| Sl No | Description | Qty | Unit | NACHIKETA TECHNOLOGY L2 | PERFECT ELECTRICAL WORKS L1 |
|---|---|---|---|---|---|
| 1.00Providing/ Fitting of new star delta starter panel suitable for 100 HP motor of pumping unit 01, MCCBs of Main LT Panel, pump room shutter at LIS Jathana | |||||
| 1.01 | Replacement of old/damaged Oil filled manual ATS by Providing/Fabricating / Fitting /Testing and Commissioning of new(dry type)star delta starter for 100 HP motor of pumping unit No.01 at LIS Jathana: The panel shall be dust and vermin proof fabricated out of Minimum 16 SWG CR Sheet supported on M.S. angle of suitable size and thus having provision for fixing it on the wall. The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking /sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables properly according to size and specification. The panel should be given two coats of anti rust primer and two coats of steel grey enamel paint.
The star delta starter panel should be equipped with following components / features:
The panel should be fitted with an M.C.C.B. of 250 Ampere (3P) 50kA rating (L&T(Lauritz Knudsen)/ Schneider/ Havells/ABB/ Equivalent Reputed make), 01 no. Digital voltmeter , 01no.Digital Ammeter along with suitable set of CTs and set of RYB phase indicators at incoming side including the suitable bus bars of appropriate size. The starter panel should comprise of 3-Pole Power Contactors of 185A rating (2No.s) (L&T(Lauritz Knudsen)/ Schneider / Havells/ABB/ Equivalent Reputed make), (1 No.)Power contactor 110 A rating (L&T(Lauritz Knudsen) /Schneider/ Havells/ABB/ equivalent reputed make), suitable for star delta starter for 100 HP motor, 1 No. timer for change over the supply of motor from star to delta, 2 Nos. push buttons for start and stop operation of motor,02 No. selector switches, 1 No. MCB of appropriate rating for the protection of internal control wiring, a neat and clean internal control wiring should be made with flexible copper cables/ bus bars to complete the star delta circuit of outgoing supply for pumping unit no.1 at LIS Jathana.
The star delta starter should have the following protections of standard /reputed make to protect the motor from following electro-mechanical faults which may otherwise damage the motor windings: Voltage related faults :Single phasing, Reverse phasing, under voltage, over voltage, unbalance voltage. Current related faults: Over current / load, dry running, unbalance current / load, other faults: protection from earth fault. Moreover, thermal overload relay of suitable range should be fitted in the starter panel as an extra protection to the motor.
The starter panel must display incoming voltage of all three phases, current of all three phases.
The job also includes Providing and laying of 50 sq mm copper cable (KEI/ Havells/ Polycab/ equivalent reputed make) - 6 nos. of 8 meter (Approx) each in length from new stardelta starter panel for unit-I to 100 HP motor of pumping unit-I and thimbling the copper cables with suitable/appropriate size of copper thimbles with help of crimping tool and cover the flexible copper cable with heavy duty PVC sleeve.
The job also includes Replacement of old/damaged MCCBs of Main LT Panel by way of disassembling/disconnecting the existing damaged MCCBs from the Main LT Panel and then Providing/fitting / testing & commissioning of 02 Nos. MCCBs of rating 250 A, 36 KA suitable for supplying/forwarding current to the starters of motors of pumping units- I & II respectively & P/F of 01 No. MCCB of rating 63 A, 36 KA suitable for supplying/forwarding current to the priming pump, Than making/correcting the necessary damaged connections through new thimbles where ever required. The job also includes replacement of damaged Ammeter/voltmeter of the main LT Panel by way of providing/fitting of new analogue ammeter/voltmeter. Than making the connections of the input and output cables to the main LT panel and checking the current supply to the motor starters of pumping units.
The Job also includes the replacement of the existing damaged entrance shutter of pump room of LIS Jathana by way of dismantling the existing shutter and its frame and than by providing/fabricating /fitting of new GI rolling shutter along with its frame of required dimensions at the entrance of pump room (entrance size: approx.9’x 6’5’’)of LIS Jathana. The shutter shall consist of Top cover of required dimensions, side locks.The firm shall provide rebate on the old/damaged shutter & its parts only .
Complete job includes the cost of materials, consumables, handling, loading, unloading, Carriage charges through mechanical means upto Jakhole and than on head load from jakhole to LIS Jathana(approx. 2.5 km). The job also includes the cost of skilled /semi-skilled labour, testing & commissioning, tools and tackles, etc required during the execution of the job at site.
Note:-The tenderers are requested to visit the site and quote the rate as per site conditions. Any modifications/ alterations of the job, absolutely necessary if required at the time of execution may be done as per actual site conditions. | 1 | Job | 2,60,499 ₹2,60,499 | 2,39,999 ₹2,39,999 Lowest |
| 1.02 | Rebate on Old Parts | 1 | Job | - | -2,400 ₹-2,400 |
Tender Value
₹3 L
EMD Value
₹6,000
Closing Date
12 Nov 2025, 2:00 pmClosed
XEN MID JAMMU
MID JAMMU
Providing/ Fitting of new star delta starter panel suitable for 100 HP motor of pumping unit 01, MCCBs of Main LT Panel, pump room shutter at LIS Jathana.
2025_IFC_291194_1
MID/J/e-NIT/2025-26/106
Open Tender
Repair and Maintenance Works
Item Wise
45 days
jathana
as per tender ntoiec
8 documents required · 8 mandatory
₹500
Executive Engineer MID JAMMU
₹6,000
MID JAMMU
1 Dec 2025
8 Oct 2025
13 Nov 2025
8 Oct 2025
12 Nov 2025
8 Oct 2025
13 Oct 2025
Providing/ Fitting of new star delta starter panel suitable for 100 HP motor of pumping unit 01, MCCBs of Main LT Panel, pump room shutter at LIS Jathana
Rebate on Old Parts
NACHIKETA TECHNOLOGY (BID ID -2619821)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.49 MB
BOQ_936142.xls
BOQ • 0.29 MB
SBD106.pdf
Additional Documents • 0.66 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .