Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹31.7 CrAccepted-AOC | ₹31.7 Cr Quoted ₹32.1 Cr | L-1 | Accepted-AOC Awarded to Lowest bidder L-1 |
| 2 | L-2₹34.3 CrRejected-Finance | ₹34.3 Cr | L-2 | Rejected-Finance Higher Amount |
| 3 | L-3₹36.0 CrRejected-Finance VILL FAZALPUR BEHIND FOCAL POINT NEAR RANDHAWA MASADAN JALANDHAR | JALANDHAR | JALANDHAR | PUNJAB | ₹36.0 Cr | L-3 | Rejected-Finance Higher Amount |
| 4 | Not Admitted-PreQual/Technical HOUSE NO 5 ADRASH COLONY BALAJI VIHAR KANGRA HP | - | - | Not Admitted-PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹23.8 L
Closing Date
8 Feb 2023, 11:00 amClosed
Executive Engineer
Executive Engineer JSV Division Nalagarh District Solan (HP)
Sub Head Providing Laying jointing and commissioning of MSERW pipe 80 and 65 mm dia of class L 210 and L 245 Providing laying GMS pipe Medium and High 125mm 80 mm 65 mm 50mm and 40 mm dia in Rising main construction of 27 No Pump house construction
2023_HPIPH_67366_1
15426-86 dated 20-01-2023
Open Tender
Civil Works
548 days
Nalagarh
Please refer Tender documents.
10 documents required · 10 mandatory
₹2,500
Executive Engineer JSV Division Nalagarh
₹23.8 L
Enginer-in-Chief JSV Tutikandi Shimla HP
31 May 2023
20 Jan 2023
8 Feb 2023
20 Jan 2023
8 Feb 2023
3 Feb 2023
3 Feb 2023
Amount
SCHEDULE B1 CIVIL WORKS : CONSTRUCTION OF PUMP HOUSES
Construction of pump house with chowkidar room including internal electrical wiring, water supply and sanitary, other allied items, cost of septic tank and as per drawing to the entire satisfaction of Engineer-in-Charge (.Refer to Data Sheet No. - 1 )
Construction of pump house with chowkidar room including internal electrical wiring, water supply and sanitary, other allied items, cost of septic tank and as per drawing to the entire satisfaction of Engineer-in-Charge (.Refer to Data Sheet No. - 1 )
CONSTRUCTION OF STORAGE TANKS:- Constructing RCC Circular under ground/partial under ground/ elevated storage reservoirs as per capacity given below at various stages/sites including excavation in all kinds and types of strata, soil strata including dewatering in M30 design mix in foundation, walls, bottom slab of roof slab, roof slab/dome with smooth finishing in 1:3 inside the tank, refilling and disposing of surplus stuff with in all leads and lifts, labour and material charges. The job also includes providing lowering, laying, erecting, hoisting and jointing of pipe assembly for inlet, outlet, overflow and scour pipe with bye pass arrangement consisting of GI / MSERW pipes special and valves / acuated valves of required classes and dia and all other accessories required such as MS ladders inside and outside CI cowl type ventilator, CI manhole covers including frames and covers (medium duty) with proper locking arrangement water level, indicator, RCC frames for all valves ventilating shafts shall also be provided including all leads and lifts as per entire satisfaction of Engineer-in-Charge. The tanks shall be hydraulically tested for water tightness all works shall be conforming to relevant IS code. The cost of valves shall be included in the rates of tanks. The cost of the actuators and chamber for valves shall be measured and paid for separately.The work shall include supplying of 5 sets of structural design and drawings and wetted/ approved from the competent authority/ IIT/NIT/PEC.
C/o Sump well 1.5 Mtr staging at LWSS Saner Bhatian Node-1 (Refer Data Sheet No.2 )
C/o Sump well 1.5 Mtr staging at LWSS Panjehra-I Node-2 (Refer Data Sheet No.2 )
C/o Sump well 1.5 Mtr staging at LWSS Joghon III Node-1 (Refer Data Sheet No.2 )
C/o Sump well 1.5 Mtr staging at LWSS Chamba Jukhari-III Node-183 (Refer Data Sheet No.2 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-2 LWSS Saner Bhatian (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-18 LWSS Saner Bhatian(Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-4 LWSS Dhabota (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-4 LWSS Lakhanpur Jhira (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-2 LWSS Bir Plassi (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-2 LWSS Rampur Poswalan (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-2 LWSS Butta Plassi (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-36 LWSS Panjehra-I (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-2 LWSS Souri Gujran (Refer Data Sheet No.3 )
C/O RCC Under Ground Main storage tank at Node-17 LWSS Chanobri Lehri (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-7 LWSS Kotla Phalahi-I (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-5 LWSS Kotla Phalahi-II (Refer Data Sheet No.3 )
C/O RCC Under Ground Main storage tank at Node-29 LWSS Chaoli Brahmana (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-4 LWSS Joghon-II (Refer Data Sheet No.3 )
C/O RCC Under Ground Main storage tank at Node-78 LWSS LWSS Joghon-III (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-4 LWSS Baroona Kashmirpur (Refer Data Sheet No.3 )
C/O RCC Elevated Main storage tank 20 mtr staging at Node-8 LWSS Mastanpur (Refer Data Sheet No.3 )
C/O RCC Under Ground Main storage tank at Node-24 LWSS Chamba Jukhari (Refer Data Sheet No.3 )
C/O RCC Under Ground Main storage tank at Node-18 LWSS Chamba Jukhari-II (Refer Data Sheet No.3 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node-5 LWSS Dabhota (Refer Data Sheet No.4 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node-17 LWSS Lakhanpur Jhiran (Refer Data Sheet No.4 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node-4 LWSS Rajpura (Refer Data Sheet No.4 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node- 49 LWSS Rajpura (Refer Data Sheet No.4 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node- 20 LWSS Bir Plassi (Refer Data Sheet No.4 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node- 2 LWSS Manjholi (Refer Data Sheet No.4 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node- 6 LWSS Rampur Chak Baircha (Refer Data Sheet No.4 )
C/O RCC Elevated sector storage tank 20 mtr staging at Node- 3 LWSS Kanganwal (Refer Data Sheet No.4 )
C/O RCC Under Ground Sector storage tank at Node-8 LWSS Chamba Jukhari (Refer Data Sheet No.4 )
C/O RCC Under Ground Sector storage tank at Node-22 LWSS Chamba Jukhari (Refer Data Sheet No.4 )
CONSTRUCTION OF BOUNDARY WALL AROUND PUMP HOUSE
Excavation in foundation trenches etc. in earth work in all kind of soil such as pick work,jumper work, blasting work in hard & soft rock and chiesaling work including slushy soil & under flooring water up to all excavated soil up to any lead & lifts from the edge of excavation and then depth and stacking the returning the stacked soil in 15 CM ( fifteen centimetres) layer's when required in to plinth sides of foundation etc. Consolidation each diposited layer by ramming & watering & then disposing of all surplus excavated earth as directed with in all lead of 20 meters in Chiselling /wedging out of rock complete in all respect.
Providing and laying cement concrete 1:6:12(Icement:6sand:12 graded stone aggregate 40mm nominal size)and curing complete excluding the cost of form work in foundation and plinth including carriage of material in all leads & lifts.
2nd class brick work using common burnt clay building bricks in foundation and Plinth in cement mortor 1:6 ( 1 cement:6 sand ) in all leads and lifts as per the direction of the Engineer-in-Charge.
15 mm cement plaster in single coat on rough side of brick masonry for interior plastering upto floor two level including arrises, internal rounded angle, chamfers and or rounded angles not exceeding 80 mm in girth and finished even and smooth with cement mortor 1:6 ( 1 cement : 6 sand ) in all leads and lifts as per the direction of the Enginner-in-Charge.
Steel work in single section including cutting, hoisting and fixing in position and applying a priming coat red lead paint in RS joist chanel , angle tees etc complete in all respect and as per direction of Engineer-in-Charge.
Finishing wall with weather proof exterior grade emulsion of approved design (Apexultima) or its equarlied on undecorated wall surfaces (two coats) to give an even shade and final finish after throughly cleaning the surface to remove all dirt, dust and other foreign matter etc including sand paper smooth complete
SCHEDULE B2 PUMPING MACHINERY (submersible)
Supply,errection,testing &commissioning of star rated enrgy efficient Submersible pumping set of KSB/Calama/ WPIL/ Crompton/BS/ SABAR / Oswal/ Kirloskar or any other approved make conforming to latest relevant BIS Code 8034:1976. The pump should be fitted with bronze impeller or suitable alloys suitable for handling Clear water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to a submersible squirrel cage electric induction motor (water proof type) of required HP & 2900/1450 rpm of reputed make conforming to BIS 9283-1979 latest with upto date amendments, totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guards, erection clamps , cable clips, depth gauge NRV & Sluice valves of approved class etc. The work should be completed to the entire satisfaction of the Engineer-in – Charge. The HP are indicative, the design /drawings of Pumping Machinery is to be got approved by L-1 Contractor from the competent authority before placing supply order for the same after finalisation of tender.The rates shall be for complete Job to run the machinery in proper working. The pumping machinery & its accessories/ valves /piping work etc. should meet with the following requirements. (i) Sluice Valves/Reflux Valves to be provided on delivey line:- These shall be double flanged valves of approved make & size of valves shall be one size higher than delivery size of offered pump.The class of valves shall be cast stell ASA-600 & for 2nd stage these shall be of cast iron PN-1.6 or cast steel ASA-600 (iii) Piping work (Column Pipe & Delivery pipesto connect Column pipe with Rising main):- The column shall be capable to with stand total dynamic preesurte + surge pressuire Or 1.5 times the total dynamic pressure whichever is more & it shall have minimum wall thickness of 4.80 mm jointed with flanged joints at every three meters. It shall also include the cost of providing, laying, jointing of column pipe with rising main, testing & commissiuoning including all types of bends & other accessories etc. (iii) Power shunt Capactor:- Capacotors shall be of suitable KVAR so as to improve power factor to 0.95 or above. (iv) Pannel Board:- It shall be of suitable size & capable to accomodate all above electrical accessories i/c providing & fixing in position these accessories & interconnections with cable of appropriate size & specifications. (v) Startes:- Starters shall be of approved make & of suitable rating suitable of safe running and operation of given motor or pumping machinery It shall be mounted on panel board with magnetic type over load release & dashpot, time lag,under voltage release with initial oil filling if required.
Booster stage (T/Well to Sump well ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 8.22 LPS with Total Head of = 59.20 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. (Saned Bhatian) (.Refer to Data Sheet No. - 6(7) )
Booster stage (T/Well to MST) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 7.77 LPS with Total Head of = 109.98 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Dabhota (.Refer to Data Sheet No. - 6 (5))
Booster stage (T/Well to MST ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.13 LPS with Total Head of = 210.79 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set Lakhanpur Jhiran (.Refer to Data Sheet No. -6(6) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 1.94 LPS with Total Head of = 126.08 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Rajpura (.Refer to Data Sheet No. - 6(6) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.69 LPS with Total Head of = 109.12 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Bir Plassi (Refer to Data Sheet No. -6 (6) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 3.57 LPS with Total Head of = 111.40 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Dhana (Refer to Data Sheet No. -6 (6) )
Booster stage (T/Well to MST ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 2.39 LPS with Total Head of = 90.45 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set Rampur Poswalan- I (.Refer to Data Sheet No. -6(7) )
Booster stage (T/Well to MST ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 2.01 LPS with Total Head of = 129.76 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set Rampur Poswalan- II (.Refer to Data Sheet No. - 6 (5))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 2.31 LPS with Total Head of = 172.32 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Goel Jamala- I (.Refer to Data Sheet No. - 6 (2))
Stage-II (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.11 LPS with Total Head of = 199.07 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Goel Jamala- II (.Refer to Data Sheet No. -6 (2) )
Stage-III (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.56 LPS with Total Head of = 213.43 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Goel Jamala- III (.Refer to Data Sheet No. -6(2) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 11.91 LPS with Total Head of = 132.07 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Tikkari Bagheri (Refer to Data Sheet No. - 6(3))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.99 LPS with Total Head of = 159.62 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Rampur Chak Baircha-I (Refer to Data Sheet No. - 6(3))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 5.11 LPS with Total Head of = 157.94 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Rampur Chak Baircha-II (Refer to Data Sheet No. -6 (3) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.32 LPS with Total Head of = 182.10 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Mastanpura (Refer to Data Sheet No. - 6(7))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.53 LPS with Total Head of = 63.56 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Chamba Jukhari -Phase- II (Refer to Data Sheet No. - 6(4) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 3.33 LPS with Total Head of =61.31 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Joghon(Malehni) - III (Refer to Data Sheet No. - 6(4) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.05 LPS with Total Head of = 117.66 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Joghon(Jagatpur) - I Chamba Jukhari T/ Well (Refer to Data Sheet No. - 6 (3))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 1.06 LPS with Total Head of = 233.74 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Joghon(Jagatpur) - II (Refer to Data Sheet No. -6 (4) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 2.65 LPS with Total Head of = 151.62 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Sakedi (Refer to Data Sheet No. -6 (5) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 2.31 LPS with Total Head of = 160.18 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Kotla Phalahi-I (Refer to Data Sheet No. - 6 (1))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 2.25 LPS with Total Head of = 130.02 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Kotla Phalahi-II (Refer to Data Sheet No. - 6 (1) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 1.09 LPS with Total Head of = 143.46 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Chonebri Lehri (Refer to Data Sheet No. -6 (1))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 2.23 LPS with Total Head of = 158.15 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Souri Gujrran (Refer to Data Sheet No. - 6 (1))
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 1.95 LPS with Total Head of = 278.28 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Panjehra-I (Refer to Data Sheet No. -6 (2) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 6.99 LPS with Total Head of = 130.23 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Gullarwala Deoli (Refer to Data Sheet No. - 6(5) )
Booster Stage- (T/Well to OHSR ) :- 2 sets (1 working & 1 standbye) for duty condition discharge of = 6.39 LPS with Total Head of = 155.97 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set. LWSS Baroona Kashmirpur (Refer to Data Sheet No. - 6 (4))
CENTRIFUGAL PUMING MACHINERY (CLEAR WATER TANK)
PUMPING MACHINERY CENTRIFUGAL:- Supply ,Installation ,Testing & Commissioning of star rated energy efficient horizontal spindle, horizontal/ radial split casing/end suctions (back pull out arrangement)single/ double/ multistage centrifugal pump suitable for operation, in parallel of recommended make such as Mather and platt/ KSB/Kirloskar/Jyoti /Beaconweir BS&BE or any other approved make confirming to BIS-1520-1980 with upto date ammendments, read with IS:9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristics with bronze/Bronze with 2.5% Nickel impellers, dia of 405mm priming funnels, casing ring and shaft sleeves of bronze/ steel, shaft of SS:410/AIS 1431 Chrom in plated with cast iron casing coupled directly through a flexible coupling on a Common MS base plate to squirrel cage screen protected drip proof induction motor/TEFC/CACA of standard make such as Kirloskar/BHEL/ Crompton/NGEF/GEC/ Siemens / Jyoti/Area Brown Boven (ABB)/CGL and suitable for operation on 11 KV HT, 50 cycles/second 3 phase AC electric supply. The power of electric motor/motors should be at least (+) 10% in excess of the maximum power required by the pump / pumps in the operation range of (+) 10% and (-) 15% of the duty point head. The motor/ motors should be as per IS: 325-1978 with upto date amendments read with IS:900-1972. The starting current of the motor shall be limited to not more than 4.5 to 5 times of full load current.
It should include cost of bearing nuts, bolts and painting etc and should meet the following requirement including Pump sets (working + standby), All electrical equipments such as Starter, ICTP switches, MCB, Bush bar chamber, MCB, Panel board indicating lamps, Ammeter, Voltmeter, Hour run meter should be of electronic type , incoming and outgoing water proof cable for panel board, Double loop earthing, copper cable pressure gauge, capacitor, common header, sluice valve, NRV including erection and testing complete necessary piping for suction and common header and control valves alongwith electrical works including all taxes, insurance, transportation, freight charges, inspection charges, loading, unloading, conveyance to Departmental stores/ site, stacking, etc. including specials and wastage etc.; complete as per Tender Specifications and instruction of Engineer in charge. The HP are indicative, the design/drawings of Pumping Machinery is to be got approved by L-1 Contractor from the competent authority before placing supply order for the same after finalisation of tender. The rates shall be for complete Job to run the machinery in proper working. The pumping machinery & its accessories/valves/piping work etc. should meet with the following requirements. (i) Sluice Valves/Reflux Valves to be provided on delivey line:- These shall double flanged valves be of approved make & size of valves shall be same as dia of column pipe or one size higher than delivery size of offered pump.The class of valves for stage -1st shall be, cast iron PN-1.6 or cast steel ASA-600 & for 2nd stage these shall be of cast iron PN-1.6 or cast steel ASA-600. (ii) Reflux Valves to be provided in Rising Main:- It shall be double flanged valve of approved make & size of valve shall be same as dia of rising main pipe. The class of valve shall be Cast steel ASA-600 for stage 1st & 2nd respectivey (iii) Piping work (Common Header, Delivery pipes & Suction pipes):- The piping work shall be of same specifications as the R-main in intial RD's. The size of common header shall be same as dia of R-Main. in No case pipe wall thickness shall be less than 4.80 mm. The common header & delivery pipes shall be properly jointed with flanges of appropriate Flange table with butt welds. (iv) Power shunt Capactor:- Capacotors shall be of suitable KVAR so as to improve power factor to 0.95 or above. (v) Pannel Board:- It shall be of suitable size & capable to accomodate all above electrical accessories i/c providing & fixing in position these accessories & interconnections with cable of appropriate size & specifications. (vi) Startes:- Starters shall be of approved make & of suitable rating suitable of safe running and operation of given motor or pumping machinery It shall be mounted on panel board with magnetic type over load release & dashpot, time lag,under voltage release with initial oil filling if required.
Sump well to Phase- I - 2 sets (1 working & 1 standbye) for duty condition discharge of = 3.56 LPS with Total Head of = 67.52 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set.Saned Bhatian Phase- I (.Refer to Data Sheet No. - 7 )
Sump well to Phase- II - 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.68 LPS with Total Head of = 49.87 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set.Saned Bhatian Phase- II (.Refer to Data Sheet No. - 8 )
Sump well to Phase- II - 2 sets (1 working & 1 standbye) for duty condition discharge of = 4.53 LPS with Total Head of = 539.82 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set.Chamba Jukhari Phase- II (.Refer to Data Sheet No. - 7 )
Sump well to Phase- III - 2 sets (1 working & 1 standbye) for duty condition discharge of = 3.33 LPS with Total Head of = 565.48 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set.Joghon ( Malehni) - III (.Refer to Data Sheet No. - 7 )
Sump well to Mst - 2 sets (1 working & 1 standbye) for duty condition discharge of = 1.95 LPS with Total Head of = 278.28 mtr. The BHP is to be offered by the bidder & rate shall be filled in by the contractor per set.Panjhera-I (.Refer to Data Sheet No. - 7 )
SCHEDULE B 3 - RISING MAINS
Excavation in drain and channels etc. earth work for pipes upto all depths in all classification of earthwork such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chiseling soft/hard rock where blasting is probihited in all lifts including forest clearence wherever required, trimming & dressing of sides, levelling of beds to correct grade including shoring/struting, planking , timbering & dewatering wherever required stacking the useable/unuseable material/soil seperately & after laying, jointing & testing of pipes, returning the useable soil in trenches in 15cm layers including consolidating of such deposited layer by ramming & watering & then disposing of all surplus excavated soil/ unuseable material as directed with in all leads & lifts including restoration of un-metalled surfaces to its original condition & including cost of diversion for traffic, right signals, fixing caution boards, crossing over trenches for acess to houses, fencing etc. complete in all respect with in all leads and lifts and as per direction of the Engineer-in-charge at site of work.
Providing, laying, fixing, jointing & testing and commissioning in trenches bavelled ended BIS marked API confirming to relevant code and specification or its equivalent latest upto date ammendments of following dia with steel grade L-210 Gr-A , L-245 Gr-B, having wall thickness and per rmt. weight as mentioned below and capable of withstanding required test pressure as prescribed in BIS /ISO code, in random lengths 5.50 to 6.50 metres . The pipe ends shall be bavelled suitable for butt welding , including the cost of jointing the butt welding confirming to IS - 816 - 1969 or latest as applicable ends with upto date amendments. (leak proof) in three layers at site of work with welding rods of standard make and all allied acessories whatever required for welding at site, tail pieces, tees,bends,and other special manufactured from parent pipes as applicable to the perticular reach and of approved specifications as per site conditions, and cutting of pipes wherever required as per site requirementi.e carries in all leads and lifts and as directed by the Engineer-in-charge. The pipes shall have Zinc coating both inside and outside confirming to IS-4736-1986 or latest ammendments and shall be engraved with as per relevant IS 3183-2007 or its equivalent. The laying shall confirm to BIS - 5822 - 1970 or latest with upto date amendments to the entire satisfaction Engineer in Charge ( earth work and cost of MS flanges after 100 metre length shall be measured and paid for sepratley).
Nominal Dia Thicknes Class
80MM 4.80 mm thick L-245 or Grade B
65 MM 4.80 mm thick L-210 or Grade A
Providing laying and jointing in trenches GMS tube (Medium & Heavy grade) of following dia meters as specified below jointed with butt welded according to relevant BIS code 816-1969 i/c all short pieces bends,tees and other specials etc. made from parent tubes as applicable for the particular reach and of approved specifications as per site conditions i/c flushing cleaning and hydraulic testing complete to the best satisfaction of the Engineer-in-charge. The laying of pipes should be confirm to BIS code 5822-1970 with all leads and lifts complete in al respects.
Nominal Dia Thicknes Class
125 MM 5.40 mm thick Heavy
125 MM 4.80 mm thick Medium
100 MM 5.40 mm thick Heavy
100 MM 4.50 mm thick Medium
80 MM 4.80 mm thick Heavy
80 MM 4.00 mm thick Medium
65 MM 4.50 mm thick Heavy
50 MM 4.50 mm thick Heavy
40 MM 4.00 mm thick Heavy
Providing and fixing M.S flanges of following dia to GMS heavy /medium / API grade tubes confirming to IS 6392- 1971 of following table,dia and welding with GMS pipe including cost of nuts , bolts washers complete as per IS 1963 specifications including packing sheet 3mm thick minimum and painting with anticorresive paints complete in all leads lifts and carriage of materials at site as directed by Enginer-in-charge.
SCHEDULE B4 GRAVITY MAINS and DISTRIBUTION
Excavation in drains and chanels etc. in earth work lift up to 1.5 meter stacking the excavated soil not more than 3 meter clear from the edge of excavation and then returning the stacked soil in 15 cm layer in trenches consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated earth as directed with in a lead of 20 meter in pick jumper work.
Providing,Laying, jointing and testing in trenches to be levelled to grades, GI pipes of following diameter confirming to IS:1239-1990( Part-I) having minimum wall thickness as per IS code and Medium and light class as per site conditions including flushing, cleaning & hydraulic testing as per directions of Engineer-in-charge.
25 mm Dia ( M)
32 mm Dia ( M)
40 mm Dia ( M)
50 mm Dia ( M)
65 mm Dia ( M)
80 mm Dia ( M)
100 mm Dia ( M)
25 mm Dia ( L)
32 mm Dia ( L)
40 mm Dia ( L)
50 mm Dia ( L)
65 mm Dia ( L)
80 mm Dia ( L)
Unipro Techno Infrastructure Pvt Ltd
R.G. INDUSTRIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid