Tender Value
₹11.8 L
EMD Value
₹23,600
Closing Date
30 Oct 2024, 5:00 pmClosed
Col A K Tripathi CWE
HQ CWE ARMY BANGALORE 101 Dickenson Road Bangalore 560042
REPAIR MAINT OF HT SWITCH GEARS , TRANSFORMERS AND HT NETWORK UNDER GE (SOUTH) BANGALORE
2024_MES_676972_1
86311/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
HQ CWE ARMY BANGALORE
AS PER TENDER
8 documents required · 8 mandatory
₹500
Yes
GE (SOUTH) BANGALORE
₹23,600
Yes
7 Dec 2024
27 Sept 2024
6 Nov 2024
27 Sept 2024
30 Oct 2024
11 Oct 2024
27 Sept 2024 - 4 Oct 2024
Amount
Filtration & Dehydration of transformers oil for transformers, HT/LT OCB, HT VL switches etc through on line filtration equipment to withstand minmum dielectirc strength 40 KV for 1min at 2.5 mm gap and flash at 60 KV without disturbing/switching off system all as specified and as directed.
Supply and topping up of transformer oil suitable for 11 KV system for transformer/OCBs having 45KV of minimum dielectric strength all as specified and as directed
Taking down carefully by Disconnecting all the electrical connections from H.T.and L.T. side, and earthing of unserviceable transformer, from Plateform / 2/4 pole structure, draining out the transformer oil in clean barrels, loading and unloading of transformer & transportation by vehicle from substation to the repairing workshop for rewinding, reconditioning or any other repairs required, reassembling making the internal H.T. & L.T. connections by fixing the studs, bushings, fitting the top cover by replacing cork sheet including gasket along with conservator including hoisting placing in position and securing properly on 4pole/ 2 pole structure, platform at site, including pouring in the transformer oil in the transformer reinstallation, commissioning and testing complete all as specified and directed by Engineer-in-Charge for following capacities of transformers. Note: (i) U/S items required for repairs shall be measured and paid under relevant item of this schedule. Transformer oil with die electric strenght not less than 40KV either new or filtered shall be filled and shall be measured and paid separately under respective item.
Transformer capacity upto 125 KVA
Transformer capacity above 125 KVA upto 250 KVA
Transformer capacity above 250 KVA upto 500 KVA
M&L for opening of top cover of transformer 11/0.433 KV including draining out required transformer oil keeping in safe custody in a dry and clean container, taking out top cover disconnecting HT/LT connnections internally and externally for replacement of unserviceable items(to be paid seperately) reconnecting after replacement of defective parts, re assembling and refitting of top cover and refilling of transformer oil including heating and testing complete for the following capacities of transformer complete all as directed by Engr-In-Charge.
Transformer capacity upto 125 KVA
Transformer capacity above 125 KVA upto 250 KVA
Transformer capacity above 250 KVA upto 500 KVA
M&L for re winding of HT coils of different type/capacity and make of transformer with superior quality super enamelled copper winding wire/strip of approved make of suitable gauge and number of turns alongwith allied materials such as cork sheet, fibre glass insulation/paper isulation cotton, empire tape and woodeen blocks, bolts, nuts and washers, soldering and other packing materials etc all as directed.
All as per ser Item 5 here in before but for copper winding strip of any size for L.T. coils of transformers.
M&L for heat treatment at the workshop furnance of complete core before and after re-assembly of coil into limps after rewinding for transformer capacity upto 500 KVA complete all as directed by Engr-In-Charge.
Supply & fix LT bushings 433V of suitable size for outdoor/ indoor type transformer of the following capacity as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 500KVA
Supply of fix HT bushings 11KV of suitable size for outdoor/indoor type transformer of following capacities as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 500KVA
Supply & fix brass stud (for LT433V side)of suitable size complete with one chuck nut, two nuts, washers and rubber seal, all as per sample for outdoor/ indoor type transformer of the following capacity as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 500KVA
Supply, installation connecting electrically & commissioning switch air break, gang operated, tripple pole mounted on insulators 12 Nos and steel frame with operating mechanism in worked from ground level, drop out fuse, for current rating upto 200 amps and working voltage 11000 volts vertical/horizontal type all as required at site or directed by Engr-in-charge. Make: Jaipuria/BHEL
M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as directed .
Taking out HT cables safely from trenches of size 95 sqmm to 150 sqmm and depositing to MES store yard for reuse after removing faults complete all as specified and directed by Engr in Charge.
Laying or passing through pipe only HT cables of size 95 sqmm to 150 sqmm in trenches after removing faults and jointing properly ( Joint will be measured and paid separatlely under respective items of Sch ' A' ) Complete all as directed by Engineer-in-Charge (Serviceable old cable retrieved under ser item No. 13 here i before will be used )
Excavation in trenches in any type of soil n exc 1.5 m in width and n. exc 1.5 m in depth and getting out all as required for laying of cables complete all as specified and directed..
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm complete all as specified and directed..
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretching and testing the cable complete all as specified and directed.
Unreinforced precast concrete cable cover class HV, Type I, flat size 300mm x 180mm x40mm , laid flat across the cable length all as per specification and directed
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty ) with aluminium conductor, 11/6.35KV grade, suitable for earthed system, with aluminium conductor, 3 core 95 Sqmm. Make: Havells/Paragon/Polycab/Gloster
Taking out U/S Vacuum Circuit Breaker 630A rating having working voltage 11000V from HT panel for repairs and strip opening complete all as required. Seggregating serviceable and un serviceable parts.Cleaning to remove complete carbon contents from the dismentled parts. Reassembling after replacement of u/s parts and adjustment for smooth functioning of the circuit breaker. Testing complete after installation of vacuum cicuit breaker in HT panel to the satisfaction of Engr in Charge.( Unserviceable parts required to make VCB serviceable will be measured separately under respective items detailed here in after.)
Supply and fix vacuum intereputer 630A 11KV rating suitable for VCB as per Sample per phase per intereputer all as required and directed .
Supply and fix porcelain bush for connection stud complete with insulating rubber sleeve as per sample for VCB of 630A 11KV rating and directed .
Supply and fix rose contact assembly as per sample for VCB of 630A 11KV rating and directed .
Supply and fix fixed contact assembly as per sample for HT panel of 630A 11KV rating and directed .
Supply and fix indicating lamp LED type suitable for any working voltage as per site requirement, red, yellow, white or green all as required or directed by engr in charge.
Supply and fix in replacement motor & gear assembly for spring charging suitable for VCB 11000 Volts matching with existing complete all as specified and directed.
Supply and fix in replacement power pack with battery back up suitable for VCB 11000 Volts matching with existing complete all as specified and directed.
Supply and fix in replacement closing coil assembly suitable for VCB 11000 Volts matching with existing complete all as specified and directed.
Supply and fix in replacement tripping coil assembly suitable for VCB 11000 Volts matching with existing complete all as specified and directed.
M&L for indoor type 11KV/110V potential transformer for VCB, 50Hz solidly grounded, accuracy class 0.5 for metering, 3 P for protection, rated burden both winding 100VA each, heremetically sealed, to eliminate breathing and prevent air & moisture, secondary terminal but should be partitioned so as to house the metering terminals separately from protection & various terminal connectors providing sufficient earth clearance complete all as specified and directed.
S & F Breather assembly for the transformer as per exisiting sizes all as specified and as directed including filling of Silica gel required for breather
S & F Silica gel complete all as specified and directed by Engr in Charge .
Supply & fix in replacement of lightening arresters metal oxid type complete with all fittings transmission class discharge capacity 65 Kilo Amps suitable for 11000 volts grade complete all specified and as directed.
Supply & fix in replacement of explusion fuse unit 11 KV drop out up to 25 Amps complete all specified and as directed.
S&F cable jointing kit for 11 KV (earthed) grade cable for indoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm. Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable for indoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm. Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable for outdoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm.Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm..Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable straight through joint cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm. Note:- Excavation, earth work, sand , Pcc cover, will be measured and paid seperately under respective items. Make: Birla 3M / Raychem / Denson
S&F cable jointing kit for 11 KV (earthed) grade cable straight through joint Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm. Note:- Excavation, earth work, sand , Pcc cover, will be measured and paid seperately under respective items. Make: Birla 3M / Raychem / Denson
M&L for finding out cable fault of HT cables of any sizes using the cable fault indicator all as specified and as directed . Note: Hiring / Providing of the HT cable fault indicator is deemed to be included in the quoted rate .
Remove coarse stone aggregate and supply and sprayed at site for loose filling of size 40mm grade inside the area of sub stations at various locations complete all as specified and directed. Note:- Removed stone aggregate shall be reused .
M & L for Repair/Maintenance , cleaning, dusting and servicing Vacuum Circuit Breaker, HT 11 KV,50 Hz , 630 Amp indoor switch gear panel by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, busbar/cable chambers, motorised spring charging mechanism , DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , heater coil, aux supply SMPS , replacing of worn out parts and fuses , applying petroleum jelly to moving and fixed mechanical parts for its smooth functioning all as specified and directed by the Engineer in charge. Location : Main Power House 515 and FMCC -07 Nos
M & L for Repair/Maintenance ,cleaning, dusting and servicing, for the smooth functioning of 3 way compact RMU, HT 11 KV , 630 Amp, 3 phase 50 cycle by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers , self powered over current and earth falult relay, T-off SF6 circuit breaker module , mechanical fault/on/off indicator etc including refilling of SF6 gas and replacing worn out parts when required etc and confirming smooth reliable operation of RMU unit all as specified and directed. Location : Marshal Barrack -01 Nos
M & L for Repair/Maintenance , Cleaning, dusting and servicing Oil circuit Breakers HT 11 KV, 50 Hz, 400 Amps capacity by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers, DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , aux supply SMPS , replacing of worn out parts and fuses carefully for its smooth functioning complete all as directed by the Engineer in charge. Location : Pump House 515ABW
Fixing in replacement of chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provission of binding wire complete all as directed.
Supply and fixing in replacement of Chain link MS galvanisd fencing, 4 mm dia and 50 x 50 mm size complete all as directed.
Excavating in post holes (or similar holes) each n.exc 0.5 Cu.m, in hard / dence soil getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, complete all as diretced.
Material & Labour for PCC 1:2:4 type B2 (using 40mm graded stone aggregate) as in foundation, mass concrete for road crossing etc., complete all as specified and directed.
Mild steel frame work conforming to Fe-410-0 or Fe 310-0 such as doors or gates of angle iron or other section including braces rails etc. complete drilled for fixing of steel sheeting or other covering doors etc. prepared for hanging or sliding with including either hooks and hinges or steel hanging door devices complete all as specified and as directed including painting with two coat of synthetic enameled paint over a coat of red oxide primer complete all as directed.
M/S - KRUPA ELECTRICALS (BID ID -3138061)
Chandana Enterprises (BID ID -3153023)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .