| Sl No | Description | Qty | Unit | ravinder sangwan contractor L2 | ALTOZ AUTOMATION L1 |
|---|---|---|---|---|---|
| 1.00 | Installation and accessories like Cabling as per site requirements, Panel Box etc.. Commissioning Charges of Flow Meter, Customization and programming of flow meter, Configurations as per site requirements and making connection with the existing SCADA software, Head Office, HSPCB and CPCB to the satisfaction of Engineering In-charge, including one year maintenance charges | 2 | Nos | 80,000 ₹1,60,000 | 70,000 ₹1,40,000 Lowest |
| 2.00 | Supply and installation ,Commissioning of DI fitting duly ISI marked as per IS:9523:2000(K12)(PN-10)500MM Flange socked 2nos. Including the cost of nut bolt and rubber ring and rubber sheets | 1 | Nos | 60,000 ₹60,000 Lowest | 60,000 ₹60,000 Lowest |
| 3.00 | Supply of Ultrasonic Type ultra sonik Flow meter to be installed On open channel with display. Input power Supply 24 VDC, 2 Wire Transmitter, HART .Protocol ,output: 4- 20MA, Process connection: 1 ½” BSP Threaded . OUTLET Make :- Altoz Automation , AQUADAX, Flickcon | 1 | Nos | 1,95,000 ₹1,95,000 | 1,90,000 ₹1,90,000 Lowest |
| 4.00 | Supply, Fixing, testing and commissioning of Remote Terminal Unit with power analyzer having inbuilt
GSM / GPRS modem. RTU suitable for multi parameter for transferring data to HPSC/PHED complete in all respect. (Make-:- Altoz Automation , AQUADAX, Flickcon with one year warranty) | 1 | Nos | 1,27,000 ₹1,27,000 | 1,25,000 ₹1,25,000 Lowest |
| 5.00 | Supply, Installation, testing and commissioning Electromagnetic Flow Meter Model No: UPCS MAG -110 W:Accuracy Class and Display:± 0.5% of measured flow: 2 Line LCD R:Indicator Converter Type: Remote, field mounted 4:Power Supply: Universal Power Supply 85 to 265VAC@45
to 65 Hz 2:Output:4 to 20mA 2:Communication Interface: RS 485 (MODBUS RTU) 0:Data Logger: Not Applicable N:Cable Entry:1/2`NPT Sensor Size (mm): 500mm 3:Pressure Rating(Kg/cm2):16 Kg/cm2
D:Design of the Measuring Sensor: Flanged-DIN
1:Flange Material: CS 6:Electrode Material:SS316
1:Earthing ring: None. With built-in earthing electrode.
4:Measuring Tube:SS304 2:Coil Housing: CS
8:Protection Class for Sensor:IP68 P:Approval:Non Hazardous area Cable L=20 mtrs (Make:- Altoz Automation , AQUADAX, Flickcon. | 1 | Nos | 5,95,000 ₹5,95,000 | 5,90,000 ₹5,90,000 Lowest |
Tender Value
₹5.5 L
EMD Value
₹10,940
Closing Date
30 Jun 2026, 3:00 pmClosed
AMIT JAIN
Mohindergarh PHED
flow meter along
2026_HRY_531023_1
202693AD0B08 A200 443A 8545 219F9441C01C597PUH
Open Tender
Civil Works
Works
365 days
Mahendragarh
2 documents required · 2 mandatory
₹1,000
₹10,940
Yes
25 Aug 2026
23 Jun 2026
30 Jun 2026
23 Jun 2026
30 Jun 2026
23 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Installation and accessories like Cabling as per site requirements, Panel Box etc.. Commissioning Charges of Flow Meter, Customization and programming of flow meter, Configurations as per site requirements and making connection with the existing SCADA software, Head Office, HSPCB and CPCB to the satisfaction of Engineering In-charge, including one year maintenance charges | 2 | Nos | - | - |
| 2 | Supply and installation ,Commissioning of DI fitting duly ISI marked as per IS:9523:2000(K12)(PN-10)500MM Flange socked 2nos. Including the cost of nut bolt and rubber ring and rubber sheets | 1 | Nos | - | - |
| 3 | Supply of Ultrasonic Type ultra sonik Flow meter to be installed On open channel with display. Input power Supply 24 VDC, 2 Wire Transmitter, HART .Protocol ,output: 4- 20MA, Process connection: 1 ½” BSP Threaded . OUTLET Make :- Altoz Automation , AQUADAX, Flickcon | 1 | Nos | - | - |
| 4 | Supply, Fixing, testing and commissioning of Remote Terminal Unit with power analyzer having inbuilt
GSM / GPRS modem. RTU suitable for multi parameter for transferring data to HPSC/PHED complete in all respect. (Make-:- Altoz Automation , AQUADAX, Flickcon with one year warranty) | 1 | Nos | - | - |
| 5 | Supply, Installation, testing and commissioning Electromagnetic Flow Meter Model No: UPCS MAG -110 W:Accuracy Class and Display:± 0.5% of measured flow: 2 Line LCD R:Indicator Converter Type: Remote, field mounted 4:Power Supply: Universal Power Supply 85 to 265VAC@45
to 65 Hz 2:Output:4 to 20mA 2:Communication Interface: RS 485 (MODBUS RTU) 0:Data Logger: Not Applicable N:Cable Entry:1/2`NPT Sensor Size (mm): 500mm 3:Pressure Rating(Kg/cm2):16 Kg/cm2
D:Design of the Measuring Sensor: Flanged-DIN
1:Flange Material: CS 6:Electrode Material:SS316
1:Earthing ring: None. With built-in earthing electrode.
4:Measuring Tube:SS304 2:Coil Housing: CS
8:Protection Class for Sensor:IP68 P:Approval:Non Hazardous area Cable L=20 mtrs (Make:- Altoz Automation , AQUADAX, Flickcon. | 1 | Nos | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.84 MB
BOQ_610070.xls
BOQ • 0.23 MB
1HB6ARZ167226.pdf
Additional Documents • 0.14 MB
OT0167226.pdf
Other Document • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .