TECHNICAL
15 conditions · 4 needing a document upload
Clause Regarding GST: (a) All the Bidders/tenderers should ensure that they are GST Compliant and their quoted tax Structure are as per GST LAW.(b) Tenderer Should Furnish their GSTIN numbers representing the States in Which they are registered GST, along with address of Registered Office.(c)The Contract is under GST Act and rules as applicable time to time.
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(AnnexureVIB of Tender Documents)
39 conditions · 11 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Electrical Works for DBRG-Upgradation and refurbishment of Pit lines no.6 & 7 at DBRG Coaching Depot.
LV-T-14-TSK-939
LV-T-14-TSK-939
Open
Works - General
14 Months
Tinsukia, Assam
₹0
₹1.8 L
27 Mar 2026
6 Mar 2026
13 Mar 2026
51 items across 3 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 38,65,013.12 | ||
| — | 96.00 | — | — | ||
| Supply, installation, testing and commissioning of IP65 rated LED Pit Light of 22 Watt conforming to the IS Specification as applicable, suitable for operation on AC input voltage range 40- 72 VAC, having pressure die-cast (PDC) aluminium housing with corrosion resistant powder coated finish, opal polycarbonate diffuser for uniform glare free illumination, high efficiency LED module with minimum luminous efficacy 110 lm/W, correlated colour temperature (CCT) 5700K-6500K, colour rendering index (CRI) 80, power factor 0.95, THD 10%, surge protection 2 kV, and minimum rated life of 50,000 burning hours (L70). The luminaire shall have minimum IP65 ingress protection, suitable for pit/inspection areas and damp locations, complete with integral electronic driver compatible with the specified voltage range, gasket, stainless steel mounting hardware, necessary accessories and connections, including proper fixing at site, wiring, testing and commissioning as directed by the Engineer-in-Charge. | — | — | — | 4,11,589.44 | |
| — | 4.00 | — | — | ||
| Supply, installation, testing and commissioning of 3 kVA Step Down Transformer, suitable for input supply 230 V AC, 50 Hz single phase and output voltage 40-72 V AC, for feeding LED Pit Lights, having copper wound coils, CRGO laminated core, air-cooled dry type construction, with high efficiency and low losses, complete with suitable enclosure, terminal connectors, earthing provision and mounting arrangement. The transformer shall conform to relevant standards, suitable for continuous operation, and the work shall include proper installation, connection with existing supply system, testing and commissioning as per the applicable IS Standards and as directed by the Engineer-in-Charge at site. | — | — | — | 1,55,650.68 | |
| — | 1800.00 | — | — | ||
| Supply, drawing and connection of single core 6 sq. mm PVC insulated, heat resistant, flame retardant low smoke and halogen (FRLSH), unsheathed multistrand copper cable conforming to IS 694 and suitable for voltage grade up to 1100 V, including laying through 32 mm dia GI pipe concealed in wall or on surface as required, complete with necessary accessories, bends, junctions and supports. The work shall include proper pulling, dressing, termination, connection and testing of the cable for Under Pit Lights, ensuring safe and reliable operation, as per direction of the Supervisor/Engineer-in-Charge at site. | — | — | — | 1,52,982 | |
| — | 803.00 | — | — | ||
| Supply, drawing and connection of single core 1.0 Sq. mm PVC insulated, heat resistant, flame retardant low smoke and halogen (FRLSH), unsheathed multistrand copper cable conforming to IS 694 and suitable for voltage grade up to 1100 V, including laying through 32 mm dia GI pipe concealed in wall or on surface as required, complete with necessary accessories, bends, junctions and supports. The work shall include proper pulling, dressing, termination, connection and testing of the cable for Under Pit Lights for earthing connection, ensuring safe and reliable operation, as per direction of the Supervisor/Engineer-in-Charge at site. | — | — | — | 13,169.2 | |
| — | 1200.00 | — | — | ||
| Supply, drawing and connection of single core 2.5 Sq. mm PVC insulated, heat resistant, flame retardant low smoke and halogen (FRLSH), unsheathed multistrand copper cable conforming to IS 694 and suitable for voltage grade up to 1100 V, including laying through 32 mm dia GI pipe concealed in wall or on surface as required, complete with necessary accessories, bends, junctions and supports. The work shall include proper pulling, dressing, termination, connection and testing of the cable for Under Pit Lights, ensuring safe and reliable operation, as per direction of the Supervisor/Engineer-in-Charge at site. | — | — | — | 46,524 | |
| — | 32.00 | — | — | ||
| Supply, fabrication, installation, wiring, testing and commissioning of 32 Amps industrial plug point complete with 32 A, 415 V, 3 phase, 5 pin industrial socket with matching plug top, housed in IP-65 weatherproof enclosure fabricated from CRCA sheet (minimum 1.6 mm thick) of size (L x B x H = 450 x 450 x 600 mm) and provided with 32 A, 4 Pole MCB (415 V, 50 Hz, breaking capacity 10 kA) for control and protection.The enclosure shall be duly folded and welded with hinged door, neoprene/rubber gasket for weatherproofing, locking arrangement, gland plate and cable entry provisions. The enclosure shall be mounted on a fabricated stand made of CRCA/MS with four legs of suitable height(approximately 1.0-1.2 m above ground level) with base plates for grouting/bolting on concrete surface. The stand and enclosure shall be provided with two coats of red oxide primer and two coats of synthetic enamel paint of approved shade.Wiring shall be carried out using 10 sq. mm, 4 core PVC insulated and sheathed aluminium cable of 1100 V grade, along with 1.0 sq. mm copper earth continuity conductor, drawn through 25 mm dia heavy duty PVC suction hose pipe and fixed with suitable MS clamps, saddles and fasteners as required.The work shall include all materials, fabrication, termination, earthing, fixing, testing and commissioning complete, as directed by the Engineer-in-Charge. | — | — | — | 3,36,785.6 | |
| — | 600.00 | — | — | ||
| Supply, laying, connection, testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable Size 120 SQ MM Single Core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988. For cable laying Excavation of earth depth 0.75 Mtrs. into breadth 0.58 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs.Complete in all aspect as per site conditions. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024 | — | — | — | 4,01,616 | |
| — | 6.00 | — | — | ||
| Supply, fitting and fixing of thermoplastic cable junction box (300 x 450 x 170 mm) with minimum IP65 protection, complete with 4 end terminals, including suitable cable glands, grommets and accessories for 120 sq. mm single core cable for loop-in and loop-out connection of power supply line, including proper fixing, termination and all materials as required, as per direction of the Engineer-in-Charge at site. | — | — | — | 2,50,620 | |
| — | 600.00 | — | — | ||
| Supply, laying, connection, testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable Size 35 SQ MM 4 Core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988. For cable laying Excavation of earth depth 0.75 Mtrs. into breadth 0.58 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs.Complete in all aspect as per site conditions. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024 | — | — | — | 4,47,000 | |
| — | 1000.00 | — | — | ||
| Supplying and laying of size 63 mm dia (OD-63 mm & ID-51 mm nominal) DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. complete as required. | — | — | — | 2,47,000 | |
| — | 1000.00 | — | — | ||
| Supply and laying of 32 mm dia medium gauge GI pipe conforming to IS 1239, including cutting, threading, bending and fixing with suitable clamps, saddles, supports and accessories, complete as required at site and as directed by the Engineer-in-Charge. | — | — | — | 4,37,000 | |
| — | 4.00 | — | — | ||
| — | — | — | 36,686.68 | ||
| — | 24.00 | — | — | ||
| — | — | — | 4,51,320 | ||
| — | 32.00 | — | — | ||
| — | — | — | 3,58,240 | ||
| — | 96.00 | — | — | ||
| — | — | — | 32,851.2 | ||
| — | 8.00 | — | — | ||
| Erection of earth by 50 mm dia 3 Mtrs. long (3.6 mm thickness) GI pipe and 8 SWG GI wire,GI nuts, bolts including masonry materials for earthing pit, salt, charcoal etc. and construction of earth pit covered with RCC cover slab 12.7 mm thickness and watering pipe per Drawing No PCEE/ELG/DRG/2024/1 Dtd 30.09.2024, | — | — | — | 34,828.32 | |
| — | — | — | 27,39,131.92 | ||
| — | 52.00 | — | — | ||
| Supply, fitting and fixing of 100 W Ultralite LED Highbay Luminaire having minimum luminous efficacy 100 lm/W, with pressure die-cast aluminium housing, aluminium heat sink, and minimum IP65 protection, suitable for 230 V, 50 Hz AC supply, complete with LED driver, necessary clamps, brackets, mounting arrangement, hardware and accessories, as required at site and as directed by the Engineer-in-Charge. | — | — | — | 6,50,000 | |
| — | 40.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of 100 W LED Flood Light having pressure die-cast aluminium housing, IP65 protection, system efficacy 100 lm/W, impact protection IK07, with inbuilt driver providing short circuit protection, reverse polarity protection, surge protection ±4 kV and THD 10%, suitable for operation on 220-240 V AC, 50 Hz supply, complete with necessary mounting arrangement, hardware and accessories, to be installed as required at site, as directed by the Engineer-in-Charge. | — | — | — | 2,00,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocumentTSK-939.pdf Tender Document
ATTACHMENT
AnexxuresSectionVIINew.pdf
ATTACHMENT
TenderDocumentTSK-939.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .