Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹32.3 LAccepted-Finance | 1 | Accepted-Finance Accepted | |
| 2 | 2₹33.3 L+₹97,180 (3.01%)Accepted-Finance | 2 | Accepted-Finance Accepted | |
| 3 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹33.3 L
EMD Value
₹67,000
Closing Date
30 Aug 2024, 11:00 amClosed
EXECUTIVE ENGINEER ED KULGAM
EXECUTIVE ENGINEER ED KULGAM
Augmentation of 4x63KVA Sub-Stations at Bogund, Srandoo, Kanipora, 100kva at Boh, Repl of old 100kva transformer at Qaimoh and Petrol Pump Kawaki Bazar, 1 No of 63KVA Dregden , and buffer stock of 63kva and 100kva under District Capex DDC Grants
2024_PDD_256333_1
EDK/e-tender/08 of 2024-25
Open Tender
Electrical Works
Turn-key
90 days
ED KULGAM
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
EXECUTIVE ENGINEER ED KULGAM
₹67,000
10 Sept 2024
10 Aug 2024
30 Aug 2024
10 Aug 2024
30 Aug 2024
10 Aug 2024
10 Aug 2024 - 28 Aug 2024
Amount
Augmentation/Replacement of 63 & 100KVA Substations
Supply, Installation, Testing and commissioning of 200kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff. Location BOH DH PORA
Supply, Installation, Testing and commissioning of 100kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff. Location Nai Bastie Qaimoh, Kawaki Bazar, Kanipora, Kumar Mohalla Bogund and Kharpora Srandoo.
Supply, Installation, Testing and commissioning of 63kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff. Location DREGDAN DH PORA
Supply , carriage, Testing and unloading at Divisional Stores of 100kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate.
Supply , carriage, Testing and unloading at Divisional Stores of 63kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff.
Safe Backcarriage, loading and unloading of old 63kva transformer from Boh, Kanipora,Kumar Mohalla Bogund and Kharpora Srandoo to divisional stores.
Safe Backcarriage, loading and unloading of old 100 kva transformer from Dregdan, Naibastie Qamoh and Kawakibazar Qaimoh to divisional stores.
Supply of Transformer Oil to Divisional stores for Block Qaimoh
Supply, laying of 300 mmsq Single Core cable, 1.1KV Grade, XLPE insulated stranded conductor, FRLS unaroumed Cable
Supply, laying of 150 mmsq Single Core cable, 1.1KV Grade, XLPE insulated stranded conductor, FRLS unaroumed Cable
Supply, laying of 70 mmsq Single Core cable, 1.1KV Grade, XLPE insulated stranded conductor, FRLS unaroumed Cable
Supplying and fixing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing anf fixing of suitable LT Fuse set Horn Gap Type as per approved drawings og KPDCL.
Supply, Erection and testing of 9Mtr. Long ST Pole SP33 with base plate and cap strictly as per REC Standards
Providing & fixing of GI Channel/Angle/Flat of sizes including clamps
Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs duly anthenticated by AEE concrened.
Supply,fixing, testing & commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type as per IS Standards
Supply,fixing, testing & commissioning of 11 kV Horn Gap Fuse Set 3-Phase 200A as per IS Standards
Supply,fixing, testing & commissioning of 11 kV Gapless Surge Arrestor, 3-Phase, 9 kV ,10 kA ,LA with polymer housing, Stn. Type as per IS Standards
Supply,fixing, testing & commissioning of 11 KV Pin Insulators (polymer/porcelain) with Pins(5KN)
Cement bottoming 1:2:4 mix as per REC Standards 0.5cum/pole
Providing & fixing of Sundry items like aluminium lugs, Jumpers, binding Tape etc
Supply Installation Testing and commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing, Fixing of GI nuts and bolts for fixing of x-arms and other accessories.
Providing and fixing of Danger Plates with clamps.
M/S Itoo Electrical
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .