Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.2 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹26.6 L+₹16,550 (0.63%)Rejected-Finance SADASHIV PHUGE NAGAR OPP SANDVIK FACTORY RADHIKA RESIDENCY F WING FLAT NO 7 PHUGEWADI PUNE 411 012 | PUNE | MAHARASHTRA | 411012 | L2 | Rejected-Finance not being lowest | |
| 3 | L3₹26.9 L+₹46,340 (1.76%)Rejected-Finance GATE NO 454 01 TAPKIR NAGAR PUNE NASIK HIGHWAY NEAR GANDHARV NAGARI MOSHI PUNE 412 105 | PUNE | MAHARASHTRA | 412105 | L3 | Rejected-Finance not being lowest | |
| 4 | L4₹27.9 L+₹1.5 L (5.86%)Rejected-Finance | L4 | Rejected-Finance not being lowest | |
| 5 | L5₹28.5 L+₹2.1 L (7.94%)Rejected-Finance | L5 | Rejected-Finance not being lowest |
Tender Value
₹36.0 L
EMD Value
₹71,960
Closing Date
25 Aug 2023, 6:00 pmClosed
Garrison Engineer (CME) Khadki
Garrison Engineer (CME) Khadki, Phugewadi, Dapodi, Kendriya vidyalay Gate , beside Unlimited (Mega Mart) Mall, Pune - 411 012
Special repair to conversion of overhead LT conductor to underground LT conductors cable in front of MD accn (near MT lane) at CME
2023_MES_609915_2
8452/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer (CME) Khadki
Class D, b(i)
9 documents required · 9 mandatory
₹500
Yes
Garrison Engineer (CME) Khadki
₹71,960
Yes
28 Oct 2023
18 Aug 2023
28 Aug 2023
18 Aug 2023
25 Aug 2023
19 Aug 2023
Amount
Dismantling of ACSR or AAC conductors and removing old material from site for taking credit all as directed.
Dismantling of concrete poles/struts of any size and removing old material from site for taking credit and making good the disturbed surfaces all as specified/directed by Engr-in-Charge
Dismantling of insulators any type, any size and removing old material from site for taking credit all as directed.
Dismantling of cross arms of MS channel or angle sections etc complete and removing old material from site for taking credit all as directed.
Dismantling of stay assembly complete demolition of concrete etc and removing old material from site for taking credit all as directed.
Demolition of cement concrete unreinforced of any description and in any position not otherwise specifically provided for all as directed by Engr-in-Charge
M&L cement concrete in foundation, filling and mass concrete type D2 (1:4:8) 40mm graded stone aggregate all as specified and directed by Engr-in-Charge
Excavation in trenches n exc 1.5m wide and n exc 1.5m deep and making good surface for laying /removing of cable all as specified and directed by Engr in charge as in
Soft/loose soil
Hard/dense soil
Soft/disintegrated rock.
Returning filling in excavated soil in trenches, watering and well ramming in layers n exc 25 cm complete all as specified and directed.
Removal of surplus excavated spoil to distance n exc 50 metre and depositing where directed at level not exceeding 1.5 m above the starting point all as specified and directed
M & L for bituminous road cutting to a width of 45 cm and depth 50 cm for laying of pipe for laying of UG cables and making good with PCC (1:3:6) type C1 (using 20mm graded stone aggregate) all as specified and directed.
Supplying and laying GI tubing light grade of size 40mm dia bore for encasing cables for mechanical protection , laid under Plinth / Floors/ Paths /Culverts or fixed on wall or concealed in wall/floor or along poles or as street light poles or as street light mounting bracket with complete accessories such as bends/sockets/reducers/saddles incl necessary threading/drilling works all as specified and directed by Engr-in-charge.
Supplying and laying GI tubing light grade of size 50mm dia bore for encasing cables for mechanical protection , laid under Plinth / Floors/ Paths/ Culverts or fixed on wall or concealed in wall/floor or along poles or as street light poles or as street light mounting bracket with complete accessories such as bends/sockets/reducers/saddles incl necessary threading/drilling works all as specified and directed by Engr-in-charge.
Supplying and laying GI tubing light grade of size 80mm dia bore for encasing cables for mechanical protection , laid under Plinth / Floors/ Paths/ Culverts or fixed on wall or concealed in wall/floor or along poles or as street light poles or as street light mounting bracket with complete accessories such as bends/sockets/reducers/saddles incl necessary threading/drilling works all as specified and directed by Engr-in-charge.
Supply , laying and testing cable XLPE insulated screened pvc bedded galvanised steel strip or wire armoured , electric power cables ( heavy duty) with stranded aluminium conductor 1100 volts grade in trenches/ passing through pipe/fixing on walls, floors etc incl connection with proper sizes lugs and gland, suitable clamp of cross sectional area 6 core 2 Sqmm in and including taking out old one all as specified and directed.
All as per item 15 above, but of the size 2 core 10 Sqmm
All as per item 15 above, but of the size 4 core 25 Sqmm
All as per item 15 above, but of the size 3.5 core 50 Sqmm
All as per item 15 above, but of the size 3.5 core 120 Sqmm
All as per item 15 above, but of the size 3.5 core 185 Sqmm
Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable incl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved
Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 77 mm and inner dia 63 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable incl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved
Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 90 mm and inner dia 76 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable incl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved
Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 120 mm and inner dia 103 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable incl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved
Supply, install, connect, test and commissioning of factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (Approx) with front made of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 60 cms above the ground level and 40 cm below ground level with cable entry glands to accommodate and including the following accessories:-
Copper bus bar rectangular 600 Amps full for phase and half for neutral and interconnection of MCCBs to Bus bar mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 400 Amps, TPN, 415 Volts, 50 Hz ,50 KA- 01 No ( Incoming)
MCCB 250 Amps, TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing)
MCCB 160 Amps, TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing)
MCCB 100 Amps,TPN, 415 Volts, 50 Hz ,36KA - 02 No ( Outgoing)
MCB SPN 40A -Each-05
RYB LED Indicator Lamp- Set of Three-01
Three pole Contactor 63 A Current Rating 70A General use 10A, 415V with coil
Digital timer switch with inbuilt backup current capacity 16 Amps operated on 415 volts AC 50 Hz
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (Approx) with front made of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 60 cms above the ground level and 40 cm below ground level with cable entry glands to accommodate and including the following accessories:-
Copper bus bar rectangular 150 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 100 Amps, TPN, 415 Volts, 50 Hz , 36 KA - 01 No ( Incoming)
MCCB 63 Amps, TPN, 415 Volts, 50 Hz , 36 KA - 01 No ( Outgoing)
MCB SPN 40 Amps :- 10
RYB LED Indicator Lamp- Set of Three-01
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (Approx) with front made of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 60 cms above the ground level and 40 cm below ground level with cable entry glands to accommodate and including the following accessories:-
Copper bus bar rectangular 150 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 100 Amps, TPN, 415 Volts, 50 Hz , 36 KA - 01 No ( Incoming)
MCCB 63 Amps, TPN, 415 Volts, 50 Hz , 36 KA - 02 No ( Outgoing)
MCB SPN 40 Amps :- 5
RYB LED Indicator Lamp- Set of Three-01
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (Approx) with front made of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 60 cms above the ground level and 40 cm below ground level with cable entry glands to accommodate and including the following accessories:-
Copper bus bar rectangular 150 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 63 Amps, TPN, 415 Volts, 50 Hz , 36 KA - 01 No ( Outgoing)
MCB SPN 40 Amps :- 12
RYB LED Indicator Lamp- Set of Three-01
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (Approx) with front made of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 60 cms above the ground level and 40 cm below ground level with cable entry glands to accommodate and including the following accessories:-
Copper bus bar rectangular 150 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 63 Amps, TPN, 415 Volts, 50 Hz , 36 KA - 01 No ( Outgoing)
MCB SPN 40 Amps :- 9
RYB LED Indicator Lamp- Set of Three-01
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply and fix pole junction box sheet moulded compound (SMC) type with hinged door and locking arrangement of size 300 X 200 X 105 mm (internal ) comprising, 01 No MCB single pole of capacity 6 Amps 240 volts and two Nos terminal for loop in & loop out suitable for three phase street light system including nuts and bolts and connecting up complete, MS clamp fabricated from 25x3mm MS flat iron all as specified and directed.
Supply and fixing or passing through pipe, 1100 volts grade heavy duty, PVC insulated round 3 core 2.5 sqmm copper cable including electrical connection complete all as specified and directed by Engr-in-Charge.
M & L for earthing complete with GI earth plate electrode of size 60 x 60 x 0.6 cms thick burried directly in ground vertically at a depth of not less than 2.25 Mtrs below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanised iron strip of 25 x 4 mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, 40 mm dia GI tubing light grade protection pipe upto test point, 20 mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30x30 CM made of RCC 1:3:6 with suitable handle, angle iron frame of angle iron size 40 x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, removal of surplus soil and returning filling in all as required at site all as specified in plate No 3 of SSR Part-I and directed by Engr-in-Charge.
M/S kirpan Enterprises
ONKAR ELECTRIC AND GENERAL STORE
Sachin Electricals
N D ELECTRICAL
M/S. Niksun Electro-Infra Private Limited
CHAITANYA WINDWELL
Rama Electricals
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .