Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 57 B FEEDER ROAD GROUND FLOOR 57 B FEEDER ROAD BARRACKPORE NORTH 24 PARGANAS WEST BENGAL 700120 | 24 PARAGANAS NORTH | WEST BENGAL | 700120 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical DISQUALIFIED AS PER TENDER DOCUMENT |
| 4 | Rejected-Technical 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | Rejected-Technical DISQUALIFIED AS PER TENDER DOCUMENT |
Tender Value
₹8.0 L
EMD Value
₹16,100
Closing Date
13 Aug 2024, 12:00 pmClosed
Superintending Engineer (EM)
Office of the Superintending Engineer (EM), RAC Works Section, Old Building IIT KGP
Supply, Installation, Testing and Commissioning of Air conditioning work at Cafeteria at ground floor at Research Park, Rajarhat, Kolkata of IIT Kharagpur.
2024_IITKG_816340_1
IITKGP/IW/RAC/RP/2024
Open Tender
Plant Protection Input/Equipment Works
Item Rate
90 days
IIT Kharagpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹16,100
RAC Works Section, Old Building IIT KGP
16 Oct 2024
12 Jul 2024
14 Aug 2024
12 Jul 2024
13 Aug 2024
12 Jul 2024
31 Jul 2024
Amount
Supply, Installation, Testing & Commissioning of Air Cooled type outdoor units of VRF system having hermetically sealed inverter scroll/twin rotary compressor, condenser coil fabricated from Seamless Copper tube & Plate type Al. Fins of Multi Row, Axial Flow, top discharge throw condenser fan, Condenser fan - motor unit, all system controls-safety. The system should have flexibility to handle total 280 Rmt of ref. piping. ODU shall be placed on structure with heavy duty anti vibrational pad to protect the system from any kind of unwanted vibration. The system shall have minmum COP of 3.7 at ARI condition as per CPWD guidelines. Each Outdoor units with High Pressure switch, Fan driver overload protector, Over current relay, Inverter Overload Protector & Fusible Plug. The unit shall be suitable for 415 ± 10 % volts, 50 Hz, 3 phase AC supply, and IP protection will be suitable for outdoor installation. The VRF System shall have green ref. gas only- R410A/ R407
Supply of Decorative Cassette Type VRF Indoor units . The unit shall be insulated with sound absorbing thermal insulation material, Poly-styrene / Polyethylene foam. The unit shall be supplied with suitable decorative panel & resin net filter with Mold resistance. Cassette units shall have independed drain pump. The unit shall be supplied with drain hose, clamp metal, washer fixing plate, sealing pads, screws, clamps, washer for hanging bracket & insulation for fitting. Power cabling with conduit from power socket to indoor is inclusive of price.
Cassette Type Indoor Unit - Capacity - 3.0TR
VRF Y JOINTS FOR BRANCH DISTRIBUTION REFRIGERENT PIPE JOINTS WITH PRECAST INSULATION
REMOTE CONTROLLER
Supply, installation, testing & commissioning of Cordlesss remotes for VRF indoor units
SITC of VRF Refrigerant Piping: Supply, installation, testing & commissioning of Seamless heavy gauge Copper piping of following size duly insulated with 13 mm/ 19mm thk. Nitrile Rubber Insulation covered with aluminium foil ( As per Specified with K Value of 0.027-0.029 K Cal/Hr.M Deg C at 0-16 Deg C) . Refrigeration piping will have to be taken in the piping rack / Support individually connecting to all indoor units for the respective floors. Even necessary supports, fittings, valves & ref. joints where ever required will be included. The exposed refrigerent insulated piping shall be covered with UV Resistance canvass coating.
28.6 mm O.D.(with 19 mm insulation )
25.4 mm O.D..(with 19 mm insulation )
22.2 mm O.D..(with 19 mm insulation )
19.05 mm O.D..(with 19 mm insulation )
15.88 mm O.D..(with 19 mm insulation )
12.7 mm O.D..(with 19 mm insulation )
22.2 mm O.D..(with 13 mm insulation )
19.1 mm O.D..(with 13 mm insulation )
15.9 mm O.D..(with 13 mm insulation )
12.7 mm O.D.(with 13mm insulation )
9.52 mm O.D.(with 13mm insulation )
6.35 mm O.D.(with 13mm insulation )
Supply, Installation and Testing of rigid PVC Drain Piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation.
32 mm dia
25 mm dia
SITC of GI perforated Cable Tray for the refrigerant pipe hanging & Covering
Supply & fixing of control cum transmission wiring of Copper conductor Shielded cable along with PVC conduit / casing for looping between indoor & outdoor VRF system.
2 C X 1.5 Sq. mm (Communication cable)
3 C X 1.5 Sq. mm - PVC insulated & PVC sheathed cable for IDU power connection
Supply, installation, testing & commissioning of require size copper conductor steel armoured power cable with termination to individual Outdoor units.(From Power Panel to VRF ODU)
Civil foundation of VRF ODU
Making wall opening for passage in the wall/glass for ref & drain pipes and cables and making good of the same for all the indoor/ outdoor units.
Comprehensive AMC of the VRF system for four years after DLP.
Comprehensive AMC 1st Year after DLP
Comprehensive AMC 2nd Year after DLP
Comprehensive AMC 3rd Year after DLP
Comprehensive AMC 4th Year after DLP
ALPHA GAMMA AIR SOLUTIONS PVT. LTD.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .