Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 CrAccepted-AOC | ₹2.7 Cr | L1 | Accepted-AOC Accepted being lowest |
| 2 | L2₹3.0 Cr+₹30.2 L (11.2%)Rejected-Finance 1ST FLOOR RAGHUNATH MARKET NEAR TELEPHONE EXCHANGE PATHANKOT 145001 | PATHANKOT | PUNJAB | 145001 | ₹3.0 Cr+₹30.2 L (11.2%) | L2 | Rejected-Finance Other than lowest |
| 3 | L3₹3.0 Cr+₹30.6 L (11.4%)Rejected-Finance | ₹3.0 Cr+₹30.6 L (11.4%) | L3 | Rejected-Finance Other than lowest |
| 4 | Rejected-Technical | - | - | Rejected-Technical Adverse remarks in WLR of CESC |
| 5 | Rejected-Technical 5037 5038 URBAN ESTATE PH 1 PATIALA 147002 PUNJAB | PATIALA | PATIALA | PUNJAB | 147002 | - | - | Rejected-Technical Adverse remarks in WLR of CEWC for QE Mar 2022 |
Tender Value
₹2.8 Cr
EMD Value
₹3.5 L
Closing Date
19 Aug 2022, 6:00 pmClosed
Chief Engineer Pathankot Zone
HQ Chief Engineer Pathankot Zone
PROVN OF STANDBY ELECT SUPPLY TO VERTICAL WIND TUNNEL PROJECT AT BAKLOH UNDER AGE (I) DALHOUSIE
2022_MES_537945_1
CEPZ-16/2022-23
Open Tender
Civil Works
Item Rate
180 days
AGE (I) Dalhousie
All as per tender Documents
8 documents required · 8 mandatory
₹2,000
AGE (I) Dalhousie
₹3.5 L
Yes
24 Sept 2022
14 Jul 2022
24 Aug 2022
14 Jul 2022
19 Aug 2022
5 Aug 2022
Amount
Supply, installation, Testing commissioning platform mounting of outdoor type, Step down transformer of 33/11KV, Capacity 3.15 MVA ONAN, 3 Phase, 50 Hz, Copper wound two winding, core type transformer as per IS -2026, Dyn 11 Vector group & IEC : 76 , OLTC+RTCC+AVR Tap Changer with indoor control panel , Tapping Range/Steps follows +5% to -10% in step of 2.5% each step,intial filling of transformer oil as per IS-335 mounted on PCC platform with mounting of rail channel as per manufacturer's, instruction and drawing complete with making connection from 33 KV HT bussing on 33KV side and cable end box on 11KV side including following acessories of complete all as specified:- Fittings and Accessories:- (i) Rating & Diagram Plate : 01 No (ii) Earthing Terminals : 02 Nos (iii) Lifting Lugs : 04 Nos (iv) Oil Level Indicator with minimum level marking: 01 No (v) Thermometer Pockets: 02 Nos (vi) Conservator ( Conventional without Air bag) with oil filling hole with cap and drain plug: 01 No. (v) Air Release Plug : 01 No (vi) Silica Gel breather : 01 No (vii) OLTC+RTCC+AVR : 01 No (viii) Bi-directional Rollers : 04 Nos (ix) Radiators (x) Explosion Vent (xi) Bottom drain-cum Filter Valve. (xii) Top filter Valve. (xiii) Dial type OTI & WTI with A&T Contacts : 01 No (xiv) Buchholz relay with trip and alarm contact & A&T contacts : 01 No (xv) Marshalling Box : 01 No (xvi) Shut of valve between conservator and bachholz relay (xvii) Winding temp. thermometer with electrical contacts for alarm / strip and controlling fan.
Supply ,installation,testing and commissioning of VCB out door type , 36 KV for user on system with nominal voltage 33 KV, 3 Phase, 50 HZ as per IEC-62271-100 complete with all accessories and of the following technical specifications of complete with support strutures all as specified and as directed by Engineer-in-Charge. (a) Rated continuous at designed ambinet temp : 800 Amps (b) Rated normal current : 800 Amps (c) Rated power frequency withstand voltage : 95 KV (rms) (d) Rated lightning impulse with stand voltage 200 Kvp (e) Short circuit breaking current : 36.3 KA (f) Short circuit making current : 65.75 Kap (g) Rated duration of short circuit 3 seconds (h) Minimum creep age distnace to ground ; 1155mm min. (j) Type of mechanism enclosed in housing ; Motor operated spring-spring (k) Rated operating sequence : 0-0.3 Sec-CO-3 MIN-CO (l) Rated closing/tripping voltage : as per manufacturer design (m) Current of closing/tripping coil : 6 A max at 110 VDC (n) Rated current for terminal connections : 800 Amps (o) Rated break time as per IEC not more than 3 cycles. (p) Total closing time not more than 5 cycles.
Supply ,installation,testing and commissioning of VCB out door type ,33 KV nominal voltage 3 Phase, 50 HZ as per IEC-62271-100 complete with all accessories and of the following technical specifications of complete all as specified and as directed by Engineer-in-Charge. (a) Rated continuous at designed ambinet temp : 630 Amps (b) Rated normal current : 630 Amps (c) Rated power frequency withstand voltage : 70 KV (rms) (d) Rated lightning impulse with stand voltage 170 Kvp (e) Short circuit breaking current : 25 KA (f) Short circuit making current : 62.51 Kap (g) Rated duration of short circuit 3 seconds (h) Minimum creep age distnace to ground ; 1155mm min. (j) Type of mechanism enclosed in housing ; Motor operated spring-spring (k) Rated operating sequence : 0-0.3 Sec-CO-3 MIN-CO (l) Rated closing/tripping voltage : as per manufacturer design (m) Current of closing/tripping coil : 6 A max at 110 VDC (n) Rated current for terminal connections : 630 Amps (o) Rated break time as per IEC not more than 3 cycles. (p) Total closing time not more than 5 cycles.
Supply, installation ,testing and commissioning of 33 KV Single Phase,outdoor, Oil cooled current transformer incommer CT 150-75/ 5-5A class 1.0/5P10 burden 30VA 25KA/ 1SEC HSV 36KV I.L 36/70/170KVP for metering , accuracy with oil as per IEC-60044-1 & IS-2705 suitable for 33 KV, 630 Amps ,SF6 breaker output supply complete all as specified and as directed by Engineer-in-Charge.
Supply, installation ,testing and commissioning of 33 KV Single Phase,outdoor, Oil cooled current transformer incommer CT 300-150/ 5-5A class 0.5/5P10 burden 30VA 25KA/ 1SEC HSV 36KV I.L 36/70/170KVP for metering , accuracy with oil as per IEC-60044-1 & IS-2705 Suitable for 33 KV, 800 Amps ,SF6 breaker output supply complete all as specified and as directed by Engineer-in-Charge.
Supply, installation ,testing and commissioning of 33 KV Single Phase,hermetically sealed, outdoor, oil cooled potential transformer incommer PT of ratio 33 KV/rt3/110 V/rt3/110V/rt3, Class 0.5-3, burden 100 VA complete for metering , accuracy with oil as per IEC-60044-1 & IS-2705 suitable for 33 KV complete all as specified and as directed by Engineer-in-Charge
Supply and fixing of lightening arresters, expulsion type, complete all fittings, transmission class, discharge capacity 100 kilo amp, suitable for working in 33000 volts complete all as specified and directed.
Supply and fixing of HT 33 KV Outdoor, double break, triple pole, revolving type and double break suitable for horizontal mounting, three phase, gang operated, horizontally manual operated with earth switch, along with 33 KV soild core insulator having creepage distance 900mm, with terminal connector switch of 400 Amps rating confirming to IS: 1818-1972 complete all as specified and directed.
Supply and laying in trenches/fixed to walls/poles etc and commissioning HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables heavy duty (Earthed) with aluminium conductor 33000 volts grade with standard aluminium conductor of size 300 Sqmm , 3 core complete all as specified and directed.
Supply & fixing cable jointing kit for HT, 33KV (Earthed) grade cable for outdoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core, XLPE, armourie aluminium conductor cable, size 300 Sqmm , complete all as specified and directed by Engineer-in-Charge.
Supply and fix of pin type procelain, viterous, white, brown or green insulator incl one galvanised MS spindle, two galvanised iron washer and one galvanised iron nut, 240mm high 240 mm dia for 33000 volts grade complete all as specified and directed.
Supply and fix of disc type procelain, viterous, white, brown or green insulator incl one galvanised MS spindle, two galvanised iron washer and one galvanised iron nut, 350 mm dia for 33000 volts grade complete all as specified and directed.
Supply and fix of pin type procelain, viterous, white, brown or green insulator incl one galvanised MS spindle, two galvanised iron washer and one galvanised iron nut, 150mm high 150 mm dia for 11000 volts grade complete all as specified and directedd.
M&L for disc type insulators porcelain vitreous enamel 145 mm high and 255 mm dia ball and socket type brown or green single disc assy for tension with tension clamps for conductors working pressure 11000 volts including taking down existing.
Supply and fixing of clamp of made of aluminium sheet 50x3mm size for over head bus bar suitable for ACSR conductor all as specified and directed.
Material & labour for aluminum conductor, steel reinforced bus bar system on steel structure/ steel tubular pole,of suitable size for HT volts complete all as specified and directed.
M&L for anti-climbing device, spikes type fabrication out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
M&L for cross arm bracing support clamps and back plates fabricated from structural steel sections including nuts, bolts and washers welding bending cold or hot drilling holes for bolts in any shape or sizes as indicated or directed inclusive of one coat of primer and two coats of aluminium paint all as directed..
M&L for stringing & fixing galvanized steel wire 4/ 6mm dia continuous earth wire on overhead line incl necessary binding with binding wire all as specified
M&L for galvanized stay strand size 7/4 incl taking down the unserviceable stay wire complete all as specified & as directed by Engineer-in-Cahrge.
Supply, installation, testing and commissionong of DC control panel of 30 volts DC dry type chargeable stationery battery set consist 15 cell of 02 volts each having 90 amps hour capacity with maintenacne free batteries including battery charging set of adequate capacity and control equipment sheet steel abinet floor mounted type suitable for input of 230 volts, single phase 50 Hz AC complete with external and internal wiring of all components, accessaries all as specified for 33 KV & 11 KV VCB panels. Complete control wiring (for connecting the DC tripping set HT 33 KV and 11 KV VCB panel board complete ) shall be copper conductor single core and size not less the 2.5 sqmm complete and comprising of the follwoing accessories :- (i) DC Ammeter/Voltmeter in 96 Sqmm size. (ii) Step down trnasformer. (iii)Choke to limit the inrush current. (iv) Variac (Auto - transformer) for the manual stepless charging. (v) Silicon Rectifier stack. (vi) Auto off manual switch. (vii) Set of protection fusese. (viii) Set of indicating lamp to indicate position of charging on auto boost, auto trickle, main on, battery earth and fuse failure. (ix) Battery switch to indicate the battery voltage.
Supply and installation, testing and commissioning of HT 11 KV ,630 Amp, 20 kA VCB Panel , Horizantal isolation, Horizantal Drawout , Indoor type with 1 No. Bus PT metering 5- way comprising of 02 Nos, motorised charging fixed - type Vacume Circuit Breaker as Incomer and 02 Nos motorised charging fixed -type Vacuum Circuit Breaker as Outgoing and 01 No of Buscoupler for operating to 02 incomer HT 11 KV supply . VCB panel inside robotically welede stainless steel 304 (Non Ferrite Non Megenetic Grade) tank having min. thickness 2.0 mm with IP67 Degree of Protection and internally to manage voltage surges. VCB Panel should be provided with intenal busbars, as well as earthing busbars of elecetrolytic grade copper, pedlock provisions, spring charging handle & complete with all acessaries. The VCB Panel shall be type tested of internal arc as per IEC 62271-200. Suitable battery charger as per nos of function of panel shall be provided complete as per manufacturers designed all as specified and directed . (A) 11KV, 630A, 20kA, Horizontal Drawout type VCB Module-VD4 (i) 11KV Indoor AIS VCB Panel with IP4X protection (ii) 230v Motorised Mechanism (iii) Closing & Tripping Coils voltage - 240Volt (iv) 800 Amps Aluminium Busbar, having HT Heat shrinkable sleeves (v) Colour coded wiring, CT-2.5 sqmm, PT & other circuit - 1.5 sqmm. (vi) Poweder Coated, Paint Shade-RA-7032
(F) ACCESSORIES (i) Trip Neutral Close Switch, 3 position (Non-Lockable type) (ii) Local - Remote (L/R Switch), 2 Pole , 2 way, 2 position (iii) Panel Space Heater (iv) 230V AC Thermostat (v) Toggle switch for Heater ON/OFF (vi) Panel Illumination Lamp (vii) Pin Plug with switch (Switch & socket box) (viii) MCB for AC (ix) 8 Windows Annunciator (x) Electronic Hooter (xi)Battery Backed up Power pack 230 V AC/ 24 V DC (G) RELAYS (i) Numerical 3 O/C (50,51) + 1 Earthfault (50N,51N) Relay with inbuilt trip circuit supervision(95), Antipumping (94), Differential Protection, UV/OV & Fuse Failure (ii) Numerical 3 O/C (50,51) + 1 Earthfault (50N,51N) Relay with inbuilt trip circuit supervision(95) (iii) Master Trip Relay (86) (iv) DC Failure Relay (v) Transformer Aux protection Relay for Winding, Oil, CZ, MOG, OSR.
Supply and install HT 11 KV, 400 Amp outdoor type gang operated single break switch tilting type vertical mounting consisting of hot dip galvanised channel iron base having 11 KV Post type insulator in stack and 3 stack per phase copper or copper alloy high pressure heavily tinned contacts plated MS arcing horns capable of breaking the magnetizing current complete with horizontal connecting square bar, GI pipe as down rod levers coupling & operating handle with locking arrangement.
Supply and install drop out lift OFF HT 11 KV, 400 Amps fuse link consisting of channel iron base having 11 KV post type insulators in stack & 2 stack per phase complete with fuse carrier of SRBP tube with heavily tinned non ferrous metal parts and spring loaded phosphor bronze contact complete manufactured as per IS 9385 complete all as specified and directed.
Supply and fixing of Lightning arresters, expulsion type, complete with all fittings, transmission class, discharge capacity 65 kilo amp, suitable for working in 11000 volts complete all as specified and directed.
Material and labour for Copper stranded control cable in ducts from 33 KV Yard to Panel Room 2.5 sqmm 2 core armoured cable complete all as specified and directed.
Material and labour for Copper stranded control cable in ducts from 33 KV Yard to Panel Room 2.5 sqmm 4 core armoured cable complete all as specified and directed.
Material and labour for Copper stranded control cable in ducts from 33 KV Yard to Panel Room 2.5 sqmm 6 core armoured cable complete all as specified and directed.
Material and labour for Copper stranded control cable in ducts from 33 KV Yard to Panel Room 2.5 sqmm 8 core armoured cable complete all as specified and directed.
Supply and laying in trenches/fixed to walls/poles etc and commissioning HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables heavy duty (Earthed) with aluminium conductor 11000 volts grade of size 185 Sqmm , 3 core complete all as specified and directed.
Supply and lay in trenches/fixed to walls/poles etc and commissioning LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables heavy duty with aluminium conductor 1100 volts grade with stranded aluminium conductor of size 10 Sqmm , 2 core complete all as specified and directed.
Supply and lay in trenches/fixed to walls/poles etc and commissioning LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables heavy duty with aluminium conductor 1100 volts grade with stranded aluminium conductor of size 35 Sqmm , 3.5 core complete all as specified and directed. ("Note item No 32 to 38 :- Excavation & earthwork if required shall be measured & paid separately under relevant items of this schedule.")
M&L cable jointing kit for HT, 11KV (Earthed) grade cable for indoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core, XLPE, aluminium conductor cable, size 185 Sqmm , complete all as specified and directed by Engineer-in-Charge.
M&L for cable jointing kit for HT, 11KV (Earthed) grade cable for outdoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core, XLPE, armourie aluminium conductor cable, size 185 Sqmm , complete all as specified and directed by Engineer-in-Charge.
M&L for stay assembly complete with accessories as shown in electric plate No.1 on page No 495 of SSR-2009 stay rod 20mm (loop type insulator stay clamps excavation & concrete measured separately all as directed.
M&L for loop type insulator vitreous porcelain, white or brown or green at large size with over all dimension 90x140mm clearance of hole 25.5 mm complete all as specified and directed.
M&L for danger notice plate of 1.6 mm thick MS sheet vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps nuts bolts of approved size complete for HT 33000/11000 volts of size 25x20 cm complete all as specified & as directed by Engineer-in-Cahrge.
Supply and erection of steel tubular swaged poles complete with cast iron base plate funnel taper plug bolts nuts & screws as specified type 410 SP 55, 11m long in truly vertical position till setting of PCC foundation complete all as specified and directed. (Note :- Excavation of post hole, PCC required for foundation and coping will be measured & paid under relevant items of Sch 'A'.)
Supply and erection of steel tubular swaged pole 410 SP 31, 9 Mtr long complete with cast iron base plate, finial Taper plug, bolts, nuts, and screws as specified type conforming to IS 2713 complete including 2 coats of aluminium paint over one coat of red oxide zinc chrome primer on external exposed surfaces and 2 coats of black bituminous paint on portion embedded in concrete in internal surfaces of pole complete all as specified and directed. (Note: Excavation, PCC work only shall be measured & paid Seperately under relvent item .)
M & L for shifting of 11 mtr two pole structure after carefully dismantling of MS chanel, bracket, clamp, nut, bolt and washer with existing LAs (one set), GOD (one set ) , DO fuse (one set) of 11 KV supply with dismantling of HT cable connection with complete demolition of work for coping/foundation of pole and refixing not more than 50 mtr for existing place with same structure with complete set of GOD, LA set and DO fuse with MS chanel, bracket, clamp, nut, bolt and washer and all HT cable connection carefully without damaging the equipment and testing after commissioning the equipments complete all as specified and directed. Note: (a) All T & P required for shifting of above mentioned equipments shall be included in quoted rates. (b) In any case of damage to any equipment during shifting ,shall be replace by the contractor with new without any extra cost . (c) Excavation for pole fountaion, PCC required for foundation and coping will be measured & paid under relevant items of Sch 'A'.
M&L for PCC type C2, 1:3:6 using (40 mm graded crushed stone aggregate) in foundations complete all as specified and directed.
M&L for PCC type B-1, 1:2:4 using (20 mm graded crushed stone aggregate) for coping, including form work complete all as specified and directed.
Material and labour for MS flat 50 x 6 mm for connecting earthing electrode to fencing equipments, earthing mesh in the yard etc complete all as specified and directed by Engr-in-Charge. Note :- (i) MS flat will be buried 60cm below ground level (ii) Cost of excavation and earth work wherever required is deemed to be included in the quoted rates nothing extra on this account shall be payable to contractor.
M & L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below the normal ground level ) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron strip 32X6mm by means of nuts bolts,washers,check nuts of GI steel all as shown in electric plate no 3 of SSR -2009 Part-I, all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe medium grade 40mm and GI watering pipe 20mm light grade with funnel and wire mesh ,40mm thick pre-cast RCC M-15 (nominal mix) cover reinforced with XPM weight not less than 4 kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover ,PCC M-15 (nominal Mix) pit,excavation and earth work in any type of soil and connected all as specified and as directed.
M & L for Earthing complete with copper earth plate electrode 600x600x 3.15 mm burried directly in ground not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.25 Mtr below normal ground level connected to the copper strip 20x3 mm size by means of bolts ,nuts,check nuts and washers of brass and 20x3 mm copper strip protected by provision of GI medium grade pipe 40 mm bore incl provision of concrete pit in PCC1:2:4 type B-1 , using 20 mm graded stone aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia bar handle ,excavation and earth work in any type of soil ,charcoal dust and salt light grade GI watering pipe 20 mm bore with funnel and wire and copper strip upto main earthing of pole/equipment complete all as shown in electrical plate No 3 of MES Sch 2009 Part-I all as specified and directed . Note:-(i) Up to 7.5 Mtr length of pipe of 40 mm dia and copper strip shall be deemed to be included in unit rate quoted by tenderer. ‘(ii) Resistance of earthing should be less than 1 Ohms failing which the contractor will do the earthing again to achieve the desired result i.e. less than 1 ohms. (iii) In case soil is not suitable same is to be replaced with good quality clay soil to achieve the desired result of less than 1 ohms.
M & L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below the normal ground level ) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron wire 4mm dia by means of nuts bolts,washers,check nuts of GI steel all as shown in electric plate no 3 of SSR -2009 Part-I, all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe medium grade 20mm and GI watering pipe 20mm light grade with funnel and wire mesh ,40mm thick pre-cast RCC M-15 (nominal mix) cover reinforced with XPM weight not less than 4 kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover ,PCC M-15 (nominal Mix) pit,excavation and earth work in any type of soil and connected all as specified and as directed.
Supply and fixing for GI strip 32 x 6 mm complete with saddles/insulators made out of porcelain or fibre and fixing screws for roof conductor/down conductor including welding or brazing for joints all as required at site complete all as specified and directed.
Material and labour for earthing strip 50x5 mm copper strip with suitable extension pieces to the structure including screws complete all as specified and directed.
Material and labour for pea size gravel 20 to 40 mm graded hand packing (any thickness ) in sub station all as per latest engineering practice and specified and directed .
Material and labour for Copper stranded control cable in ducts from 33 KV Yard to Panel Room 2.5 sqmm 12 core armoured cable complete all as specified and directed.
M&L for cutting and fixing of chequered plate for 7mm thick for inside sub station/VCB panel room openable cable duct with complete fixing arrangement all as specified and directed.
Supply and laying of rubber mat of size 1meter x 2meter x 3 mm thick suitable for HT protection at inside Sub station yard suitable for 33 KV HT supply protection complete all as specified.
Supply and laying of electrical safety rubber mat for HT floor 3 mm thick mating suitable for 11KV supply laying /pasting on floor surface inside panel room for prtection of sock complete all as specified and directed .
Supply and fixing LED street light fitting 70 Watt, 230 V, AC, outdoor type with high pressure die cast aluminiumhosing and heat resistant complete with driver, lamp bracket with impact and corrision resistant including thermal management in multiple optics complete with IP 65/66 protection and connecting up to looping box with PVC insulated multi stranded copper conductor cable 1.5 sqmm twin Core complete all as specified
S & F FRP moulded cable looping box of size 250 mm x200 mmx115 mm complete with electrolytic aluminum bus bar of 100A capacity for 3 phase and neutral fixed on ebonite insulator and one MCB 6-16 A complete all as specified and directed.
M&L for installation the weather proof, vermin proof feeder piller box outdoor type of suitable size made out of 3.15mm thick MS Sheet including support of angle iron of suitable size to take the load and with PCC platform minimum 30 cum above of ground level with double door and suitable locking arrangment dully painted with two coats of synthetic enamel paint over a coat or red oxide primer and comprising of the following :- (A) INCOMING - (a) MCCB 63 Amps, 4 pole 415 volts - 01 No Adjustable thermal & magnetic setting type, 16 kA breaking cap. – 01No. (B) OUTGOING - (a) MCCB 40 Amps, 4 pole 415 volts - 01 No Adjustable thermal & magnetic setting type, 16 kA breaking cap. – 01No. (b) MCB 32 Amps, 4 pole 415 volts - 02 No Adjustable thermal & magnetic setting type, 16 kA breaking cap. – 02No. (c) Multi function meter having LCD Display,96 x 96 sq.mm -01 No (d) Current transformer of suitable ratio, Accuracy - 5VA, Class - 1. (e) LED INDICATORS RIBBED LENS WITH TRIMMED COLLAR - Red, Yellow and Blue - 1 Each, (f) Aluminium bus bar for suitable 100 Amps rating for R-Y-B phases and Neutral. (g) Base frame for cubical mounting made out of 40x40x6mm equal angle iron duly painted. (h) Foundation for the panel should provided with PCC 1:4:8 at a depth of 150 MM below G.L. and 100 MM above the G.L. with slot openings for incoming and outgoing cables.
M&L for PCC M-20 nominal mix, type B-1, using 20mm graded crushed stone aggregagte as in earthing pit and like including weathering, slightly rounded or chamfered angles and throating including necessary form work, complete all as specified and directed
M&L for form work to sides of pillers posts, struts, piers,columns and stanchions in square or rectangular complete all as specified and directed
M&L for Mild steel round bars 10 to 12 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hopping for columns, hooking endsand binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clip complete all as specified.
M&L for Mild steel round bars 6 to 8 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hopping for columns, hooking endsand binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clip complete all as specified.
Excavation in trenches for not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out in hard/dense soil including taking out faulty cable/cable, cable covers and GI pipe complete all as specified and directed.
Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed.
Removing excavated materials n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point.
M & L for dry river sand as sand cushioning for protection of UG cable including punning down of sand in layers all as specified.
Supply & laying un-reinforced precast concret cable cover class LV type 1, flat size 250mm x 150mm x 40 mm all as specified & directed.
Supply & laying reinforced precast concret cable cover class EHV type 1, flat size 450mm x 230mm x 50 mm all as specified & directed.
M&L for LED display glow sign PVC board for Bakloh cantt main Electic supply installtion and inside the borad moulded letter for writing 250/400mm hight illuminated after provide to power supply for the board and letters are display on the board for " MAIN RECIVING 33/11 KV HT SUB STATION AGE (I) DALHOUSIE" on top of the board and ''(MES BAKLOH)'' at the bottom of the board with both side MES Logo on the board complete with fixing arrangement of the board in the gate coloums with suitable size Angle iron frame and should be fixed to the main gate of Electric sub staion yard on the top of two vertical coloums with complete grouting and fixing arrangement by using of anchor fastner including testing after fixing of glow sign board complete with PCC work complete all as specified and directed .
M&L for GI pipe Light grade 100 mm bore for protection of HT cable with all fittings complete laid in trenches/fixed on pole complete all as specified and directed.
M&L GI pipe Light grade 40 mm bore for protection of LT cable with all fittings complete laid in trenches/fixed on wall surface complete all as specified and directed.
JCC ENGINEERS PRIVATE LIMITED
N K BUILDERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .