 volt, 4 wire, AC 50 Hz of size 1.2 mtr X 1.2 mtr X 0.6 mtr, made out of 3.15 mm thick CRCA sheet , weather and vermin proof apoxy powder coated bothside(interior & exterior)front openable with locking arrangement for outdoor mounting with having degree of protection as per IP-56 complete factory lock two earth terminal suitable cable gland for all incoming and outgoing and removable neutral link, connecting strip/solid conductor brought out to cable chamber brass/copper nut, bolts/washer etc including grouting of feeder pillar box 60 cm above ground level including suitable size angle iron stand made up of 65 x 65 x 6 mm welded on all the four corner embedded in PCC 1:2:4, type B-1 (using 20 mm graded crushed stone aggregate) upto 30 cm including excavation and earth work complete with following asseccories :- (a) Aluminium insulatd busbar high conductivity 600 Amp rated 3 phase including neutral bus bar complete - 01 No. Incoming :- (b) MCCB 4 - pole 400 Amps breaking capacity 35KA, 50 HZ - 01 Nos. Outgoing :- (c MCCB 4 - pole 160 Amps breaking capacity 25KA, 50 HZ - 4 Nos. (d) Digital multifunction meter M 4410 with CT - 01 No. (e) Indicating light LED type RYB - 01 Set.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured,earthed electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 95 sq mm x 3 Core complete all as specified and directed.
M & L for Earthing complete with galvanised steel earth plate electrode 60X60cmX6mm thick , buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level , connectred to galvanised lead wire 4.00 mm dia by means of nuts, bolts, washer of GI steel as shown on electrical plant No 3 of MES schedule part I connected to earthing test point and testing on completion with including necessary excavation and earth work, earth electrode, earthing lead from electrode to equipment/substantion, adequate quantity of charcoal dust and common salt, test point, PCC 1:3:6 type C-I (using 20mm graded black trap/granite/basalt stone aggregate) for earth pit with 40x40x6mm mild steel angle iron frame for cover ,precast RCC 1:2:4 type B-I (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 6 mm dia bars 3 Nos both way with 12mm dia round bar handle , GI light grade earth lead protection pipe 15 mm bore 7.5 mtr long from the top of earth electrode and GI pipe 20 mm bore for watering pipe are deemed to be included under this item and additional earth lead, if any, required at site shall be measured and paid for separately under appropriate item of schedule “A” complete including testing on completion all as specified and directed.
M&L for Earthing complete with galavanised copper plate electrode 60x60cmx3.15mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.25 mtr below normal ground level, connected to copper 32x6mm earth strip by means of nuts, bolts, washer of GI steel as shown on electrical plant No 3 of MES schedule part I connected to earthing test point and testing on completion with including necessary excavation and earth work, earth electrode, earthing lead from electrode to equipment/substantion, adequate quantity of charcoal dust and common salt, test point, PCC 1:3:6 type C-I (using 20mm graded black trap/granite/basalt stone aggregate) for earth pit with 40x40x6mm mild steel angle iron frame for cover ,precast RCC 1:2:4 type B-I (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 6 mm dia bars 3 Nos both way with 12mm dia round bar handle , GI light grade earth lead protection pipe 40 mm bore 7.5 mtr long from the top of earth electrode and GI pipe 20 mm bore for watering pipe are deemed to be included under this item and additional earth lead, if any, required at site shall be measured and paid for separately under appropriate item of schedule “A” complete including testing on completion all as specified and as directed.
Supply and fixing HT 11 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting rotating type complete with drop out fuse having 12 insulators of rating upto 200 Amps
Supply and fixing cable jointing kit for 1.1 KV grade cable end termination joint complete with Jointing material cold Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 25 to 50 sqmm,Indoor/outdoor type complete all as specified and directed.
Supply and fixing cable jointing kit for 1.1 KV grade cable for cable end termination joint complete with Jointing material cold Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured,Aluminium conductor cable of size 70 to 90 sqmm,Indoor/outdoor type complete all as specified and directed.
Supply and fixing cable jointing kit for 1.1 KV grade cable for cable end termination joint complete with Jointing material cold Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminiumconductor cable of size 120 to 150 sq mm.,Indoor/outdoor type complete all as specified and directed.
Supply and fixing cable jointing kit for 1.1 KV grade cable for cable end termination joint complete with Jointing material cold Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 185 to 240 sq mm.,Indoor/outdoor type complete all as specified and directed.
Supply and fixing cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 50 Sqmm to 95 sqmm, Indoor/outdoor type complete all as specified and directed.
Supply and fixing cable jointing kit for 11 KV grade cable for out door termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 50 Sqmm to 95 Sqmm complete all as specified and directed.
Supply and installation of 11 KV single phase in door resin cast CT of ratio 400/5-5A class 1.0/ 5P10,burden 15VA – 15 VA complete all as specified and directed.
Supply and installation of 11 KV single phase in door resin cast PT of ratio 11 KV/rt3/110 V/rt3/110V/rt3,Class 0.5-3, Burden 50 VA – 50 VA complete all as specified and directed.
Supply and errection of steel tubular pole swaged type 410-SP 31(9.0m long pole) as per IS:2713 (part I to III) 1980 complete with cast iron base plate, pole cap, mild steel bolt, nuts and screws complete including dismantling of exsiting pole all as specified including consisting of following works:- (a) Excavation in trenches not exceeding 1.5 mtr wide & 1.57 mtr deep for pole foundation & getting out in soft/loose soil, returning filling in the excavated of soil after fixing the pole in foundation ramming earth around in layer not exceeding 25 cm thick and disposal of surplus soil to a distance not exceeding 50 mtrs complete all as specified and directed. (b) M&L for PCC 1:4:8, type D2 (using 40mm graded crushed stone aggregate) in foundation 900mmx600mm cross section and planting depth 1.5 mtr for concrete encasing the pole upto GL complete all as specified and directed. (c) M&L for providing PCC 1:3:6, type C-1 (using 20mm graded crushed stone aggregate) for plinth block/collar above GL 500mm high and 450mm dia complete all as specified and directed. (d) M&L for painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminium paint over a coat of red oxide primer including preparation of surface including painting of 30 cm wide bands 3 Nos with synthetic enamel paint of appropriate colour in alternate layer upto the height of 1.5mm above plinth block. (e) M&L for writing letter or figures (Block Roman, Italic as Indian) with thick synthetic enamel paint of apprised shade not exceeding 5 cm height including numbering of pole complete all as specified and directed. NOTE : Manufacture's test certificate will be produced before execution work.
Supply and fixing LED street light luminaires 90 watt with pressure aluminium die-cast powder coating housing and frame with heat resistant, high efficiency, toughned glass with EPDM gasket for IP66 protection, complete assembly with LED, driver and accessories pre-wiredup to terminal block, including connection on pole or building, including taking down of old / unserviceble street light fitting, complete all as specified and directed.
M & L for cross arm ,bracing supports, clamps, back plates fabricated from structural steel section including nuts, bolts and washers welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive one primer coat of red oxide, one under coat and one finishing coat of synthetic enameled paint complete all as specified and directed.
M & L for for bore hole for passing cable through / insertion of 80/50/40 mm dia GI pipe under PCC road/ taxi track/ runway/ hard standing not less than 1200 mm deep complete all as directed. NOTES :- (i) Cost of equipments, tools & plants, material required for boring shall be deemed to be included in unit quoted rates above. (ii) Cost of GI pipe80/50/40 mm dia shall be deemed to be included in quoted rates above measured and paid Separately.
S & F HT cable route marker(metal type ) of 2 feet height MS flat with 3mm thickness welded with 100 mm dia x 3mm thick rounded MS sheet on top with inscription thereon ,fixing the same on ground as required complete all as specified and directed.
S & F LT cable route marker(metal type ) of 2 feet height MS flat with 3mm thickness welded with 100 mm dia x 3mm thick rounded MS sheet on top with inscription thereon ,fixing the same on ground as required complete all as specified and directed.
M & L for Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP- 55 ( 11 meters long) with following work :- (a) Excavation in trenches not exceeding 1.5 mtr wide & 1.80 mtr deep for pole foundation & getting out in soft/loose soil, returning filling in the excavated of soil after fixing the pole in foundation ramming earth around in layer not exceeding 25 cm thick and disposal of surplus soil to a distance not exceeding 50 mtrs complete all as specified and directed. (b) M&L for PCC 1:4:8, type D2 (using 40mm graded crushed stone aggregate) in foundation 900mmx600mm cross section and planting depth 1.5 mtr for concrete encasing the pole upto GL complete all as specified and directed. (c) M&L for providing PCC 1:3:6, type C-1 (using 20mm graded crushed stone aggregate) for plinth block/collar above GL 500mm high and 450mm dia complete all as specified and directed. (d) M&L for painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminium paint over a coat of red oxide primer including preparation of surface including painting of 30 cm wide bands 3 Nos with synthetic enamel paint of appropriate colour in alternate layer upto the height of 1.5mm above plinth block. (e) M&L for writing letter or figures (Block Roman, Italic as Indian) with thick synthetic enamel paint of apprised shade not exceeding 5 cm height including numbering of pole complete all as specified and directed. NOTE : Manufacture's test certificate will be produced before execution work.
Supplying, installation, testing & commissioning of 11 KV RMU, 630 Amps, 21kA/3s, outdoor Non extensible SF6 gas insulated floor mounted Compact Switchgear with copper bus bar consisting of 02 Nos incoming and 01 Nos outgoing motor operated draw out type VCBs, 8DJHST Type: LLL+ME . All live parts, bus bars, VCB will be enclosed in robotically welded 2.5/3 MM thick non ferrite non magnetic stainless steel tank filled with SF6 at 1.4 bar with IP class IP67, leak rate less than 0.1% and tested for Internal arc 21kA/0.1 sec as per latest IEC 62271-200 complete all as specified and directed. The unit shall include the following with all necessary standard fitting required at site.
i) “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings.
ii) Removable front door with locking arrangement to avoid unauthorized access
iii) R Y B Phase indication
iv) Rated Voltage - 12kV Rated power frequency withstand voltage - 28kV Rated lightning impulse withstand voltage - 75kV
v) Rated current for Ring main feeder - 630A @ 40Deg // 600 @ 45DegC // 565A @ 50Deg C
vi) Rated current for VCB feeder - 630A @ 40Deg // 600 @ 45DegC // 565A @ 50Deg C
vii) Rated short-time current (Ik)- 21kA / 3 Sec
viii) Rated short making current - 52.5kA
ix) Ambient temperature - 40 Deg Internal arc rating/classification- 21KA/0.1s
x) Busbars :Copper SF6 Gas insulated
xi) Stainless Steel sheet thickness for SF6 gas tank: As per Type tested Design
xii) Material & Sheet thickness for outer enclosure: CRCA of thickness minimum 2.5 mm
xiii) Paint Shade / Procedure / Paint Layer thickness : RAL 7032 / 7tank powder coating process / 100 + 25 Micron
A) Each Vacuum Circuit Breaker (L) includes
i) Motor operated Operating mechanism of VCB with position ON-OFF:
ii) Operating duty: O-3min-CO-3min-CO, Maximum No of operations at full STC: upto 20operations
iii) VCB Auxiliary switch with 2NO+2NC+2CH
iv) Operating mechanism for Disconnector ON - OFF: Motor
v) Operating mechanism for Earth switch OFF - EARTH: Manual
vi) Fixed type Capacitive Voltage Indicator (CVI) - Leelen make
vii) 1 no CT operated low energy release
viii)3 nos LV Current transformer- CTR 200-100/1A, 1-5P10, 2.5VA
ix) Self Powered Relay having protections (50,51, 50N, 51N) C&S CSDPR-V2
x) Padlocking Facility to avoid unauthorized access
xi) Cable Cover standard with Interlocking Provision for connecting 1R X 3C 95 sqmm cable
xii) 2X12 V Battery with battery charger with suitable burden for motor operation. Input 230 V AC & Output 24 V DC.7 AH Battery make : EXIDE
xiii) Green(ON)/Red(OFF) push buttons to operated VCB
B) Bus Connected PT Unit -1 No for Metering consisting of following
i) 3nos - 11KV/sqrt3/110V/sqrt3/110/3, Cl. 1.0, 50VA, 3P, 50VA
ii) Digital multifunction meter EM6400
iii) 1set indicating Lamps R,Y,B, Thermostat, Space Heater, 2pin plug & socket
iv) Digital Ammeter and Digital Voltmeter
C) Common Accessories including following
i) 1 no-Manometer without contacts for SF6 gas low indication
ii) 1 no - Operating handle
iii) 1 set - Cable boots per feeder to terminate upto 1R X 3C 95 sqmm per feeder
FACTORY INSPECTION :- A factory inspection program will be scheduled by contractor before supply of RMU and no extra cost admissible on this account. Before supply of RMU contractor shall inform to Accepting officer through GE for factory inspection and the representative of Accepting officer shall visit the factory to ascertain the quality of RMU.
Supply and fix power factor improvement single phase static 12 KV capacitor 300 KVAR per phase with automatic Power Factor Correction (APFC) Panel suitable for HT 11 KV 3 Phase, 50 Hz system complete all as specified and directed. The unit shall include the following with all necessary standard fitting required at site.
Voltage rating 11 (+10%) kV
Frequency 50 (+5%) Hz Ambient Temperature 50 deg C
Short circuit fault level 25/1 kA/sec
Seismic Zone Zone II
System earthing Earthed through Resistor
11 KV, 300 KVAR per phase, switched metal enclosed capacitor bank
12.65 KV, 300 KVAR( per phase) APFC with 0.2% reactors with 4 Step rating 2x 100 KVAR+2x50 KVAR. The APFC System shall comprise of the following Subsections.
A) Main Incomer Panel- Indoor (ACU)
B) Outdoor Panel
APFC Panel shall be metal enclosed, free standing, floor mounted suitable for outdoor installation with IP-55 ingress protection. The APFC System shall comprise of the following Subsections.
a) Main Incomer
3 nos. of 12 kV, 10KA, Class-III, single pole, FRP type Lightning Arrestors.
1 no. 11kV, 200A, 25kA/1sec, 3-Ph, 50Hz, Manually operated single break, panel mounted isolator with earth switch
1 no. 11 kV, 2 Core, 0.5/3PR, indoor resin cast type RVT suitable for unbalance protection mounted in panel.
Enclosure Details
Simplex type, free standing CRCA cubicle with epoxy based powder coated paint (shade RAL 7032).
All openings, covers, doors shall be provided with self-adhesive neoprene type beading.
Outdoor panel with IP55 protection.
Enclosure at all sides are of 3.0 mm thickness. Method of cable entry is bottom- 3mm removable aluminum gland plate for power cable and control cable.
Enclosure lighting.
Base frame of minimum 75mm ISMC channel (black).
Tinned copper earth bus bar running through entire panel.
FACTORY INSPECTION :- A factory inspection program will be scheduled by contractor before supply of APFC Panel and no extra cost admissible on this account. Before supply of APFC Panel contractor shall inform to Accepting officer through GE for factory inspection and the representative of Accepting officer shall visit the factory to ascertain the quality of APFC Panel.
Supply and installation,testing and commissioning of HT 11 KV, 3 phase, 50 Hz ,totally enclosed metal clad switchgear complete with Vacuum circuit breaker having rupturing capacity upto 350 MVA , overload and earth fault protection, ammeter, voltmeter and of rating upto 630 Amp complete all as specified and directed. The unit shall include the following with all necessary standard fitting required at site.
i) Vaccum circuit breaker fitted with vaccum interrupters, triple pole metal clad indoor type , totally enclosed & fully interlocked draw out type VCB as per IEC 62271-100/200/IS 13118 including coupling with existing VCBs with new coupling arrangement all as specifed and directed.
ii) Single break trip breaker with motor operated spring charged mechanism,mounted on a truck carriage/ cassette, complete with self contained operated fully interlockedrack in & Rack out mechanism ON /OFF Indicator with hand trip device
iii) Spring operated Motor(230 V AC ) shunt trip coil (30V DC) & Auxillary switch of 4 NO + 4 NC, manually operated spring closing mechanism complete auxillary switches trunk type with ON/OFF indicator of rupturing capacity of 350MVA and rating up to 630 Amp as mentioned with one set of triple pole IDMT numerical relay with three overcurrent relay 50% to 200 % in step of 25 % in range of 5 amps and one ,earth fault relay 20 % to 80% in steps of 10% range 5 Amps
iv) Fully compartmentalised sheet steel enclosure floor mounting type with automatic safety shutters,independent pressure discharge flaps with heat shrinkable PVC sheeves.
v) The system shall be 11 KV ,630 Amps ,18.4 KA for 3 sec and incomer cum outgoing feeder with line PT
vi ) Degree of protection shall be IP 42
vii) Equipment shall be horizontal draw out horizontal isolation
FACTORY INSPECTION :- A factory inspection program will be scheduled by contractor before supply of VCB and no extra cost admissible on this account. Before supply of VCB contractor shall inform to Accepting officer through GE for factory inspection and the representative of Accepting officer shall visit the factory to ascertain the quality of VCB.
SHALABH INDIA INDUSTRIES
BHARAT ELECTRICAL TRADERS
M/S S.B. Singh and Sons
GUPTA ENGINEERING WORKS
DEORA ELECTRIC WORKS
UMESH TRADERS
SAGGI ELECTRIC COMPANY
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .