| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.4 LAccepted-AOC | ₹16.4 L Quoted ₹16.8 L | L1 | Accepted-AOC lowest bidder |
| 2 | L2₹17.6 L+₹82,710 (4.92%)Rejected-Finance | ₹17.6 L+₹82,710 (4.92%) | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹18.6 L+₹1.8 L (10.6%)Rejected-Finance 0 MANPUR CHITBARAGAON CHITBARAGAON BALLIA UTTAR PRADESH 221713 | BALLIA | UTTAR PRADESH | 221713 | ₹18.6 L+₹1.8 L (10.6%) | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 4 | L4₹19.0 L+₹2.2 L (13.3%)Rejected-Finance | ₹19.0 L+₹2.2 L (13.3%) | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 5 | L5₹22.9 L+₹6.1 L (36.1%)Rejected-Finance | ₹22.9 L+₹6.1 L (36.1%) | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | M/S AKHILESHWAR ASSOCIATES L1 | G M ENGINEERING SERVICES L6 | M/S VIDYA ENTERPRISES L4 | ASHOKKUMAR SURI L5 | M/S KABIR CHOUDHARY L7 | NATIONAL TRADING COMPANY L3 | Maqsood Ahmed L2 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed by Engineer-in-Charge. | 90 | Cum | 100 ₹9,000 Lowest | 200 ₹18,000 | 150 ₹13,500 | 180 ₹16,200 | 200 ₹18,000 | 130 ₹11,700 | 250 ₹22,500 |
| 2.00 | Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in hard/dense soil complete all as specified and directed by Engineer-in-Charge. | 10 | Cum | 250 ₹2,500 | 200 ₹2,000 | 250 ₹2,500 | 180 ₹1,800 | 150 ₹1,500 Lowest | 150 ₹1,500 Lowest | 300 ₹3,000 |
| 3.00 | Returning, filling in, including spreading, leveling, watering and well ramming in layer not exceeding 25 cms thick after laying and testing of cable complete all as specified and directed. | 89 | Cum | 50 ₹4,450 | 50 ₹4,450 | 20 ₹1,780 Lowest | 45 ₹4,005 | 100 ₹8,900 | 40 ₹3,560 | 150 ₹13,350 |
| 4.00 | Removing excavated soil to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above starting point complete all as specified and directed by Engineer-in-Charge. | 11 | Cum | 100 ₹1,100 | 50 ₹550 | 50 ₹550 | 45 ₹495 Lowest | 150 ₹1,650 | 50 ₹550 | 110 ₹1,210 |
| 5.00 | Supply , laying,15 mm bore steel water tubing medium grade galvanised with all fittings including short lengths, laid in trenches, complete with all fittings (such as bends, elbows, Tee, short pieces, connectors, back nuts, diminishing pieces, caps and plugs, unions etc.) including taking down old unserviceable pipe any type complete all as specified and as directed by Engr-in-Charge. | 200 | RM | 100 ₹20,000 Lowest | 180 ₹36,000 | 150 ₹30,000 | 170 ₹34,000 | 480 ₹96,000 | 160 ₹32,000 | 150 ₹30,000 |
| 6.00 | All as per item No 05 here-in-before but with size of 20 mm bore complete. | 160 | RM | 50 ₹8,000 Lowest | 160 ₹25,600 | 200 ₹32,000 | 150 ₹24,000 | 600 ₹96,000 | 220 ₹35,200 | 150 ₹24,000 |
| 7.00 | All as per item No 05 here-in-before but with size of 25 mm bore complete. | 200 | RM | 50 ₹10,000 Lowest | 220 ₹44,000 | 210 ₹42,000 | 200 ₹40,000 | 580 ₹1,16,000 | 260 ₹52,000 | 220 ₹44,000 |
| 8.00 | All as per item No 05 here-in-before but with size of 40 mm bore complete. | 400 | RM | 100 ₹40,000 Lowest | 310 ₹1,24,000 | 250 ₹1,00,000 | 300 ₹1,20,000 | 800 ₹3,20,000 | 290 ₹1,16,000 | 250 ₹1,00,000 |
| 9.00 | All as per item No 05 here-in-before but with size of 50 mm bore complete. | 300 | RM | 190 ₹57,000 Lowest | 420 ₹1,26,000 | 300 ₹90,000 | 400 ₹1,20,000 | 800 ₹2,40,000 | 350 ₹1,05,000 | 380 ₹1,14,000 |
| 10.00 | Supply, laying and Fixing HDPE pipe PN10 dia 75mm using water supply including provisioning of suitable fittting and bolts, nuts and double washers etc for holding of pipe including taking out old broken pipes, complete all as specified and as directed by Engr-in-Charge.
Note for 5.00 to 10.00: Excavation and earth work shall be measured and paid seperately under relevant items | 200 | RM | 200 ₹40,000 | 320 ₹64,000 | 500 ₹1,00,000 | 300 ₹60,000 | 200 ₹40,000 | 260 ₹52,000 | 120 ₹24,000 Lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
9 Aug 2025, 6:00 pmClosed
GE AF Jammu
GE AF JAMMU
MAINTENANCE OF WATER SUPPLY AT OP LOCATION SHASHITAR UNDER GE AF JAMMU
2025_MES_719864_1
CA NO GE/AFJ-29/2025-26
Open Tender
Civil Works
Item Rate
180 days
RAJOURI
PLS REFER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE AF JAMMU
₹60,000
Yes
3 Oct 2025
11 Jul 2025
16 Aug 2025
11 Jul 2025
9 Aug 2025
26 Jul 2025
Amount
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in hard/dense soil complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling, watering and well ramming in layer not exceeding 25 cms thick after laying and testing of cable complete all as specified and directed.
Removing excavated soil to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above starting point complete all as specified and directed by Engineer-in-Charge.
Supply , laying,15 mm bore steel water tubing medium grade galvanised with all fittings including short lengths, laid in trenches, complete with all fittings (such as bends, elbows, Tee, short pieces, connectors, back nuts, diminishing pieces, caps and plugs, unions etc.) including taking down old unserviceable pipe any type complete all as specified and as directed by Engr-in-Charge.
All as per item No 05 here-in-before but with size of 20 mm bore complete.
All as per item No 05 here-in-before but with size of 25 mm bore complete.
All as per item No 05 here-in-before but with size of 40 mm bore complete.
All as per item No 05 here-in-before but with size of 50 mm bore complete.
Supply, laying and Fixing HDPE pipe PN10 dia 75mm using water supply including provisioning of suitable fittting and bolts, nuts and double washers etc for holding of pipe including taking out old broken pipes, complete all as specified and as directed by Engr-in-Charge. Note for 5.00 to 10.00: Excavation and earth work shall be measured and paid seperately under relevant items
Supply, laying and Fixing HDPE pipe PN10 dia 32mm using water supply including provisioning of suitable fittting and bolts, nuts and double washers etc for holding of pipe including taking out old broken pipes, complete all as specified and as directed by Engr-in-Charge.
S&F Hot water pipe duly insulated with glass wool and aluminium cladding up to 25 mm bore including joints, bend, tee,complete all as specified and as directed.
M & L for Insulation of GI Pipe with PUF slab 30 mm thick with and including applying bituminuous compound and aluminium cladding with 26 gauge sheet of 50 mm bore including joints, bend, tee,complete all as specified and as directed.
Attending day to day emergency breakdowns / complaints of damaged water supply lines of 15 to 25mm bore in distribution system and restoration of water supply by stopping the leakage occured by deputing skilled /semi skilled man power for smooth functioning of water supply, complete all as specified and directed by Engineer-in-Charge.
Attending day to day emergency breakdowns / complaints of damaged water supply lines of 40mm to 50mm bore in distribution system and restoration of water supply by stopping the leakage occured by deputing skilled /semi skilled man power for smooth functioning of water supply, complete all as specified and directed by Engineer-in-Charge.
Note for srl item No- 14 to 15 (a) The complaint / breakdown shall be rectified by the contractor within 24 Hours. Any delay thereafter, recovery at double the rate quoted per job shall be deducted from the dues of contractor by the Enginer-in-charge without any notice. (b) A proper record of complaint slip shall be maintained by the Engineer-in-Charge for making the payment against these items and recovery if any in case of failure of attending and rectifying the complaint within 24 hours. (c) Two pipe fitter and two helper with required T&P shall always be made available for attending complaints. (d) All material such as bends,unions,nipple,tees,sockets and all other items rate includes each job.MES not given any material and not paid seperately
Supply and laying of 40 mm CPVC pipe SDR 11 & plain CPVC SDR 11 fitting including making connection with existing line including all accessories and fixing on wall and ground/ceiling or laying in floor complete including taking out old rusted/broken GI pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and laying of 25 mm CPVC pipe SDR 11 & plain CPVC SDR 11 fitting including making connection with existing line including all accessories and fixing on wall and ground/ceiling or laying in floor complete including taking out old rusted/broken GI pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and laying of 15 mm CPVC pipe SDR 11 & plain CPVC SDR 11 fitting including making connection with existing line including all accessories and fixing on wall and ground/ceiling or laying in floor complete including taking out old rusted/broken GI pipes, complete all as specified and as directed by Engr-in-Charge.
Cleaning the semi underground reservoir cap 20000 gallons by draining the complete water and brushing the surface with iron brush and removing the complete mud/ silt and and washing the complete inner surface of the tank to the entire satisfaction of Engineer in Charge and writing the date of cleaning on surface of tank with white synthetic enamelled paint on black background including covered the opening hole of tank with chicken wire mesh with wooden frame, hinges and locking arrangement complete all as directed by Engr-in-Charge.(Salyarchatta-02) Note: T&P, material, labour involved in cleaning shall be arranged by the contractor without any extra cost to the department.
M& L for removing bore well HDPE pipe upto 50 mm dia with submersible flat cable of any type and dismantling and taking up/down SUBMERSIBLE PUMP & Motor ASSEMBLY of capacity 2HP to 5HP , shifting to workshop and removing unserviceable spares, replacing with new spares such impeller, bushes distance bush, seal etc of same specifications / type / model. removing burnt copper winding from motor and rewinding with same guage and type of insulation copper conductor winding wires and insulation sheets , applying insulating varnish over the complete winding , drying up by heating , assembling back and testing for proper function including necessary machining works as required , bringing back and reinstalling into the bore well complete all as specified and directed. Note: HDPE Pipes will be measured and paid for separately under relevant Item.
Supply, laying and testing PVC insulated and sheathed flat 10 Sqmm 3 core copper stranded conductor water proof submersible cable fixed to submersible monoblock pump set to starter as directed including taking out old unserviceable cable of following sizes:
Servicing / maintenance including repairs including spares as required for following components of complete Altoc Dosing system installed at a pump house 02(Nos) including following operations: (a) Dismantling of Altoc Dosing System complete part by part in MES yard/ workshop, cleaning of all the stationary and rotary parts,repairing to gear box and display the parts at site for inspection of Engr-in-Charge to ascertain the serviceability / unserviceability of plant and to ascertain the quantam of defects and repairs involved. (b) Transporting the defective parts to authorised dealer for repairs as decided by the Engnr-in-Charge and carrying out the needful repairs including replacement of defective unserviceable parts. (c) Assembling the Altoc Dosing System after repair/service and carrying out necessary test in presence of Engnr-in-Charge to establish functionability of the repaired plant upto the entire satisfaction of Engnr-in-Charge. Note : (i) Maintenance / servicing of each Altoc Dosing System shall be measured and paid maximum twice in every month. However, in case of unserviceability of the same, the contractor shall be required to carry out the job for its maintenance any number of times as required and directed at site as a case of emergency breakdown. (ii) Any parts required to be replaced during repair / servicing of Altoc Dosing System shall be supplied by the firm without any extra cost to the department.
Material and labour for disconnecting and removing the Squirrel cage 3 phase 415 Volts, 50 Hz Induction motor of following capacity from its foundations/ base frame bydisconnecting electrical connections and motor couplers,taking it to workshop for repair and dismantling and opening up of MOTOR , removing burnt out winding wires complete,cleaning startor and rotor assembly, rewinding the startorwith same guage and type with insulation copper conductorwinding wires and insulation sheets , applying insulatingvarnish over the complete winding , drying up by heating ,assembling back the stator and rotor including replacementof terminal blocks and terminal bolts, nuts and washers,refixing back to its postion after getting repaired and makingall connections, carry out alignment, testing for satisfactoryfunction all as specified and as directed complete all asspecified and as directed. Note: (i) Bearings shall be measured and paid separately.
20 to 30Hp Capacity
1 Hp to 3.0Hp Capacity
Supply only anti friction heavy duty bearings suitable for 20 to 30HP motor Make: SKF/ZKL
Supply only anti friction heavy duty bearings suitable for 1 to 3HP motor Make: SKF/ZKL
Gun-metal, globe or gate valves/stop cock, ISI marked, with iron wheel head, screwed both ends for iron pipe of size 20 mm, fixed in repairs, complete all as specified and as directed by Engr-in-Charge
Gun-metal, globe or gate valves/stop cock, ISI marked, with iron wheel head, screwed both ends for iron pipe of size 25mm, fixed in repairs, complete all as specified and as directed by Engr-in-Charge
Gun-metal, globe or gate valves, ISI marked, with iron wheel head, screwed both ends for iron pipe of size 40mm, fixed in repairs, complete all as specified and as directed by Engr-in-Charge
Gun-metal, globe or gate valves, ISI marked, with iron wheel head, screwed both ends for iron pipe of size 50mm, fixed in repairs, complete all as specified and as directed by Engr-in-Charge
Bib taps , fancy type cast copper alloy, chromium plated, with crutch or butterfly handle screwed down for iron pipe or for brass ferrule for bore of pipe 15 mm, fixed in repairs, complete all as specified and as directed by Engr-in-Charge
S&F Iron foot valves size of 50 mm complete all as specified and directed by Engineer In Charge location such as under ground sump located Salyarchatta
Taking down old u/s starter and Supply and install star delta starter in sheet steel enclosure with three phase protection feature suitable for operation on AC, Three phase four wire , 415 Volts, 50 Hz supply for Motor of capacity up to 40 HP with relay range 9-15Amps complete and directed by Engr- in Charge
M & L for carry out water quality anyalsis for bacterial , chemical and biological analysis including for collection of water samples from the Pump House or form location as specified by Engineer-in-charge and testing from Govt approved testing laboratory , submitting of report from minium following parameters. (a) Free chlorine (b) pH (c) Total Hardness (d) Total Alkalinity (e) Bacterological standards (f)Chemica standars (g) physical standards (h) copper (i) chloride (of Govt testing lab). Notes: 1. Saperate water samples should be collected & tested for Each location as specified above 2. No payment shall be made to contractor till submission of water test report for the water samples of loactions mentioned above
Supply and transportation of fresh drinking water through water bouzer of capacity 4000 litres from nearest water filling points made by PHE (Public health Engineering or approved by Engineer-in-Charge) to Sahsitar and filling water in storage water tanks at Air Force Station Sahsitar complete all as specified and as directed by Engr-in-Charge. Notes :- (a) Supply, filling, transportation and filling water in tanks at different locations of Sahsitar shall be included in the rate quoted by contractor and contractor will be informed one day before actual shifting of water bouzer for arrangement to vehicle etc time to time as per requirement. (b) Contractor shall ensure that the water being supplied is potable for drinking purpose as per WHO norms.
M&L for cleaning of valve pit chamber removing sludge deposited inside chabers,removing sliuce valve changing packing rope and also spindle,clearing of all leakages from chamber complete all as specified and directed by Engineer In Charge
Supply only Altoc GP Calcium Based granular Disinfectant (Aqua Fit) for Water Treatment Packing 45Kgs Plastic drum.
Supply and lay M S Pipes heavy grade with all fittings laid in floors or fixed to walls and ceilings etc of size 50mm dia with all fittings complete including taking down old unserviceable pipe complete all as specified and as directed by Engr-in-Charge.
M & L for sub main wiring with two single core FRLS, PVC insulated, stranded, unsheathed cable copper conductor with size 06 Sqmm and drawing through & including Non metallic PVC conduit in wall including earth continuity conductor of size 06 Sqmm PVC insulated unsheathed stranded copper conductor cable and connected to earth dolly to be drawn in PVC conduit including connecting from main board/starter to Motor complete all as specified and directed by Engineer-in-Charge.
Supply & fixing PVC insulated sheathed service wire twin core 10 Sqmm aluminium solid conductor 1100 volts grade incl taking down old unserviceable one.
Supply and fixing change over switchs off-load 200 amps 4 pole sheet metal encloser including taking dwon old UNSV one complete all as specified and directed.
Supply and fixing in repairs change over switchs off-load 400 amps 4 pole sheet metal enclosure including taking down old UNSV one complete all as specified and directed.
Supply and fixing MCB TPN 40 Amp to 100 amps four pole C curve 25 KA including taking dwon old UNSV one complete all as specified and directed.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying of DWC (Double Wall Corrugated) HDPE Pipe, ISI Marked IS 16205 Part-II, of outer dia of 53 mm and inner dia 40 mm with smooth internal and profiled external surface for non pressure under ground cable including all connected accessories like coupler, 'O' Ring etc, for protection of cable complete all as specified and as directed.
Material and labour for making 100% serviceable to the AMF/LT PANEL suitable for Motors and DG set by tracing out defects and replacing unserviceable parts including control wiring complete all as specified and directed. minor parts such as nuts, bolts, washers, thimbles, control wiring, MNX any size contactor, relay etc shall be deemed to be included in the quoted rate. including taking out the worn out material i.e, contactor, MCCBs, MCB if any Size (Note :- The work to be carried through the company rep only)
M&L Plain cement concrete 1:4:8 type D2 using 40mm graded stone aggregate for foundation of poles complete all as specified and as directed.
M & L PCC 1:3:6 type C1 using 20 mm graded stone aggregate for coping of poles/road/plinth blocks of LT poles etc incl fair finishing the exposed surfaces even and smooth without using extra cement including necessary form work complete all as specified & directed.
Construction of brick masonry platform in cement mortar 1:4 of size 2500 x 2000 x500 mm for RO having sides finished with brick work with plaster complete with PCC foundation of 1:5:10 & PCC platform at top with 30 cm thick of PCC 1:5:10 and 10 cm thick of PCC 1:2:4 complete all as directed by Engr - in - charge.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 25 x 4 mm galvanised earth strip by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm(.d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. ( f) Requisite quantity of common salt and charcoal.(g) Testing of earthing. Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Earthing of machinery/equipment Installed at power house/substation complete with copper earth plate electrode 60×60cm.× 3.15mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead 20x3 mm Copper strip by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion.
SCHEDULE 'A' PART-II (Schedule of credit) Credit amount of Rs (Refer schedule of credit) for retrieved material mentioned in Sch 'A' Part-II of Tender documents in PDF form will be deducted offline during acceptance of tender of lowest bidder.
Maqsood Ahmed (BID ID -3373199)
NATIONAL TRADING COMPANY (BID ID -3388221)
M/S VIDYA ENTERPRISES (BID ID -3386709)
ASHOKKUMAR SURI (BID ID -3387579)
G M ENGINEERING SERVICES (BID ID -3387670)
M/S KABIR CHOUDHARY (BID ID -3388286)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .