Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹91,600
Closing Date
4 May 2024, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
office of the S.E., EUDC-II, Sec-18, Noida.
Replacment of Damged Pole Wire etc Under EUDD-3 Noida
2024_PVVNL_922299_1
Replacment of Damged Pole Wire etc Under EUDD-3 Noida
Open Tender
Electrical Works
Item Rate
60 days
office of the S.E., EUDC-II, Sec-18, Noida.
Attached in DOC
2 documents required · 2 mandatory
₹3,540
S.E. EUDC-II, Noida.
₹91,600
22 May 2024
15 Apr 2024
4 May 2024
15 Apr 2024
4 May 2024
15 Apr 2024
Amount
[k.M ds vUrxZr vkus okys lHkh 19 ux fo|qr midsUnzksa ij LFkkfir 42 ux ikWoj ifjorZdksa dh MsYVk vfFkZax cksj eSFkM ds }kjk djkus dk dk;A leLr lkexzh o dk;Z dk;Znk;h laLFkk }kjk lEikfnr djk;k tkuk gS iw.kZ VuZdh ijA
Fabrication of 32mm MS round 1.5Mtr Long and V Shape as per drawing and conecting them with main earth mat in X and Y MS round bars by excavation of earth, inserting of MS round bars, welding and back filling of earth.
Boring with 150mm dia casing pipe to a probable depth of 19 meter long from ground level with skilled and unskilled labour including all T&P, boring apparatus and supervision charges etc required for proper completion of work.
Inserting 32x6mm G.I> Flat in 50mm dia B-Class (Jindal/Tata) ISI mark 6.0Meter long 3 pipe placed horizontally on ground and bolting the G.I. flat with 150mm Long 75x6mm copper plate conical piece on and then bolting the G.I. Flat with G.I. Pipe in such a way that copper flat remains in contact with the pipe. Lowering of 6 Meter Long G.I. Pipe with conical copper plate connected and at bottom along with G.I. flat inside the pipe in boring of 150mm G.I. Pieces by G.I. sockets along with 40x6mm g.I. flat running inside the pipe by making 150cm lap joints 75mm above ground level. Taking out 40xx6mm G.I flat the upper end of Pipe by making a cut of 45mm wide up to a depth of 50mm in upper portion of G.I. pipe and providing 1 No. Cap type GI socket on upper threaded portion of pipe for water pouring in the pipe at regular filling the space. all the required material will be provided by contractor.
Excavation of pit of size for formation delta for 1 Meter x1 Meter x 1 Meter M.S. electrodes of 40mm dia 3 Mtr long in the earth on all the three corner of the pit equal distance of 1Meter long keeping the top of electrode 50cm above the pit ground level, welding of 40mm MS round pieces of required length on all three sides of electrodes. 50x6mm M.S. Flat connecting bore earthing & neutral (HV&LV) of all T/Fs.
Replacement of Damage Distribution Tranformer Fencing 100 Nos at All 19 Nos Sub Station under EUDD-III Noida
Construction of New Fencing of Transformer. The fencing shall be frame of size 1.5mt x1.80 mt fabricated out of MS angle iron of size 40x40x5 mm having 2 Nos. legs of 45 Cm. long in each frameduly welded and fixed with wire mesh of size 75mm 25mm, 10 SWG within the frame, pressed under MS flat of size 25x5 mm inside the angle iron on all four sides with the help of approx. 20 Nos. bolts and nuts. of 10 mm dia along with cross bracing of 25x5 mm MS flat on every frame will be grouted in 1:2:4 cement mortar with cement, coarse sand 20 mm gauge stone ballast in the size 0.22x0.22x0.45 Mtrs. Every frame after repairing will be painted with one coat of red oxide and two coats of blue synthetic enamel paint of approved make after proper cleaning. The above mentioned frame will be jointed with each other with 70 mm long MS flat of size 25x5mm by first class welding as per site. Fabrication and providing of wire mesh fencing frame for gate of size 1.5x180 Mtrs. Fabricated as items no. 2 and fixing of gate frame at each S/S as per site requirement with grouted frame providing 3 Nos. 100 mm size heavy duty hinges duly welded and having suitable locking arrangment and proper painting.
SUPPLY AND INSTALLATION OF 100 Nos. L.T. THREE PHASE METER PANNEL BOX (KANSHIRAM YOJNA SECTOR - 45 NOIDA) ON TURN-KEY BASIS UNDER EUDD – III AS PER FOLLOWING :- leLr lkexzh o dk;Z dk;Znk;h laLFkk }kjk lEikfnr djk;k tkuk gS iw.kZ VuZdh ijA
Supply and Installation of new L.T. Meter Pannel Boxes (Three Phase) for 08 Nos./16 Nos. Meter as per following specification with all relevant certificate:- 1) Providing of new L.T. Meter Pannel Box of size 1350x1200 Sq.mm. + 450x900 Sq.mm. = 2.025 Sq. Mtrs. (as per drawing) made of MS sheet of 1.6 mm (+ 0.2 mm)/16 SWG thick which required into 4 columns contains & feeders as per drawings enclosed of size 450x450 Sq.mm. each for fixing the consumer's meters, 01 Nos. busbar chamber of size 900x300 Sq.mm. for fixing 04 Nos. Aluminium bus-bars for R, Y, B &N in box & 450x300 Sq.mm. feeder for incoming MCCB 200 Amp. All 04 Nos. aluminum bus bars of suitable size (40x10mm) shall be provided R, Y, B & N by insulators. The metallic covers will have to be provided on each columns of the box. The side wall of box will have suitable holes for service cables. For fixing the meter pannel box, necessary arrangement by providing clamps, nut & bolts etc. are to be made. Wiring of meter pannel box has to 10mm copper wire & lugs. Complete meter pannel box (inside & outside) should be painted with one coat of red oxide primer then 02 coats of light grey enamel paint of reputed brand make. Before painting the sun faces shall be thoroughly cleaned from dust, grease of rust. Locking arrangement with 01 No. pad lock shall be provided on each cover of the Meter Pannel Box. Complete the work in all respect. 2) Meter Pannel Box mounting by MS Angel 40x40x5mm for Meter Pannel Box mounted on wall. 3) Incoming MCCB of 200 Amp. TP L&T / Havell’s / ABB make to be installed in Meter Pannel Box. 4) Fixing of Consumer's meters in Meter Pannel Box (08 Nos./ 16 Nos. three phase) in each box or as per site requirement) and reconnection of consumer's connections with the meters and cable reconnections with the Bus-bars. Complete the work in all respect.
Disconncetion of all consumer connection from pannel as per requirement.
Reconncetion of all consumer connection from pannel after replacement as per requirement.
Dismantling of damaged L.T. Meter Pannel from earth on work site.
Carriage of above dismantled Pannel from works site to JE store/ any store of PVVNL Discom & proper stacking and safe Carriage with loading & unloading both ends.
Installation of above new L.T. Meter Pannel (Three Phase) in place of damgaged L.T. Meter Pannel with required items complete in all respect.
Providing & fixing of 3.5c x 70/150 sq mm aluminium armoured XLPE L.T PVC cable or as per site requirement and as per approved PVVNL technical specification for installation above Meter Pannels as per requirement.
Chemical earthing for above new L.T. Meter Pannel Boxes (Three Phase) and installation as per following :-
Chemical earthing with earth elctrode strip in pipe terminal type chemical earthing proper hot deep galvanization dia 50 mm length 3 mtr down conductor size - 32mm x 6mm terminal connection hole dia 8mm The cavity between the strip & pipes is filled with condutive mixture - for hermetically filling inside the cavity i.e. between secondary conductor & primary conductor, crystline compound is to be injected in the electrode assembly. It is a combination of high conductivity metal alloys, copper & aluminum power, conductive carbon / cement and bonding material etc the electrode should be sealed from both the ends. The outer pipe of the elctrode should be zinc coated the characteristics of this compound is highly cnductive, non magnetic & non corrosive in G.I. Including providing of Pgs backfill compound each elctrode should be supplied with bags of 25 k.g. x 2 bfc compound (ground resistance enhancement powder 50 kgs each CPRI tested to connect the above chemical earthing with the GI strip of size 32mmx6mm.
Providing and installation of LT ACB 800 Amp. with cabinet / structure (Make L&T, Schneider, ABB, Hevell's, C&S, HPL etc.) as per following specification on Turnkey Basis with all relevant certificate :-
800amp. 03 pole fixed manual ACB.
Red/yellow/blue light indication
ON & OFF Indication
Amp., Volt meter& energy meter digital
Metering C.T 800/5A,
Panel fabrication of size 1250mm x 900mm x 600 mm made of M.S sheet 14 gauge with powder coating with panel lock and key arrangement.(two nos). and additional locking arrangement seprately including providing hut type shape as per drg.
Fabrication of aluminium bus-bar for each phases
Incoming size 425 mm x 50mmx12 mm (twin)
Out going size 720 mm x 50mm x 12 mm(twin)
Neutral size 900mmx50mmx12 mm.
Fabrication of pannel stand made of M.S Angle of size 900mm x 600mm x 500 mm as per drg.
Assembly of above ACB, Indicators, Meters, Metering CT & bus bar arrangment in the panel, fitting the panel on Stand with nut and bolts with wiring etc. & grouting in ratio 1:4:8 with cement, coarse sand and brick blast.
Providing and fixing of aluminium bus bar of size 300mmx60mmx12 mm on L.T side of T/F.
Making all connections with ACB & Distribution T/F and commissioning the ACB complete in all respect.
PROVIDING AND INSTALLATION OF CHEMICAL EARTHING FOR ACB (WITH ALL MATERIAL AND LABOUR) AFTER INSTALLATION RESISTANCE SHOULD BE LESS THAN ONE OHM. AS PER FOLLOWING (The all material and labour shall be provided by the contractor)
Providing of earth elctrode for chemical earthing Pipe in pipe type proper hot deep galvanization dia 50 mm length 3 mtr - 32mm x 6mm terminal connection hole dia 8mm The cavity between the pipe & pipe is filled with conductive mixture - for hermetically filling inside the cavity i.e. between secondary conductor & primary conductor, crystalline compound is to be injected in the electrode assembly. It is a combination of high conductivity metal alloys, copper & aluminum power, conductive carbon / cement and bonding material etc the electrode should be sealed from both the ends. The outer pipe of the elctrode should be galavanized the characteristics of this compound is highly cnductive, non magnetic & non corrosive in G.I. Including providing of backfill compound each elctrode should be supplied with bags of 25 kg x 2 bfc compound (ground resistance enhancement powder 50 kgs each CPRI tested for LT ACB installed at different DTs.
Providing and fixing of GI strip of size 32 mm x 6 mm suitable for LT ACB installed at different DTs.
Providing and fixing of PVC Pit covers for above earthing electrode terminals.
Providing AND FIXING of Al. Lug size 400mm./800mm AS PER SITE REQUIREMENT.
Shiva Electricals Company
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .