Turnkey/Composite Works Tender (Civil/Interior, Electrical and Allied, HVAC) for infrastructure creation for staff seating arrangement at C-DAC STP building, SPPU Campus, Pune.
2022_DIT_731689_1
CDACP/LnB-STP/22-2463/22-23
Open Tender
Civil Works - Others
Works
60 days
Pune
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,500
CDAC
Exempted
Pune
31 May 2023
27 Dec 2022
16 Jan 2023
27 Dec 2022
16 Jan 2023
11 Jan 2023
28 Dec 2022 - 11 Jan 2023
3 Jan 2023
Amount
INTERIOR/CIVIL WORK - Dismantling of old material
Dismantling aluminium/ Gypsum partitions: Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material within 50 meters lead as directed by Engineer-in-charge
Providing and applying PU grouting to glass façade gap between wall & glass façade with firstly open the 4mm crack by grander around glass façade, cleaning that particular area & applying nitoseal PU40 grout chemical 6mm to 10mm depth including transport, cantilever zulla, safety belt etc. All the works to be carried out as per relevant IS specifications & code of practices.
Removing old paint like dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches scaffolding etc. complete.
Construction and Painting Work
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete
Providing and applying plastic emulsion ( luster) paint of approved quality, colour and shade to old and new surfaces with one coat of primer and two coats of paint including scaffolding, preparing the surface. etc. complete
New partition, ceiling and aligned work
Providing and fixing in position Gypsum board false ceiling with 12.5 mm thick Gypsum boards, screwed/fixed to the under structure of suspended G.I. Grid constructed and suspended from the main ceiling consisting of ceiling sections of size 25 x 50 mm maximum centre to centre distance of 600 millimetre perimeter channel and intermediate channels at maximum centre to centre distance 1200 millimetre galvanized grid should be fixed to reinforced cement concrete slab. The gypsum board should be fixed to galvanized iron grid with necessary screws. The boards should be taped and filled from underside to give smooth, seamless ceiling. The rate should include necessary additional ceiling sections and intermediate channels. Additional intermediate channels should be fixed to strap hangers for additional support to prevent strapping at every 1200 millimetre item to be completed in all respect including necessary sleeves for ducts finishing of joints cut outs, painting including labour, material, lifts etc. all complete.
Supply & fixing of acoustical mineral fibre board (Dune-ML-RH-99) false ceiling of Armstrong/AMF or equivalent make system with 16 mm Silhouette (BR) grid quick hook suspension system having main tee 3000mm long x 38 mm web height x 15mm wide silhouette (BR) sections. The main runner is to be fixed with 4mm thick pre-stretched GI wire with soffit clear & GI Raw plug inserted on the main roof to be fixed at 1200 mm c/c. The last hanger at the end of each main runner should not be greater than 450 mm from the adjacent wall. The main runner will be at the distance of 1200 mm c/c. The 1200 mm x 38 mm x 15 mm silhouette (BR) wide cross tee sections, having an integrally formed hook nose with precise butt cut joint end is to be fit in between the main tee at a distance of 600 mm to make a module of 1200mm x 600mm. Another cross tee having an integrally formed hook nose with precise butt cut joint end of size 600 mm x 38mm x 15mm is to be fitted at 1200 mm sections parallel to main tee at 600mm centre to make a square grid of 600 mm x 600 mm. All base frame material should be made of good quality galvanized steel. It should have a capping of material coated with baked polyester paint. The shadow moulding perimeter angle white coloured secured at 450 mm c/c is to run all along the peripheral, Prime Dune, RH-99 per painted tiles, micro look, 15 mm thick suitable for 600mm x 600mm grid to be placed on grid. Tiles should have NRC of 0.50, STC of 34 dB, having light reflection of 85% or more & thermal conductivity K-0.052-0.057W/sq.m/ degrees centigrade. The fire rating of tile should be class 0 for fire propagation & class I for spread of flames as per BS 476 & having humidity resistance of 99% RH. The board should have a density of 240-260 kg/Cubic meter. The rate should include for cut-out for AC grills & light fixtures, additional members if required are to be provided into the grid system. The work has to be done as per the direction of Engineer-in-charge.
Providing and Fixing Vertical Blinds of approved Make and shade of 100mm regular fabric with powder coated aluminium channel with tilting PVC chain & bottom weight plate with all necessary fixtures and fitting etc. complete. (Sample to be final by Engineer In-charge prior execution of work)
Terrace floor waterproofing work: Granite joint filling with water proof grouting material, providing and laying 125mm thick, M10 grade concrete in slope to drain out the rain water.
Providing and applying chemical coating primer and 2 coat of waterproof paint coating to exterior side of wall which should match to existing colour shade, including transport , cantilever zula safety belts etc. all works to be carried out as per relevant IS specification & code of practices.
FURNITURE
Modular Linear Workstation of Size 1200(L) X700(W): Supply and installation of above workstations with minimum 70 mm thick 950 mm high panels as partition (Sample Drawings are attached). With combination of two separate metal raceways for data and power at bottom, two intermediate fabric blocks, top tile - fabric tackable, white board, fabric magnetic.. The table should be complete with suitable keyboard holder tray. The cut-outs for Raw Power +6 Module for power UPS and 2 Module for network point has to be there .The sample shop drawing has to be approved by client before delivery. Note:- 1)Material of table top:- Work top should be made of 25mm thick Pre-laminated particle board. 2)Material for tiles foretop: Fabric magnetic (over GI sheet) plus white board 3)Material of bottom tile: Metal tile (GI Sheet) 4)Plain edge banded with 2mm PVC tape 5)Frame of the workstation: Powder coated extruded Aluminium sections
Supply and installation of Top supporting pedestal with flat metal front of total size 390w x 585d x 700 ht, 3dr = 2 box + 1 file, central locking. Note - 1) The top supporting pedestal should be from the same OEM of modular workstation. 2) The material of pedestal shall be CRCA / GI sheet of minimum 0.6mm thickness in power coated finish as per approved colour.
Providing and fixing removable raised/false flooring on existing false grid of approved make and of 600mm x600mm & 35mm thickness which should match to the existing false flooring.
Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied over an under coat of primer applied of approved brand and manufacture
ELECTRICAL & ALLIED WORKS - MAIN LT PANEL / DB'S
Supply & Installation of 25/32A, DP, MCB, box with 20A, metal clad / modular plug-socket including power circuit of (4/6 sq.mmX3core) copper flexible wires directly taken from the relevant Raw/AC DB through PVC conduits for room CASETTE /SPLIT A/C including all necessary hardware & accessories, etc. (Schneider / Hager / Legrand / Siemens / L&T make)
CABELS / MAINS
SSupply & Installation of 1100V grade armoured cable having sector / circular shaped aluminium / copper conductor PVC insulated cores, laid up, PVC tape wrapped d inner sheathed, GI strip / wire armoured and overall extruded PVC sheathed confirming to IS: 1554, laid on wall / ceiling using GI clamps & spacers as per route shown at site and further as directed by Consultant at site in the following sizes :- (Make - Polycab / Finolex / RR / Havells) NOTE :- All Armoured cables shall be provided with temporary labelling at every 5mtrs & then finally with metal identification tags showing the size & the location from/to the respective Panel / DB, at both the ends. The rate should include terminations at both ends with suitable lugs and glands as applicable
4C x 10 Sq.mm Copper Armoured cable with 2 runs of 12 SWG GI bare wire(Main VTPN DB to Classroom RAW/LIGHT/UPS DB)
3C x 6 Sq.mm Copper Armoured cable with 2 runs of 12 SWG GI bare wire(UPS/Light DB)
WORKSTATION UPS POWER WIRING
Supply & Installation of concealed / reassessed UPS point wiring using 600V 3R (P+N+E) x 1.5 Sq.mm copper conductor PVC insulated wires (with proper R,Y,B colour code) pulled through already laid PVC raceway on walls and through table partition including 3R (P+N+E) x 2.5 Sq.mm circuit wires from the relevant DB and also including 2.5 sq mm green colour copper earth wire and approved make modular type switch plate, switches, MS concealed back box, etc. as required & as approved by the consultant. (The item rate shall include Lighting / Raw / UPS Power Circuit wiring from relevant DB to the switch board with 3Rx2.5 Sq.mm wires& from switch board to next switch board OR to the first light point / primary point / full point)NOTE :- 1. Only PVC insulated wire shall be used; 2. Conduit carrying circuit wiring should not carry point wiring and Conduit carrying point wiring should not carry sub main/circuit wiring; 3. Flexible conduits & Elbows are not allowed; 4. The wires from ceiling junction to light points / light fixture shall be drawn in flexible PVC conduit with adaptor& cover for junction box & crimp type lugs at both the ends along with necessary hardware & accessories, etc. as required; 5. Proper ferrules, lugs, must be used in all cabling and wiring on both load / source end; 6. Each switch board must be provided with respective ferrules representing the respective DB, Phase & Circuit numbers; 7. Looping of Neutral / Earth wire between two separate Primary / Full Points is strictly not allowed; 8. Looping of Neutral / Earth wire between two separate circuits on similar or other phase is strictly not allowed; 9. Feruling / numbering / tagging to wires with circuit number &db name for all lighting & raw / ups power shall be strictly followed at both DB & switch board / switch socket boards ends
Supply & Installation of primary UPS point wiring for UPS or stabilized power plug points on workstations / table for computers using 3C X 2.5 Sq mm copper conductor PVC sheathed white colour flexible cable pulled through already laid Surface PVC Box raceway and table/workstation partition raceways and taken up to table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 5A , 3 pin sockets above table top/bottom & 1 No., 15A Switch above table top, wired together forming one point. The earth wire of 3 core flexible cable to be of yellow-green colour only. (Maximum 3 nos desks served by one circuit from DB)
Supply & Installation of Secondary UPS point wiring for UPS or stabilized power plug points on workstations / table for computers using 3C X 1.5 Sq mm copper conductor PVC sheathed white colour flexible cable pulled through already laid table partition raceways and taken up to table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 5A , 3 pin sockets above table top/bottom & 1 No., 10/15A Switch above table top, wired together forming one point. The earth wire of 3 core flexible cable to be of yellow-green colour only.
WORKSTATION RAW POWER WIRING
Supply & Installation of concealed / reassessed RAW point wiring using 600V 3R (P+N+E) x 1.5 Sq.mm copper conductor PVC insulated wires (with proper R,Y,B colour code) pulled through already laid PVC raceway on walls and through table partition including 3R (P+N+E) x 2.5 Sq.mm circuit wires from the relevant DB and also including 2.5 sq mm green colour copper earth wire and approved make modular type switch plate, switches, MS concealed back box, etc. as required & as approved by the consultant. (The item rate shall include Lighting / Raw / UPS Power Circuit wiring from relevant DB to the switch board with 3Rx2.5 Sq.mm wires& from switch board to next switch board OR to the first light point / primary point / full point)NOTE: - 1. Only PVC insulated wire shall be used; 2. Conduit carrying circuit wiring should not carry point wiring and Conduit carrying point wiring should not carry sub main/circuit wiring; 3. Flexible conduits & Elbows are not allowed; 4. The wires from ceiling junction to light points / light fixture shall be drawn in flexible PVC conduit with adaptor& cover for junction box & crimp type lugs at both the ends along with necessary hardware & accessories, etc. as required; 5. Proper ferrules, lugs, must be used in all cabling and wiring on both load / source end; 6. Each switch board must be provided with respective ferrules representing the respective DB, Phase & Circuit numbers; 7. Looping of Neutral / Earth wire between two separate Primary / Full Points is strictly not allowed; 8. Looping of Neutral / Earth wire between two separate circuits on similar or other phase is strictly not allowed; 9. Feruling / numbering / tagging to wires with circuit number &db name for all lighting & raw / ups power shall be strictly followed at both DB & switch board / switch socket boards ends.
Supply & Installation of primary raw point wiring for raw power plug points on workstations / table using 3C X 2.5 Sq mm copper conductor PVC sheathed white colour flexible cable pulled through already laid Surface PVC Box raceway and table/workstation partition raceways and taken up to table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 5A , 3 pin Modular sockets above table top/bottom & 1 No., 15A Modular Switch above table top, wired together forming one point. The earth wire of 3 core flexible cable to be of yellow-green colour only. (Maximum 3 nos desks served by one circuit from DB)
Supply & Installation of Secondary raw point wiring for raw power plug points on workstations / table using 3C X 1.5 Sq mm copper conductor PVC sheathed white colour flexible cable pulled through already laid table partition raceways and taken up to table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 5A , 3 pin Modular sockets above table top/bottom & 1 No., 15A Modular Switch above table top, wired together forming one point. The earth wire of 3 core flexible cable to be of yellow-green colour only.
LIGHTING POINTS IN ROOM,
Supply & Installation of concealed / reassessed / surface light point / fan point / call bell point wiring using 600V FRLS grade 3R (P+N+E) x 1.5 Sq.mm copper conductor PVC insulated wires (with proper R,Y,B colour code) pulled through heavy gauge PVC conduits laid concealed over false ceiling or in wall chases or on the ceiling in case of an open ceiling including 3R (P+N+E) x 2.5 Sq.mm circuit wires from the relevant DB and also including 2.5 sq mm green colour copper earth wire and approved make modular type switch plate, switches, MS concealed back box, etc. as required & as approved by the consultant. (Each circuit shall not feed more than 8 points OR 800 watts as per following configuration.) (The item rate shall include Lighting / Raw / UPS Power Circuit wiring from relevant DB to the switch board with 3Rx2.5 Sq.mm FRLS wires & from switch board to next switch board OR to the first light point / primary point / full pointint)
Primary light points including the cost of 5A switch
Secondary light points looped from the above point(maximum 3 points looped from one primary)
Supply & Installation of (26-32W) (2' X 2') full lit panel type LED Light fixture, CRI>80,The fitting shall be suitable for grid / plain ceiling type & surface mounted / to be hanged from the ceiling at the height approved by architect. (CGL, PHILIPS WIPRO, GE or equivalent category & model as approved by client / architect / consultant.)
Supply & Installation of (12 W) LED Spotlight/Down light flush mounted Light fixture. (CGL, PHILIPS WIPRO, GE or equivalent category & model as approved by client / architect / consultant.)
DATA NETWORKING
Supply & Installation of Modular Data point including approved make Cat - 6 UTP cable through already laid trenches, and new flexible conduit in table partition ,RJ45 information outlet face plate, etc. with Termination, Testing and Documentation of UTP Points complete as required.(D-Link or equivalent)
Supply & installation of 24 Port 1 Gbps(Minimum) Unmanaged switch including crimping complete in all respect etc. with both ports for Ethernet and Fibre Up-linking(D-Link or equivalent)
Supply & installation of 24 port jack panel in existing network rack(D-Link or equivalent)
Supply of mounting patch cord (3 feet')
Supply of mounting patch cord (7 feet')
Supply & Installation of 12 U floor/wall mounted network rack including all necessary hardware, accessories, etc. in classrooms
Supply & laying of approved make Cat - 6 UTP cable through PVC conduits, with Termination, Testing and Documentation complete as required for up linking(D-Link or equivalent)
Supply & installation of Fire Extinguisher 5 Kg ABC Type
TRENCHING / FLOOR -RACEWAYS
Supply and laying PVC Raceways with cover, & two cable compartment for UPS Power Circuit Cable and Data cables
75 x 75 x 1.6mm thick PVC Raceways with cover
VOICE/TELEPHONE NETWORKING
Supply & Installation of Telephone /Voice point including approved make Cat - 6 UTP cable through already laid trenches / conduits, RJ45 information outlet, in single face plate, in workstation partion wall etc. with Termination, Testing and Documentation of UTP Points complete as required.
Supply & Installation of and commissioning of indoor type telephone 50 pair MDF with Krone module including all hardware & accessorised , etc. complete as required. With suitable S.S. frame for mounting tag module, cable, wires and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthling. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc, to be provided in the box
Supply & Laying of 20 pair telephone cable through heavy gauge pvc conduit including all necessary hardware & accessories, etc.
HVAC Work-HIGH SIDE WORK
FOR STAFF ROOM -Supply of Cassette AC of 2TR (minimum 2star non inverter model) with onsite One year Comprehensive warranty.
HVAC Work-Low SIDE WORK
Cassette AC Indoor and outdoor unit Installation, testing, commissioning charges
REFREGERENT PIPING,POWER/CONTROL CABLING:-Supply, Installation, Testing & Commissioning of copper piping complete with copper fittings & charge of refrigerant gas for the above units(including drilling through wall), Piping associated with Cassette AC/Split AC units shall be insulated with 13 mm thick closed cell elastomeric insulation .Quoted price shall be inclusive of UV protection paint for all exposed pipes. Note:- 1) The required copper pipe size shall be as recommended by OEM of the AC. 2)Price shall be comprise of suitable perforated tray for refrigerant pipe laying with adequate supports & copper power cabling from indoor to outdoor unit as required.
CONDENSATE DRAIN PIPING-Supply, Installation Testing and Commissioning of 25 mm dia. Chlorinated Polyvinyl Chloride (CPVC) pipes, including all CPVC plain fittings, including fixing the pipes with pipes clamps & hanging support to be taken from ceiling/wall at 1.00 m spacing. This includes joints of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Supporting arrangement in accordance with the approved shop drawings and specification. Pipes shall be insulated with 9mm thick closed cell elastomeric insulation in tubing form.
Dismantling and shifting of 10-11TR capacity PAC unit from 1st floor to C-DAC Main building( 200 mtr distance from dismantling position)
Dismantling and shifting of 10-11TR capacity PAC unit Outdoor unit from 1st floor C-DAC Main building( 200 mtr distance from dismantling position)s
SNEHAL ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .