Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.1 LAccepted-AOC | L1 | Accepted-AOC Reasonable | |
| 2 | L2₹35.8 L+₹3.0 L (9.21%)Rejected-Finance | L2 | Rejected-Finance High Rate | |
| 3 | L3₹37.6 L+₹4.8 L (14.8%)Rejected-Finance | L3 | Rejected-Finance High Rate | |
| 4 | L4₹38.0 L+₹5.2 L (16.0%)Rejected-Finance 171 NARAYAN PETH PUNE PUNE MAHARASHTRA 411030 | PUNE | MAHARASHTRA | 411030 | L4 | Rejected-Finance High Rate | |
| 5 | L5₹38.7 L+₹6.0 L (18.2%)Rejected-Finance FLAT NO 401 TULSANI HEIGHTS 4TH FLOOR GREEN PARK SOCIETY AKURDI GURUDWARA TO WALHEKAR WADI ROAD CHINCHWAD PUNE 411033 | PUNE | MAHARASHTRA | 411033 | L5 | Rejected-Finance High Rate |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
25 Mar 2021, 6:55 pmClosed
GE NDA KHADAKWASLA
GE NDA KHADAKWASLA
REPAIR/MAINT OF VOLTAGE STABILIZER LT APFC PANEL AND E/M INSTALLATION MISC WORKS AT NDA KHADAKWASLA
2021_MES_427308_1
GE (K) 66 OF 2020-2021
Open Tender
Civil Works
Item Rate
180 days
GE NDA KHADAKWASLA
AS TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
Yes
GE NDA KHADAKWASLA
₹94,000
Yes
16 Apr 2021
2 Mar 2021
27 Mar 2021
3 Mar 2021
25 Mar 2021
13 Mar 2021
3 Mar 2021 - 12 Mar 2021
Amount
M&L for disconnecting carefully electrical connection both LT (incoming & outgoing) sides of the Voltage stabilizer oil cooled, keeping them at safe side and taking out the Voltage stabilizer indoor/ outdoor type of capacity 500 KVA, 415 Volts, AC, 50 Hz. Make : AEI Ltd for carrying out complete overhauling through authorised service dealer of OEM which shall comprises of the following (a) M&L for lifting, transporting, handling the voltage stabilizer to workshop and opening top cover of the voltage stabilizer by unscrewing nuts, bolts, washers etc. including disconnecting core assembly from bushing and lifting the same gently and taking out from the shell (container/body) of the voltage stabilizer. (b ) M&L for draining out contaminated voltage stabilizer oil from the above said voltage stabilizer. (c) M&L for cleaning the voltage stabilizer body from inside, removing deposited dirt/ sludge/ foreign particles etc. from the bottom / body of the voltage stabilizer and drying up the shell from inside before refilling of the stabilizer oil. (d) M&L for cleaning and washing thoroughly core and windings of the voltage stabilizer oil by hosing down with clean dry oil conforming to IS 335/1983, removing deposited dirt/ sludge/ foreign particles from the windings/ core, thorough inspection of windings, providing insulations to leads and terminals, heating/ drying /baking complete carefully and throughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc. all as per IS 1986-8 and directed by Engr- in -charge. (e) Refixing the top cover including replacement of cork sheet/ gasket 8 mm thick, tightening of nuts/bolts/washers etc. all as directed by Engr-in-charge. (f) Lifting /shifting to the place from where removed and re-installing the voltage stabilizer including connecting incoming /outgoing / neutral connections etc all as directed by engr-in -charge. (g) the inspection of voltage stabilizer shall involve :- (i) Checking of all clamps , nuts , bolts including core bolts & cover fixing bolts. (ii) Checking all brazings, joints, tap heads and connection joints. (iii) Checking all terminations / connections inside the voltage stabilizer . (iv) Painting of voltage stabilizer complete with two coats of synthetic enamel paint externally by spray and painting with a coat of oil resistant paint inside the transformer shell complete all as directed by engr-in -charge. (vi) Inspection / checking the moving and fixed contacts for contact wear and connection to winding. (h) Conducting the test on core and windings as per IS like ratio, magnetic, imbalance, short circuit etc. in presence of Engr-in-charge. (j) Note :- (i) Any damage to insulators / bushes /windings etc. while in the custody of the contractor shall be made good at no extra cost to govt. The serviceability of the voltage stabilizer shall be checked and confirmed by the contractor before taking into his custody. (ii) M & L for rewinding of LT (primary/secondary) coils, bushes studs , voltage stabilizer oil, filtration of oil , cable box etc will be measured and paid separately.
Ditto all as per item No. 1 above but capacity of 250 KVA.
Ditto all as per item No. 1 above but capacity of 100 KVA, 415 Volts .
M & L for Sensing / control card including its controlled circuit complete for voltage stabilizer of capacity 500 KVA.
Ditto all as per item No. 4 above but capacity 250 KVA.
Ditto all as per item No. 4 above but capacity 100 KVA.
S & F in replacment Servo motor 240 volt, including its controlled circuit complete, suitable/compatible to 500 KVA voltage stabilizer.
Ditto all as per item No. 7 above but capacity 250 KVA.
Ditto all as per item No. 7 above but capacity 100 KVA.
S&F in replacement analog type Volt meter including suitable size of PTs, suitable /compatible to existing Voltage stabilizer of any make/capacity including its control wiring etc complete all as directed. Make : as per existing.
S&F in replacement analog type ammeter including suitable size of CTs, suitable /compatible to existing Voltage stabilizer of any make/capacity including its control wiring etc complete all as directed. Make : as per existing.
Supply and top up of voltage stabilizer oil with di-electric strength not less than 50 KV in to the body tank of the voltage stabilizer etc at various locations complete all as directed and also submit the test result before and after the top up. Make : Poweroil/ Transol/ Sabitha Chemicals]
M&L for rewinding of voltage stabilizer of any capacity/ type by winding the defective coils with new copper wire as per I.S. of same gauge and existing size together with new insulated materials/ bracings before placing in to the voltage stabilizer and assembling the coil with new insulation and fitting the coils in the chamber, testing and commissioning the voltage stabilizer and recording the test results complete all as directed.
M&L for re-assembling of iron core of voltage stabilizer of any capacity/ type by re-assembling the defective iron core with new iron core as per I.S. of same gauge and existing size together with new materials/ bracings before placing in to the voltage stabilizer and assembling the iron core with new insulation and fitting the coils in the chamber, testing and commissioning the voltage stabilizer and recording the test results complete all as directed.
M & L for control Wiring complete with suitable copper wire of required size or as per sample including accessories for voltage stabilizer of capacity upto 500 KVA complete.
M & L for control Wiring complete with suitable copper wire of required size or as per sample including accessories for voltage stabilizer of capacity upto 250 KVA complete.
M & L for control Wiring complete with suitable copper wire of required size or as per sample including accessories for voltage stabilizer of capacity upto 100 KVA complete.
M&L for replacement of the LT porcelain bushings with bushing rod of 500 KVA capacity voltage stabilizer complete all as directed. Make : GE or as approved
M&L for replacement of the LT porcelain bushings with bushing rod of 250 KVA capacity voltage stabilizer complete all as directed. Make : GE or as approved
M&L for replacement of the LT porcelain bushings with bushing rod of 100 KVA capacity voltage stabilizer complete all as directed. Make : GE or as approved
M & L for dehydration/filteration of voltage stabilizer oil at site by taking proper shutdown of various capacity of Voltages Stabilizers located at various Sub Stations inside NDA, desired di-electric strength of oil not less then 50 KV complete all as directed and specified and also submit the test result before and after the de-hydration of the stabilizer oil.
M&L for servicing / maintenance by opening the top cover of the Voltage stabilizer, oil cooled type of following capacity and applying the grease /petrolium jelly at all moveable part of the servo control motors, checking the all control wiring and cleaning internally by applying air pressure through blower and ensure testing voltage, current, Earthing etc of volatge stabilizer of following capacity including rectifying the fault of oil leakages. Note : Servicing done through authorised service dealer of OEM also submit servicing/fitness certificate of the eqpt. 500 KVA
Ditto all as per item No. 23 above but 250 KVA
Ditto all as per item No. 23 above but 200 KVA
Ditto all as per item No. 23 above but 100 KVA Make : M-Guard / Volina
Ditto all as per item No. 23 above but 75 KVA
Ditto all as per item No. 23 above but 50 KVA
Ditto all as per item No. 23 above but 25 KVA
Ditto all as per item No. 23 above but 20 KVA
M&L for servicing / maintenance by opening the top cover of the Isolation Transformer, Air Cooled type of 75 KVA, 415 Volts, 50 Hz, Checking all control wiring and cleaning internally by applying air pressure through blower and ensure testing voltage, current, Earthing etc complete all as directed. Note : Servicing done through authorised service dealer of OEM and also submit servicing/fitness certificate of the eqpt.
Supply & replacement of hydraulic oil of Hydraulic ladder as per OEM recommendation complete all as specified and directed and it shall be carried out through OEM.
M&L for preparation of existing surface of following capacity Voltage stabilizer, Oil Cooled type by srapping down /peeled off old paint, loose scale grease, Lubricants etc by abrasive paper and applying one coat of smoke gray paint by spray complete all as specified and directed 500 KVA
Ditto all as per item No. 33 above but 250 KVA
Ditto all as per item No. 33 above but 100 KVA
Ditto all as per item No. 33 above but 25 KVA
Ditto all as per item No. 33 above but 20 KVA
M&L for servicing/Maintenance of Heavy Duty Siren from 3 HP, 3 Phase, 415 V, 50 Hz by opening the siren complete including correcting defects like alignment of wheel /shaft, cleaning of fins, replacement of worn out bearing as per existing to made siren serviceable incl greasing cleaning including taking down from existing place and testing etc as specified and directed for entire satisfaction. Note :- (i) The rates quoted against the Item is deemed to be included for cost of labour, cost of T & P required for replacement of unserviceable parts and cost of handling / transportation of defective item to & from OEM workshop for repair/servicing. (ii) M & L for rewinding motor if any etc will be measured and paid separately.
Ditto all as per item No. 38 above but Capacity 10 HP, 3 Phase, 440 V, AC supply 50 HZ.
Dismantling motor of siren of capacity 3 HP, 3 phase, 415 V, AC supply 50 HZ from the existing position and taking down burn out copper winding wire, including cleaning the slots etc and re-winding the motor with supper enameled copper wire with existing guage & insulating with high quality insulation lamination and varnishing, heating and making necessary connection, testing & commissioning complete as directed.
M & L in repalcement of LED Illumination, colour as directed of one face of 9' dials (Indices & clock hands) LED lighting :- Each face of the 9' dia tower clock shall be provided with following LED lighting arrangment of reputed brand :- a) Illumination for the dial (Indices) : Total 175 modules of 0.75 watts each distributed as 75 modules for 4 Indices (22"x 6") and remaining 100 modules for 8 Indices (16"x 6") controlled by one SMPS of 20 Amps. b) Illumination of the Clock Hands: Total 50 modules of 0.75 watts; 30 modules for Minute hand and 20 modules for Hour Hand controlled by one SMPS of 5 Amps Note - Necessary working platform / scaffolding for fixing the LED illumination system on the external face of the tower (clock) at MP Block shall be arranged by the vendor / contractor and the unit rate quoted is deemed to be included the cost of it.
M & L in replacement of 110- 240 V +15% AC, 50 Hz input and 12V DC, 20 Amp output SMPS suitable to existing system of tower clock LED illumination of the dial (indices) complete all as specified and directed.
M & L in replacement of 110- 240 V +15% AC, 50 Hz input and 12V DC, 5 Amp output SMPS suitable to existing system of tower clock LED illumination of the dial (indices) complete all as specified and directed. Make : JBN, Model No. JBN1205
S & F in replacement of back up system of 12 volts 12 Ah capacity dry type, maintenance free sealed battery, suitable/compatible to existing tower clock system complete all as specified and directed. Make : Chloride Safepower/Trontek
S & F in replacement of LED indicator lamp Red/Yellow/Blue size and capacity as per existing including drilling and cutting the panel sheet if required complete all as directed.
S & F in replacement of Cylindrical panel locks size as per existing including cutting and drilling the panel sheet if required complete all as directed.
S & F in replacement of Cold rolled mild steel hinges suitable to existing APFC panel door or as per sample including cutting/welding to panel sheet and painting to match with the existing colour complete all as directed.
M & L for preparation of existing surface of APFC Panel by scrapping down, peeled off old paint with abrasive paper including applying one coat of smoke grey paint by spray or as directed including cleaning the APFC panels from inside by blowing the air through compressure etc complete all as directed.
Fixing in repair Cylindrical panel locks of any type/size including cutting and drilling the panel sheet if required complete all as directed.
M & L for demolition of un-reinforced PCC, floors etc in any position and any description including removal of demolished material atleast 100 mtr away from site complete all as directed.
M & L for Plain Cement Concrete (1:3:6) type C2 (40 mm graded aggregate) for foundation, filling and mass concrete including necessary form work etc complete all as directed.
S & F in replacement of Aluminium tube terminals, suitable/compatible to 10 Sqmm AL stranded cable complete all as directed.
Ditto all as per item No. 52 Above but 16 Sqmm
Ditto all as per item No. 52 Above but 25 Sqmm
Ditto all as per item No. 52 Above but 35 Sqmm
Ditto all as per item No. 52 Above but 50 Sqmm
Ditto all as per item No. 52 Above but 70 Sqmm
Ditto all as per item No. 52 Above but 95 Sqmm
Ditto all as per item No. 52 Above but 120 Sqmm
Ditto all as per item No. 52 Above but 150 Sqmm
Supply only nuts, bolts and washers made up of GI or Cadmium plated, high tensile as per sample complete.
S & F in replacement of Copper tube terminals, suitable/compatible to 6 Sqmm Copper stranded cable complete all as directed.
Ditto all as per item No. 62 Above but 10 Sqmm
Ditto all as per item No. 62 Above but 50 Sqmm
Ditto all as per item No. 62 Above but 70 Sqmm
Ditto all as per item No. 62 Above but 95 Sqmm
Supply, installation, testing and commissioning LT Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55 with locking arrangement for front and back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs. The panel shall be provided with RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be showing the arrangements of circuit shall be pasted inside the panel door and covered with transparent laminated plastic sheet . The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both sided and suitable extended rotary handles for incoming/outgoing MCCB complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX350mmX1000mm (WxDxH). The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands including 2 Nos of Earting Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-charge. (a) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In with both side of spreader links and phase separater etc - 01 No. (Incomer) Make : L&T/Legrand (b) MCCB 4 Pole, 415 Volts, 63 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In with both side of spreader links and phase separater etc - 02 Nos. (Outgoing) Make : L&T/Legrand (c) MCB 4 Pole, 230 Volts, 32 Amps, 10 KA - 02 Nos Make : L&T/Legrand (d) MCB 2 Pole, 230 Volts, 32 Amps, 10 KA - 04 Nos Make : L&T/Legrand (e) 4 Nos bus bars of high conductivity aluminium alloy for phase (R,Y,B,N) suitable for 400 Amp rating.
Fixing only chain link fencing MS galvanised, using 3 mm dia MS wire, including line wires, of mesh size 50 mm x 50 mm, rails, straining bolts, etc. including provision of binding wire any size or type including taking down existing one complete all as specified and directed.
Supply only chain link as in fencing MS galvanised, using 3 mm dia MS wire, including line wires, of mesh size 50 mm x 50 mm, rails, straining bolts, etc. including provision of binding wire any size or type complete all as specified and directed.
M&L for MS work as in Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embedding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed.
M & L for MS round/square bars 10mm dia and over,cut to length, bent to shape required, including cranking, bending spirally for hooping for chain link fencing, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips quality conforming to MS round bars complete all as specified and directed.
M & L for PCC Cement concrete Block masonry Set in Cement mortar (1:4) and PCC (1:3:6) type C1 (20 mm graded aggregate) including dismentaling existing one complete all as specified and directed
M & L for cement plaster (1: 4) for rendering 10mm thick on fair faces of brick work or concrete surfaces complete all as specified and directed
M & L for preparation of old painted Surfaces of any description over 10cm girth or width, not otherwise described and apply priming paints plaster coat etc complete all as specified and directed
S & F in replacement junction box inner dimension 270mm X 175mm X 105mm (HxWxD), 3 phase, 4-wire system, door fixed by means of sliding lock, including 6 Amp MCB DP with mounting channel, cable connecting base, Cable lugs of suitable to 16/10 Sqmm 4 core cable, cable connection for incoming and outgoing, cable glands, Aluminium Busbar with insulators, etc including fixing arrangements at tubular poles/walls etc complete all as specified and directed . Make : National/Sintex or equivalent as approved
S & F in replacement of nominal 2.5 mm thick class B Voltage upto 11KV Electrically insulated PVC synthetic mat conforms to IS 15652-2006 and applying adhesive to fix before laying the new one complete all as specified and directed.
M & L in replacement for Synthetic insulation mat of size 2m x 1m x 19mm complete all as directed.
M & L for removing existing de-graded / weathered stone aggregate of any size and type by excavating upto the natural ground surface and depositing where directed at a distance not less than 100 mtrs and cleaning the complete sub stn yard, removing tree roots, sepplings, grass etc and spreading 1'' layer of lime before laying the stone aggregate complete all as directed
M&L for 40 mm graded stone aggregate for evenly spreading at sub station yard upto the required thickness from natural ground level complete all as directed
M & L for 20 mm graded stone aggregate for evenly spreading at sub station yard upto the required thickness from natural ground level complete all as directed
M & L for servicing and repairing of Gang Operating Device by taking proper shutdown and applying petrolium jelly on male female contacts, tightning Nut, Bolts and washers and also Jumpers, lightning arrestors, etc including one coat of Aluminium paint on complete 2 pole structure complete all as specified and directed
M&L in replacement Pin type porcelain vitreous white brown or green insulator including one galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut 100 mm height 65 mm dia 1100 volts grade including taking down complete all as specified and directed. Make - GEC/National
M&L in replacement Shackle type porcelain vitreous white brown or green insulator including one galvanised mild steel straps washers insulators bolts washers and nut as under 75 mm height and 90 mm dia 1100 volts grade including taking down complete all as specified and directed Make - GEC/National
S & F in replacement drop out fuse unit expulsion type for our door air break gang operated switch, single pole, mounted on and including insulators for 11 KV working pressure, fixed to and including MS channel with nuts, bolts, washers etc. complete with line taps and suitable for current carrying capacity upto 50-100 Amps, including taking down existing one all as specified and directed. Make : Jaipuria/Elpro/Atlas
M & L in replacement switch air break triple pole mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current rating upto 200 Amps for 11000 volts including taking down existing one all as specified and directed. Make - Jaipuria Bros / Rashtriya/Elpro
M&L in replacement Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 Kilo Amp suitable for 11000 volts including taking down existing one all as specified and directed. Make - jaipuria Bros / Rashtriya/ Elpro
M & L in replacement End Jointing Kit suitable for 3 Core 95 Sqmm XLPE HT armoured aluminium conductor cable (earthed) grade for indoor termination heat shrink type joint complete with jointing material and accessories including taking shut down and opening the cable from both side of Bus Bar Panel/VCB/RMU/GOD etc and re-terminated the same cable in the same Bus Bar Panel/VCB/RMU/GOD etc after completion of jointing work complete all as specified and directed. Make - Rychem / Denson / M-Seal/3M
M& L in replacement End jointing kit suitable for 3 Core 95 Sqmm XLPE HT armoured aluminium conductor cable (Earthed) grade for outdoor termination heat shrink type joint complete with jointing material and accessories including taking shut down and opening the cable from both side of Bus Bar Panel/VCB/RMU/GOD etc and re-terminated the same cable in the same Bus Bar Panel/VCB/RMU/GOD etc after completion of jointing work complete all as specified and directed. Make - Rychem / Denson / M-Seal/3M
M & L in replacement Straight Through jointing kit suitable for 3 core 95 Sqmm XLPE 11 KV HT armoured aluminium conductor cable (Earthed) grade for straight through termination heat shrink type joint complete with jointing material and accessories including taking shut down and opening the cable from both side of Bus Bar Panel/VCB/RMU/GOD etc and re-terminated the same cable in the same Bus Bar Panel/VCB/RMU/GOD etc after completion of jointing work complete all as specified and directed. Make - Rychem / Denson / M-Seal/3M
M&L for replacement of earthing complete with galvanised steel earth plate electrode 60x60cmx6.3mm GI thick burried directly in ground ( earth plate pit not less than 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised iron strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No. 3 of SSR Part-I 2009 connected to eqpts/panel etc complete all as specified or indicated and testing on completion as directed by the Engineer-in-Charge including necessary excavation & earth work in any type of soil strata and pit re-filled with Charcoal, Salt and black cotton soil. PCC chamber (1:3:6) type C1, PCC pit cover, funnel with wiremesh including 20mm dia medium grade GI Pipe for watering complete all as directed.
M&L in replacement of GI strip 32 x 6 mm as earth continuity conductor or main earthing lead fixed to wall batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation with suitable size of SMC/FRP Insulators at suitable gaps, nut, bolts and washers etc complete all as specified and directed.
Pruning / trimming of branches of trees interfering or overhanging electrical overhead lines in such a way to have a clearance of not be less than 2 mtrs from the outermost conductors on both side including thrown away the same atleast 100 mtr from the site complete all as specified and directed. Note : Span of conductor shall be measured from insulator to insulator without allowance for overlapping.
S & F in replacement of HT jumpering with the help of Aluminium Counductor Steel Reinforcement covered with insulating material/sleeve and suitable size of aluminium Lugs, nut, bolt and washers etc. The length of jumper shall not be less than 3 meter including connection with the help of connector on the HT pole complete all as specified and directed
S & F in replacement Busbar panel weather proof outdoor type single door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7032 ( Siemens Gray) shade with matt finish with seven tank pre treatment process. The Panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof. All doors and covers shall be provided with cylindrical panel locks and shall be fully gasketed with neoprene rubber and shall be lockable. The panel shall be provided with aluminium bus bars, shall not be less than 400mmX40mmX8mm( L x W x thickness) electrolytic grade of adequate rating including required size of nut bolts for fixing of cables upto 240 Sqmm. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding and fix horizontally. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in a dedicated compartment and provision of cable glands, thimbles etc. All joints and connection shall be done with galvanised or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with 04 Nos 50mmx50mmx5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. Including cable connection and providing 4 Nos cable entry holes. The overall size of the Busbar panel shall not be less than 500mmx300mmx700mm (LxWxH) including earthwork all as directed and specified Note : (i) 4 Nos of Entry holes for cables from bottom side shall be provided upto 400 Sqmm and each busbar shall be provided neccessary arrangement to connect 4 Nos of cables including Nut bolts etc
S & F in replacement Busbar panel weather proof outdoor type single door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7032 ( Siemens Gray) shade with matt finish with seven tank pre treatment process. The Panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof. All doors and covers shall be provided with cylindrical panel locks and shall be fully gasketed with neoprene rubber and shall be lockable. The panel shall be provided with aluminium bus bars, 300mmX40mmX8mm(thickness) electrolytic grade of adequate rating. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding and fix horizontally. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in a dedicated compartment and provision of incoming and outgoing cable. All joints and connection shall be done with galvanised or codmium plated high tensile nuts, bolts and washers. The panel shall be provided with 04 Nos 30mmx30mmx5mm thick angle iron supports of not less than each 1 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at uitable depth as per site requirement. The overall size of the Busbar panel shall not be less than 400mmx200mmx550mm (LxDxH).including earthwork all as directed and specified . Note : (i) 4 Nos of Entry holes for cables from bottom side shall be provided upto 185 Sqmm and each busbar shall be provided neccessary arrangement to connect 4 Nos of cables including Nut bolts etc
S&F in replacement of GI bracket suitable for LED street light fitting including suitable size of clamps, nuts, bolts etc and fitted on the street pole including taking down existing one complete all as specified and directed at site.
S & F in repalcement LED Street Light 60 W made up of pressure die cast housing with individual LEDs with modular secondary optics and IP 55 protection, including taking down existing one complete all as specified and directed.
S & F in repalcement of LED Post tops 40 W made up pressure die cast aluminium housing with decorative clear opal acrylic diffuser and IP65 protection including taking down existing one complete all as specified and directed. Make : Bajaj Cat Part No BGCT W4 LED
S & F in replacement PVC insulated copper cable 3 core 1.5 sqmm with 20mm PVC conduit, multistranded to be drawn through including saddling/necessary digging for conduit etc and taking down existing one complete all as specified and directed. Make : Polycab/Havells
S & F in replacement PVC insulated copper cable 3 core 1.5 sqmm for security light, multistranded to be drawn through properly hole of street light pole including making of 10mm 2 hole in street light pole and taking down existing one complete all as specified and directed. Make : Polycab/Havells
Labour for restretching/tightening the existing LT overhead conductors & GI earth wire mounted on insulators of any type on poles manually or by mechanical means to the extent of permissible sag and tension and binding with steel wires of appropriate size complete having 5 to 7 conductors per span of approx 35-40 mtr length. All as specified and directed
M&L in replacement aluminium conductor steel reinforced size according to site requirement fixing on the over head LT pole with the help of aluminium tapes/ binding wire including taking down existing one complete all as specified.
Supply & laying in replacement including, fixing on walls, floors with suitable size of GI Clamps, nuts, bolts and washers etc of LT cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes:- Note - Excavation / earthwork, Bricks Cable Cover & sand cushioning will be measured and paid separately under respective item of sch A. 4 Core 10 Sqmm
Ditto all as per item No 103 above but 4 Core 16 Sqmm
Ditto all as per item No 103 above but 3.5 Core 25 Sqmm
Ditto all as per item No 103 above but 3.5 Core 35 Sqmm
Ditto all as per item No 103 above but 3.5 Core 50 Sqmm
Ditto all as per item No 103 above but 3.5 Core 95 Sqmm
Ditto all as per item No 103 above but 3.5 Core 120 Sqmm
Ditto all as per item No 103 above but 3.5 Core 150 Sqmm
Ditto all as per item No 103 above but 3.5 Core 185 Sqmm
Ditto all as per item No 103 above but 3.5 Core 400 Sqmm
Excavation in trenches, n.exc 1.5m wide and n. exc 1.5 m depth and getting out in for foundation of pole, stay, laying of cable and pipe etc : Hard/Dense soil
Ditto all as per item No 113 above but soft /disintegrated rocks
Ditto all as per item No 113 above but hard rocks
Returning and filling in, including spreading and well ramming in layers n exc 25 cm all as specified and directed.
Removing excated material a distance n. exc 50 m & depositing where directed at a level n. exc 1.5 m above the starting point.
M&L for dry sand cushioing to under ground cable intrenches incl spreading, leveling and hand punning complete all specified. Note : For measurement purpose punned thickness shall be considered.
Supply and laying common burnt clay building sub class B old size bricks, laid in right angle along the cable, complete all as specified.
M & L in replacement for laying of half round reinforced concrete pipe, of inner dia 150 mm and Outer dia 200 mm, half round for bottom and half round for top and before laying excavated area shall be leveled, complete all as specified and directed. Note : 01 Half round top and 01 half round bottom together will be considered as one running meter. Make :As per sample approved
Supply and lay G.I pipe light grade with all fittings required for protection of under ground cable of 100 mm dia
Ditto all as per item No 121 above but 80 mm dia
Ditto all as per item No 121 above but 50 mm dia
M&L for road cutting size (0.45 x 0.50) Mtr (W x D) for laying pipe/cable etc including make good with existing material or with PCC 1:2:4 type B1 complete all as specified and as directed.
Relaying serviceable LT UG cable of following sizes complete all as specified and directed. Note - Excavation / earthwork, cable protection covers & sand cushioning will be measured and paid separately under respective item of sch A. 4 Core 10 Sqmm
Ditto all as per item No 125 above but 4 Core 16 Sqmm
Ditto all as per item No 125 above but 4 Core 25 Sqmm
Ditto all as per item No 125 above but 3.5 Core 35 Sqmm
Ditto all as per item No 125 above but 3.5 Core 50 Sqmm
Ditto all as per item No 125 above but 3.5 Core 70 Sqmm
Ditto all as per item No 125 above but 3.5 Core 95 Sqmm
Ditto all as per item No 125above but 3.5 Core 120 Sqmm
Ditto all as per item No 125 above but 3.5 Core 150 Sqmm
Ditto all as per item No 125 above but 3.5 Core 185 Sqmm
Ditto all as per item No 125 above but 3.5 Core 240 Sqmm
Ditto all as per item No 125 above but 3.5 Core 300 Sqmm
Ditto all as per item No 125 above but 3.5 Core 400 Sqmm
M&L for straight through Jointing Kit, heat shirnkable type complete with all jointing materials and suitable for 1100 Volts XLPE LT UG Power Cable aluminium stranded conductor of following sizes cable including taking shut down and opening the cable from both side of Bus Bar/Feeder Panel/LT Panel/ACB etc and re-terminated the same cable in the same Bus Bar/Feeder Panel/LT Panel/ACB etc after completion of jointing work according to existing system complete all as specified and directed. Make- Raychem/Denson /M-Seal/3-M 3.5 Core 400 Sqmm
Ditto all as per item No 138 above but 3.5 Core 300 Sqmm
Ditto all as per item No 138 above but 3.5 Core 240 Sqmm
Ditto all as per item No 138 above but 3.5 Core 185 Sqmm
Ditto all as per item No 138 above but 3.5 Core 150 Sqmm
Ditto all as per item No 138 above but 3.5 Core 120 Sqmm
Ditto all as per item No 138 above but 3.5 Core 95 Sqmm
Ditto all as per item No 138 above but 3.5 Core 70 Sqmm
Ditto all as per item No 138 above but 3.5 Core 50 Sqmm
Ditto all as per item No 138 above but 3.5 Core 35 Sqmm
Ditto all as per item No 138 above but 3.5 Core 25 Sqmm
Ditto all as per item No 138 above but 4 Core 16 Sqmm
Ditto all as per item No 138 above but 4 Core 10 Sqmm
S & F in replacement MCCB 3P 320 Amps, 25 KA breaking capacity with adjustable thermal and adjustable magnetic overload protection with Ics=100% of Icu including suitable size of spreader links with galvanised or codmium plated high tensile nuts, bolts and washers etc and cutting of panel Sheet and drilling also without disturbing to the existing accessories complete all as specified and directed. Make: L&T/Legrand
Ditto all as per item No. 151 But 3P 250 Amps, 25 KA. Make : L&T/Legrand
Ditto all as per item No. 151 But 3P 200 Amps, 25 KA. Make : L&T/Legrand
Ditto all as per item No. 151 But 3P 160 Amps, 25 KA. Make : L&T/Legrand
Ditto all as per item No. 151 But 3P 100 Amps, 25 KA. Make : L&T/Legrand
Ditto all as per item No. 151 But 3P 63 Amps, 25 KA. Make : L&T/Legrand
Ditto all as per item No. 151 But 4P 200 Amps, 25 KA. Make : L&T/Legrand
S & F in replacement of AC supply power contactor MNX140 (2 NO + 2NC) type, 140 Amps, 3-Pole, 415 Volts, 50 Hz, complete all as specified and directed. Make : L&T /Leagrand
M & L for core cutting, boring/ drilling in any type of walls (i.e Stone walls etc) of suitable dia for passing the LT Cables of size from 10 Sqmm to 400 Sqmm, Earth conductors etc including filling/making good to the disturbed surface of walls with existing one complete all as directed.
S & F in repair of Solar PV modules multi-crystalline panel of size (2.0x1.0) Mtr and capacity 310 WP/ 24V, installed at various security posts along boundary wall of NDA complete all as specified and directed . Note :- The rates quoted against the item is deemed to be included for cost of Labour, cost of T & P required for replacement of unserviceable parts and cost of handling / transportation of defective item to and from OEM workshop for repair / servicing. Make of Solar Panel : Waaree/Bikram Solar System
Supply and Install in replacement of old damaged /broken Solar PV modules multi-crystalline panel of size (2.0x1.0) Mtr and capacity 310 WP/ 24V, suitable /compatible to existing system installed at various security posts along boundary wall of NDA complete all as specified and directed . Make : Waaree/Bikram Solar System
S & F in repair of Solar PCU, 2 KVA, 24/4872V AC/DC hybrid input power with inbuilt MPPT charge controller, installed at various security posts along boundary wall of NDA complete all as specified and directed . Note :- The rates quoted against the item is deemed to be included for cost of Labour, cost of T & P required for replacement of unserviceable parts and cost of handling / transportation of defective item to and from OEM workshop for repair / servicing.
S & F in repair of Solar LMLA tubular battries @ C10 capacity, 12V, 200AH installed at various security posts along boundary wall of NDA complete all as specified and directed. Note :- The rates quoted against the item is deemed to be included for cost of Labour, cost of T & P required for replacement of unserviceable parts and cost of handling / transportation of defective item to and from OEM workshop for repair / servicing. Make : Exide/Amron/Indo Solaris
Supply and install in replacement of Solar LMLA tubular battries @ C10 capacity, 12V, 200Ah including all connection, installed at various security posts along boundary wall of NDA complete all as specified and directed . Make : Exide/Amron/Indo Solaris
S & F in repair Solar module mounting structure of MS GI type (Hot dipped GI) including suitable size of high tensile nut, bolts, fastners and washers etc or suitable / compatible to existing system, installed at various security posts along boundary wall of NDA complete all as specified and directed . Note : Mounting structure will be fixed on the top of roof hence after re-fixing where fastners, bolts used for errecting the structure should be sealed properly with requisite sealent/solvent to avoid any leakage/seepage from slab.
M & L for cleaning the glass of Solar PV modules multi-crystalline panel of size (2.0 x 1.0) Mtr (06 x Panels per security post along boundary wall of NDA) and capacity 310 WP/ 24V by removing the mud/algee/foreign materials from the panel complete all as directed. Note : If any damages noticed during this job, the contractor shall remain responsible to make good without any extra cost to the deptt. Make : Waaree/Bikram Solar System
M & L for top up of distilled water in battries upto required level at every 3 months intervals at site i.e. Various security posts along boundary wall of NDA complete all as specified and directed
S & F in repair of Solar Water Heating System (Flat Plate Collector, size 2.1 x 1.10 Mtr, Total No. of Panel 10 Nos) based on direct transfer of heat of capacity 600 Ltrs Per day with suitable electric backup complete all as specified and directed
Supply and install in replacement of Solar Flat Plate Collector Panel of size (2.10 x 1.10) Mtr, suitable /compatible to existing system complete all as specified and directed.
M & L for cleaning the hot water insulated tank of 600 ltrs capacity of Solar Water Heating System by removing the sludge /foreign material from inside the tank and rectifying the fault of water leakages complete all as directed.
M & L for cleaning the Glass of Flat Plate Collector Solar Panel of size (2.1 x 1.10) Mtr (10 x Panels) by removing the mud/algee/foreign materials from the panel on quarterly basis complete all as directed. Note : If any damage notices during this job, the contractor shall remain responsible to make good without any extra cost to the deptt.
S & F in repair including servicing/maint of Booster Pump of 0.5 HP, Single Phase, Outdoor type complete all as specified and directed
S & F in repair of Solar Water Heating System Flat Plate Collector type, size : (2.0 x 1.0) Mtr based on direct transfer of heat of capacity 100 Ltrs Per day with suitable electric backup of 2 KW complete all as specified and directed
M & L for cleaning the hot water insulated tank of 100 ltrs capacity of Solar Water Heating System Flat Plate Collector Type by removing the sludge /foreign material from the tank and recifying the fault of water leakages complete all as directed.
M & L for cleaning the Glass of Solar Flat Plate Collector Panel of size (2.0 x 1.0) Mtr by removing the mud/algee/foreign materials from the panel on quarterly basis complete all as directed. Note : If any damages occurred to the solar panel during this job, contractor shall be responsible to make good without any extra cost to the deptt.
Supply and install in replacement of Solar Flat Plate Collector Panel of size (2.0 x 1.0) Mtr, suitable /compatible to existing system complete all as specified and directed.
S & F in replacement of composite PEX-AL-PEX pipes as per ASTM F 128-2017 of size inner dia 15 mm and outer dia 20 mm, suitable/compatible to existing system complete. Make : Kitec or its equivalent.
S & F in replacement of CPVC pipes of size outer dia 16 mm with all standard fittings such as suitable size of MS clamps, screws, hooks, Elbow, bends, tees etc complete all as directed.
S & F in replacement of heating element of 2 KW capacity duly ISI marked, 1-ph, 240 volts suitable/compatible to existing solar heating system complete all as directed.
S & F in replacement Brass/Gun Metal Butterfly gate valve of 15 mm dia, ISI marked, suitable/compatible to extisting system complete all as specified and directed.
Fixing only and including complete connection of electric meters upto 25 Amps with existing cables without disturbing to existing fitments and old one deposited to MES store.
S & F in replacement of SS pipe flange of 15 mm dia or suitable/compatible to existing solar Flat plate collector system including suitable size of nut bolts and washers etc complete all as specified and directed.
S & F in replacement of rubber gaskets 15 mm dia or suitable/compatible to existing solar Flat plate collector system complete all as specified and directed.
M & L for preparation of surfaces by peeled off or scrapped down rust/old paints from Sub Stn fencing, mesh size (50 x 50) mm and application of one coat of primer and two coats of synthetic enamel black/smoke grey paint on the same sub station fencing by brush complete all as specified and directed.
M & L for preparation of surfaces by peeled off or scrapped down rust/old paints from MS Angle, Strip, Gate, Rolling Shutter and Solar Mounting Structure etc of any description over 10 cm width or girth free from dust, dirty, loose scale grease etc scrapping with sand /abrasive paper or pumic stone touching up and application of one coat of primer and two coats of synthetic enamel black/smoke grey paints on the same MS Angle, Strip, MS Gate, Rolling Shutter and Solar Mounting Structure etc by spray complete all as specified and directed.
S & F in replacement of Air Termination, single pointed, Aluminium rod 12 mm dia and 300 mm long with base plate including suitable for fixing on AL strip on ideal position on top of the roof etc complete all as specified and directed. Note : Suitable arrangement i.e ladder, scafolding or any other working plateform required for climbing on high rise buildings and structure for carryout said work is the responsibility of vendor/contractor and the rates are deemed to be included in this quoted rate.
M & L for Aluminium strip of size (25 x 3.15) mm including fixing with suitable size of SMC/FRP insulators/ GI Saddles, nut, bolts, washers and screws etc for roof conductors and down conductors above ground complete all as directed. Note : Suitable arrangement i.e ladder, scafolding or any other working plateform required for climbing on high rise buildings and structure for carryout said work is the responsibility of vendor/contractor and the rates are deemed to be included in this quoted rate.
M & L for test point terminal block made of gun matel or phosphorus bronze size (75 x 75 x 25) mm, drilled and screwed including 3 Nos 8 mm dia 25 mm long hex head screw.
Labour for disposal of old/unserviceable retrivated CFL/LED/Tube light (Approx 10,000 Nos) at least 100 mtrs away from the MES store yard complete all as directed.
M & L for servicing of MS Rolling shutter, size (3.0 x 3.0) Mtr approx by applying the grease /petrolium jelly/ Lubricants etc and make it suitable for smooth operation/movement complete all as specified and directed.
M & L for fixing in repair of Angle Iron Gate by providing and welding the holdfast/hinges of suitable size/ capacity with existing Pillars or column on both side and make this MS gate openable without any hindrance complete all as specified and directed.
Supply and fix Brass/Gun Metal Gate Valve of size 25 mm dia with iron wheel head or suitable /compatible to existing Voltage stabilizer by cutting/screwing /Threading/ welding etc for drain out the Stabilizer oil of following capacity and make including drain out the complete voltage stabilizer oil and kept safely in container /drum/barrel and re-fill the same oil in the same stabilizer after completion of fixing work of drain valve including rectification of oil leakages noticed,if any complete all as directed. 500 KVA
Ditto all as per item No. 192 above but 250 KVA
Ditto all as per item No. 192 above but 200 KVA
Ditto all as per item No. 192 above but 100 KVA Make : M-Guard / Volina
Ditto all as per item No. 192 above but 75 KVA
Ditto all as per item No. 192 above but 50 KVA
Ditto all as per item No. 192 above but 25 KVA
Ditto all as per item No. 192 above but 20 KVA
Labour for cleaning the Sub Stn Yard of size (20 x 15) Mtr approx ncluding fencing and 1 mtr all around the sub Stn fencing by removing/cutting/digging out from roots of trees, bushes & sepplings etc and thrown away the same atleast 100 mtr away from the sub stn yard complete all as directed
M & L for servicing and maintenance of Air curtain door opening size 46"x78", 3-phase, 415 Volts, AC, Air velocity 1-1.5 m/sec through authorised person of OEM.
Supply & Laying in trenches or fixing on wall/floor/ceiling GI tubing "Medium Grade" 15 mm bore with all standard fittings such as suitable size of MS clamps, screws, hooks, Elbow, bends, tees etc complete all as directed. Note : Excavation and Earth work shall be measured and paid separately.
S & F of Bronze/Gun Metal Gate Valves (Hexagonal type) 15 mm bore with iron wheel head, screwed both ends for iron pipe complete all directed. Make : Kirloskar/BIR
S & F of Stop valves of PTMT any colour, 15 mm dia, screwed for pipes high pressure (minimum weight 90 gms) complete all as directed. Make : Prayag/Polytuff
Labour for cleaning the drain, size (0.5 x 1.0) Mtr (W x D) including dug out and removing the Rubbish/mud/ foreign materials and thrown away the same atleast 100 mtr from the MRS Compound complete all as directed .
Labour for tree branch cutting of high rise trees, overhanging/interferences to the Two/Four Pole Structure GODs (size of tree branch approx 80 mm to 300 mm dia) without damages to the Two/Four Pole Structure/GODs etc including thrown away the same alteast 100 Mtr away from the Sub Stn Yard complete all as directed. Note : Suitable arrangement i.e ladder, scafolding or any other working plateform required for climbing on high rise trees for carryout said work is the responsibility of vendor/contractor and the rates are deemed to be included in this quoted rate.
S & F in replacement 1 to 4 KVAr rating heavy duty capacitors cylindrical type, 440 V, 50 Hz, AC with over current withstand capability 1.8 x In, Peak inrush current withstand capability 250 x In, No of switching operations per year 7500, operating life 130000 hrs complete all as directed Make : L & T/Epcos
S & F in replacement 5 to 15 KVAr rating heavy duty capacitors cylindrical type, 440 V, 50 Hz, AC with over current withstand capability 1.8 x In, Peak inrush current withstand capability 250 x In, No of switching operations per year 7500, operating life 130000 hrs complete all as directed. Make : L & T/Epcos
S & F in replacement 20 to 30 KVAr rating heavy duty capacitors cylindrical type, 440 V, 50 Hz, AC with over current withstand capability 1.8 x In, Peak inrush current withstand capability 250 x In, No of switching operations per year 7500, operating life 130000 hrs complete all as directed Make : L & T/Epcos
S & F in replacement 1 to 25 KVAr rating standard duty capacitors (LTCCF & LTCCD) series, cylindrical type, 440 V, 50 Hz, AC with over current withstand capability 1.5 x In, Peak inrush current withstand capability 200 x In, No of switching operations per year 5000, operating life 100000 hrs complete all as directed. Make : L & T/Epcos
S & F in replacement 5.5 to 15 KVAr rating heavy duty capacitors Box series type, 480 V, 50 Hz, AC with over current withstand capability 1.8 x In, Peak inrush current withstand capability 300 x In, No of switching operations per year 8000, operating life 150000 hrs complete all as directed . Make : L & T/Epcos
S & F in replacement capacitor duty contactors, type MO-C, 440 V, 3-Ph, 50 Hz, suitable for KVAr rating up to 10 KVAr.
S & F in replacement capacitor duty contactors, type MO-C, 440 V, 3-Ph, 50 Hz, suitable for KVAr rating 12.5 KVAr.
S & F in replacement capacitor duty contactors, type MO-C, 440 V, 3-Ph, 50 Hz, suitable for KVAr rating 20 KVAr.
S & F in replacement capacitor duty contactors, type MO-C, 440 V, 3-Ph, 50 Hz, suitable for KVAr rating 25 KVAr.
S & F illuminated display board of size (1.28 x 0.2 x 0.9) Mtr (L x B xH) with Flex of Light Blue (MES Colour), Colour of letters shall be white, outerside fabrication bordered with Aluminium angle Frame of size (20 x 25) mm x 3mm thick, innerside fabricated with 12mm MS square bar and aluminium sheet for top, bottom, back side, left side and right side of the display board, 50mm dia GI Pipe medium grade shall be fixed both side of board with 2 Nos 30 mm x 4mm thick MS flat of 0.2 Mtr length welded to GI pipe and nut bolt and washer with display board not less than 2.5 Mtr and PCC 1:4:8 for foundation including all internal wirings and illuminated with LED 40 W Tubelight fitting 01 No, SMC/FRP Junction Box 140mm x 140mm x 95mm inner dimension make Sintex/National, the board must be openable from back side for maintenance of tube light, control wiring etc. Make : Bajaj Cat Part No BCLAB 20W /Wipro/Havells including its fixing arrangement and written Letters in capital not less than 10 letters and more than 40 letters, size of letters proportion with overall size of board complete all as specified and as directed. Note : (i) Before manufacturing Boards drawing and design of Board including colour of board shall be approved. (ii) Each board display name shall be given seperately.
Fixing in repair illuminated display board of size (1.28 x 0.2 x 0.9) Mtr (L x B xH) with Flex of Light Blue (MES Colour) and grouted with PCC 1:4:8 for foundation including change all internal wirings and LED 40 W Tubelight fitting 01 No, SMC/FRP Junction Box 140mm x 140mm x 95mm inner dimension make Sintex/National complete all as specified and as directed.
M & L for scrapped down/peeled off old paint with abrasive paper and applying two coats of synthetic anamel paint of post office RED Colour on both side of board (size 1.5m x 1.5m) and re-writing the letters as "SAVE WATER SAVE ELECTRICITY" with White paint according to existing size of letters and two coats of black paint on its border and two fixing supports of MS round pipe of height 2.5 mtr complete all as specified and directed. Note : This job shall be carried out through professional Painter and decorator person.
M & L for scrapped down/peeled off old paint with abrasive paper and applying two coats of synthetic anamel paint of post office RED Colour on both side of board (size 1.5m x 1.5m) and re-writing the letters as "NO ADMISSION WITHOUT PERMISSION" with White paint according to existing size of letters and two coats of black paint on its border and two fixing supports of MS round pipe of height 2.5 mtr complete all as specified and directed. Note : This job shall be carried out through experienced Painter and decorator.
Supply only bamboo Ladder suitable for climbing upto 7.0 Mtr height complete all as directed. Make : as per sample.
Supply only Insulation tape roll size 18mm width and 6.5 Mtr length of superior quality complete all as directed. Make : as per sample.
Labour for cleaning the 3 mtr sarrounding area of LT Panel/Feeder Panel/Bus Bar Panel by removing/cutting out from roots of trees, bushes & sepplings etc and thrown away the same atleast 100 mtr away from the site complete all as directed
ELIEYAS TRADERS
Tejas Enterprises
KESARI AND SONS
SHAILENDRA B TULSANI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .