Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.3 LAccepted-AOC 37 222 BUNDU KATRA AGRA UP | AGRA | UP | L1 | Accepted-AOC L1 | |
| 2 | L2₹18.1 L+₹9,385 (0.52%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹18.4 L+₹37,930 (2.11%)Rejected-AOC 202 NEW RAM VIHAR COLONY PINTO PARK MORAR GWALIOR 474005 | GWALIOR | GWALIOR | MP | 474005 | L3 | Rejected-AOC L3 | |
| 4 | L4₹18.5 L+₹52,260 (2.91%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹22.8 L+₹4.8 L (26.5%)Rejected-AOC 43 VIMAL ENCLAVE CHAMRAULI MODE SHAMSHABAD ROAD AGRA UP 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | L5 | Rejected-AOC L5 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
3 Aug 2022, 6:00 pmClosed
GE Bharatpur
as per tender document
Repair/Replacement of internal electrification, ceiling Fan geyser sub main wiring DB, earthing and connected items in OTM/MD Accn at 39 FAD, Dayal Bagh MES IB in Mil Stn Bharatpur
2022_MES_535390_1
8167/E8
Open Tender
Civil Works
Item Rate
270 days
GE Bharatpur
as per tender document
6 documents required · 6 mandatory
₹500
GE Bharatpur
₹40,000
Yes
24 Aug 2022
2 Jul 2022
11 Aug 2022
2 Jul 2022
3 Aug 2022
18 Jul 2022
7 Jul 2022 - 16 Jul 2022
Amount
Disconnecting & taking down the ceiling fan of any sweep for carried out preventive maintenance and re hanging the same after cleaning the dust etc with air pressure, cotton cloth & brush, taking out ball bearing and bush, cleaning with kerosine oil, lubricating greasing, oiling, cleaning to winding including supply and replacement of nuts, bolts, rubber seal, split pin, connector and copper cable PVC size 3 core 0.5 Sqmm upto required lenght from ceiling rose to connector of ceiling fan including , connecting up and testing all as directed.
M&L for spray painting of ceiling fan of any sweep complete with blades, down rod etc with synthetic enamel paint of approved colour by spraying including filling cavaties with filler, preparation of surfaces cleaning all dust etc and writing of MES No of size not exc 5cm high using black enamelled paint all as directed. Note : Cost of disconnecting & taking down and rehanging is considered under item no 1
M&L for cutting and dismantling the existing winding of ceiling fan of 1200mm sweep and rewinding with super enamelled copper winding wire of suitable gauge including varnishing, lubricating, greasing, oiling and testing including replacement of ball bearing-02 Nos if required complete all as directed by Engr-in-charge.
Description all as per ser item No 03 here in above but 1400mm sweep ceiling fans including replacement of ball bearing-02 if required Nos complete all as directed by Engr-in-charge.
Supply and replacement of following parts/components suitable for ceiling fan 1200/1400mm sweep :-
Capacitor 2.5/3.5 mfd, oil filled, 400V AC, 50 HZ, 85 degree C ISI marked Make : Asian/Unistar/Usha.
Hanging clamp complete with rubber real Make as existing /sample kept in AGE E/M office complete all as directed by Engr-in-charge.
Fan Hook complete as standard real existing in market for fixed in GI Pipe/Existing Channel
Ceiling fan blade suitable for ceiling fan of any sweep (set of three blades)
Down rod 50 cm long 15mm internal dia heavy duty MS Pipe duly painted including hanging clamp, rubber ring, nut and bolts complete with canopy
Disconnecting & taking down the exhaust/wall fan of any sweep for carried out preventive maintenance and re hanging the same aftercleaning the dust etc with air pressure, cotton cloth & brush, taking out ball bearing and bush, cleaning with kerosine oil, lubricating greasing, oiling, cleaning to winding including supply and replacement of nuts, bolts, rubber seal, split pin, connector and copper cable PVC size 3 core 0.5 Sqmm upto required lenght from ceiling rose to connector of exhaust/wall fan including hanging, connecting up and testing all as directed. (Note for Srl item No 01 and 11 here in before : (i) Minor parts such as nut, bolt, washer,rubber seal, split pin, connector copper cable pvc insulated 0.5 sqmm 3 core are deemed to included with unit rate of item.(ii) Parts/components replaced other than mentioned above will be measured and paid separately under respective items. (iii) The services of ceiling fan carrying out door to door.(iv) After completion of work all fans shall be tested to the entire satisfaction of Engr-in-charge Note:Major item such as ball bearing, capacitor, fan blade etc shall be measured and paid seperately as supply only.)
M&L for spray painting of exhaust/wall fan of any sweep complete with blades, down rod etc with synthetic enamel paint of approved colour by spraying including filling cavaties with filler, preparation of surfaces cleaning all dust etc and writing of MES No of size not exc 5cm high using black synthetic enamelled paint all as directed.
M&L for cutting and dismantling the existing winding of exhaust/wall fan of any sweep with super enamelled copper winding wire of suitable gauge including varnishing, lubricating, greasing oiling testing incl replacement of ball bearing/GM bush as requiredcomplete all as directed by Engr-in-charge.
Supply and replacement of following parts/components suitable for exhaust fan 200 to 450mm sweep(PVC & Steel ,body) :-
Capacitor 4 mfd, oil filled, 400V AC, 50 HZ, 85 degree C ISI marked Make : Asian/Unistar/Usha.
Fan blade set (set of three) for exhaust fan of 380mm sweep.
Fan blade set (set of three) for exhaust fan of 450mm sweep.
Exhaust fan mounting bracket incl nuts,fastners
Exhaust fan motor of 200-300mm sweep as per existing PVC exhaust fan
Exhaust fan motor of 300-450mm sweep as per existing steel body exhaust fan
Louvers and shutters of PVC/ MS as per existing exhaust fan
Taking down U/S plug top and S&F new 3 pin plug top 16 amps, 230 volts, ISI marked. Make : Anchor/Kinjal /cona/ Recold/ Leader.
Taking down U/S plug top and S&F new 3 pin plug top 5 amps, 230 volts, ISI marked. Make : Anchor/Kinjal /cona/ Recold/ Leader.
Taking down of old unserviceable copper / aluminium flame proof point wiring (light,socket) with conduit complete including fitting & fixture such as switches, ceiling roses, light fitting etc removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions seperately) and making good disturbed surfaces of walls, floors etc complete.
Taking down old U/S sub main wiring Without conduit .
Taking down carefully copper/aluminium point wiring (light, fan, bell,same board, independent or power) complete fittings such as switches, ceiling roses, pendents, regulators, sockets etc removing materials for taking credit and making good disturbed surfaces of wall, floor & ceiling etc.
Dismantling of old U/S sub main wiring and service wire of any size & make with Conduit.
Dismantling of old U/S rusted main switch/DB of any size capacity and make.
M&L concealed point wiring complete with two runs of 2.5 sqmm, single core multi stranded copper conductor PVC insulated and unsheathed FRLS cable, 1100volts grade IS-694 marked drawn through and including rigid steel ERW conduit min 20mm dia ( stove enameled) heavy duty as per IS 9537 Part I and including all necessary flame proof , weather proof conduit accessories and fitting fixed to concealed in wall/ceiling with teflon tape sealed in all threaded joints in conduit and fittings for light points and including 2.5 sqmm (or nearest equivalent Metric size) single core multi stranded copper conductor PVC insulated and unsheathed cable 1100 volts grade continuity wire (connecting to earth dolly) & wiring shall be suitable for flame froof area as per STEC-7 for the following :-
Two light points controlled by one switch/MCB
One light points controlled by one switch/MCB
M&L submain wiring in existing conduit complete with 2.5 Sqmm single core multi standred PVC insulated and sheathed cable FRLS copper conductor two runs and one run of 2.5 Sqmm copper cable for earth continuity conductor complete all as specified and directed. Note :- Two runs of single core of 2.5 sqmm, one run of 2.5 sqmm earth continuity conductors shall be measured as one unit run length.
M&L concealed point wiring complete with 1.5 Sqmm 02 x single core multistranded copper conductor of 1100 volts grade PVC pre insulated FRLS and unsheathed cable enclosed in PVC conduit pipe size not less than 20 mm dia with all PVC accessories such as Tee, bend, collar, elbow, square junction box etc fixed on the concealed surface and making good the disturbed surfaces of wall/ceiling by means of Wall putty and matching colour of existing wall, PVCsleevel/dash fastners with cadmium plated screws including suitable size of PVC boards/ sunken box for mounting fittings like switches, sockets, fan regulator etc including 1.5 Sqmm insulated but unsheathed copper earth continuity conductor to common earth and connected to earth dolly complete all as specified and directed for the following :-
One light point controlled by one way switch.
One fan point controlled by one way switch.
One 3 pin 6 Amp socket point outlet on the same board with other switches
One 3 pin 6 Amp socket point outlet on the independent board
One bell/buzzer point controlled by one push button.
All as per item No 19 above but with multi stranded copper conductor cable 2.5 Sqmm size for 3 pin 16 Amps socket point outlet on independent board including 2.5 Sqmm copper cable PVC insulated FRLS unsheathed copper continuous earth wire including connecting to common earth dolly complete all as specified and directed.
M&L point wiring complete with 1.5 Sqmm single core multistranded copper conductor of 1100 volts grade PVC pre insulated FRLS and unsheathed cable enclosed in and including PVC casing and caping double locked box type with all PVC accessories such as Tee, bend, collar, elbow, square junction box etc fixed on the surface of wall/ceiling by means of PVCsleevel/dash fastners with cadmium plated screws including suitable size of PVC boards for mounting fittings like switches, sockets, fan regulator etc including 1.5 Sqmm insulated but unsheathed copper earth continuity conductor to common earth and connedcted to earth dolly for the following :-
One light point controlled by one way switch.
One fan point controlled by one way switch.
One 3 pin 6 Amp socket point outlet on the same board with other switches
One 3 pin 6 Amp socket point outlet on the independent board
All as per item No 21 above but with multi stranded copper conductor cable 2.5 Sqmm size for 3 pin 16 Amps switch socket outlet on independent board including 2.5 Sqmm copper cable PVC insulated FRLS unsheathed copper continuous earth wire including connecting to common earth dolly.
S&F ceiling rose surface bakelite three terminal ISI marked including suitable size of PVC board make : Anchor code No 3290 penta or equivelent make as specified in Appx 'B'.
S&F Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type multi purpose flush type 230 volt
S&F switch piano flush button single pole one way 6 Amps 230 volt grade
S&F switch piano flush button single pole one way 16 Amps 230 volt grade.
S&F socket 3 pin 16A, flush type
S&F bell push flush type 5 Amps 230 volts grade.
M&L bell multi musical type 230 volts grade.
S&F step type electronic fan regulator EME type 450 watt.
M&L concealed submain wiring complete with 6 Sqmm single core multi standred PVC insulated and sheathed cable FRLS copper conductor two runs and one run of 6 Sqmm copper cable for earth continuity conductor in and including drawn through PVC conduit size not less than 20 mm dia with all PVC accessories.Note :- Two runs of single core of 6 sqmm, one run of 6 sqmm earth continuity conductors and one run of 20mm dia PVC conduit with accessories shall be measured as one unit run length.
M&L concealed submain wiring complete with 4 Sqmm single core multi standred PVC insulated and sheathed cable FRLS copper conductor two runs and one run of 4 Sqmm copper cable for earth continuity conductor in and including drawn through PVC conduit size not less than 20 mm dia with all PVC accessories. Note :- Two runs of single core of 4 sqmm, one run of 4 sqmm earth continuity conductors and one run of 20mm dia PVC conduit with accessories shall be measured as one unit run length.
Supply and fixing of distribution board factory made and tested made of sheet metal enclosure powder coated suitable for mounting the MCB 240 volt, 415V of the following DBs
4 way TPN with busbar 415 volts (double door)
8 way SPN with 200 amps rated busbar 240 volts (double door type).
4 Way SPN with 200Amp rated busbar 240V (Double door type)
S&F in repair MCCB's, MCB's of following capacity :-
MCB TPN 63 Amps 415 volt, Category- C curve, 10kA rapturing capacity ( ISI marked IS-8828)
MCB TPN 32 Amps 415 volt, Category- C curve, 10kA rapturing capacity ( ISI marked IS-8828)
MCB SP 6-32 Amps, 240 volts,Category- C curve, 10kA rapturing capacity ( ISI marked IS-8828)
MCB SPN 6-32 Amps, 240 volt,Category- C curve, 10kA rapturing capacity ( ISI marked IS-8828)
MCB SPN 40 Amps, 240 volt,Category- C curve, 10kA rapturing capacity ( ISI marked IS-8828)
Supply and fixing in replacement of 20 watt LED tubelight fitting retro fit type 4 feet long with replacable rod complete with all accessories and including connecting up with three core twisted flexible copper conductor cable with suitable size of 230V, 50 Hz, complete all as specified and directed. make: Cromption or equivelent in Phillips/Surya/Helonix/Havells
Supply and fixing sensor based 20 watt LED tubelight fitting batten type 4 feet long with rod complete with all accessories and including connecting up with three core twisted flexible copper conductor cable with suitable size of 230V, 50 Hz, complete all as specified and directed. make: Cromption Cat No:R20RBA or equivelent in Phillips/Surya/Helonix/Havells
S & F lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings all incl 9watt LED lamp as directed by Engineer-in-charge.
S&F modular sheet metal enclosure of single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of SP 25 Amps, 240 volts.
S & F street light GI bracket of 0.6 mtr long made out of 40mm dia light grade GI pipe bend to shape of 120 degree end welded at required including 02 Nos MS clamp of FL 40 x 6mm including nuts bolts & washers complete necessary fixing arrangements on pole as directed.
S&F 35/36 watts LED street light fitings new generation energy saving, environmental friendly, long life, versatile pressure die cast aluminium IP66 with 10KV surge protection road way, luminaire with high power LED as light source with warranty option of 5 years and suitable drivers etc and connecting with 2.5 sq mm solid aluminium conductor PVC insulated twin core weather proof cable from fittings to over head lines or to the jucntion box and fixing to complete all as specified and directed , Make crompton Cat: LSTS-36 CDL-M or equivalent in Bajaj/Havells/Phillips
Supply and fixing LED luminaire 600 mm x 600 mm,35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cable of suitable size complete.Make crompton or equivalent in Bajaj/Havells/Phillips
M & L for Earthing complete with Galvanised steel earth plate electrode 600 x 600 x 6 mm buried directly in the ground vertically to depth not less than 3 Mtr below the ground level with the top edge of earth plate, depth not less than 2.25 Mtr below the ground level connected to GI earth wire 4mm dia by means of bolts, nuts and washers protected by GI tubing light grade 15 mm dia uptoTest point, 20 mm dia watering pipe with funel & wire mesh, PCC pit in PCC 1:2:4 using 20 mm stone aggregates chamber 40 mm thick RCC cover slab (1:2:4) type B-1 using 20 mm graded stone aggregates complete all as specified and shown in electrical plate No.3 of SSR Part-I including earth work in any type of soil ,removal of surplus sil and providing charcol dust & salt layers all around the earth plate upto 15 cm all as required specified & directed by engr in charge (Note:- Up to7.5Mtr length of pipe of 15 mm dia and GI wire shall be deemed tobe included in unit rate quoted by tenderer GI pipe and GI strip beyond 7.5) will be measured separately under respective item
Supply of Lithium based Energy efficient Integrated Solar Street Light of 32 Watt" in single FRP body with duly polyurethane coating (camouflage color), encases with monocrystalline solar PV panel of 65-67WP , Lithium Battery 11.1/12.8V, 33.0AH with inbuilt BMS, IP 65 high brightness W-led(160-180LM/WATT) lamp with aluminum reflector for better light distribution, CRI>70, Color Temperature 5700K-6500K, Microcontroller based charge controller cum driver, automatic dimming function (first four hours at full brightness& rest of the time at lower light level with PIR Motion sensor) . Dusk to Dawn operation, suitable to working temperature: (-) 10C to (+) 55C, weight not more than 16-18KG with adjustable MS clamp suitable for pole/wall mounting etc complete as required.Protections: Short Circuit, overload, Reverse polarity and battery protections, Firm should provide vital parameters test report from NABL accredited lab and should be of made in india with CE & ROHS compliant. Make Axxon (AXN-32W)
Supply and fixing in repair PVC Tape for insulation of 18mm width of 25RM length all as specified and directed.
Supply and fixing in repair Gang box switch socket combition for 5 Amp all as specified and directed.
Supply and fixing in repair Gang box switch socket combition for 15 Amp all as specified and directed.
Supply and fixing in repair 1.5sqmm copper conductor all as specified and directed.
Supply and fixing in repair capacitor 2.5/3.5/4.0 mfd 240V ISI mark complete
Supply and fixing in repair Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type multi purpose flush type 230 volt
Supply and fixing in repair switch piano flush button single pole one way 6 Amps 230 volt grade
Supply and fixing in repair Socket outlet 3 pin 15 amp flush type multi purpose flush type 230 volt
Supply and fixing in repair switch piano flush button single pole one way 16/15 Amps 230 volt grade
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole of the following sizes:-
16 Sqmm 4 core
10 Sqmm 2 core
M/s Ranaji Construction Co
AUTOMATION AND SWITCHGEAR CONTROL
krishna Associate
S S TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .