CWE (AF) BAGDOGRA
Commander Works Engineers (AF) Bagdogra Bagdogra Airport (WB) Pin- 734 421 Tele 0353 - 2698308
PROVN OF TROLLY MOUNTED STANDBY TRANSFORMER OF 500KVA AND 500KVA DG SET AT AF STN BAGDOGRA UNDER GE (AF) BAGDOGRA.
2024_MES_639058_1
8543/BAG/2023-24/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BAGDOGRA
MES Contractor enlisted as Class C category bii having deposited Standing Security of Rs 1,75,000.00 with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category.
10 documents required · 10 mandatory
₹1,000
₹1.6 L
Yes
11 Mar 2024
27 Jan 2024
26 Feb 2024
27 Jan 2024
19 Feb 2024
12 Feb 2024
Amount
Note 1:- (Applicable for all parts/items) : The biidders/contractors are advised to read tender documents & all corrigendum/amendments and general condition of contracts before entry/quoting the rates. Note 2:- Attention to bidder is hereby invited to upload revised BOQ if published during their bid submission. Uploading of incorrect/ pre-revised BOQ shall be treated as non bonafide and rejected. Fixed credit has been given in technical documents which shall be taken into account during acceptance of bid/tender.
Supply, installation, testing and commissioning of Trolly mounted Silent Diesel Engine driven generating set of cap 500 KVA/400 KW, 0.8 PF, at NTP conditions, complete with AMF panel, control panel having meters sound proof canopy considering all derating factors with mounted on common base frame along with sound proof enclosure (acoustic enclosure), 1500 RPM, with silencer pipe independently supported from Engine to outside upto 01 meter , AVM padded foundation as per manufacturer's design, cold starting kit, battery start with suitable size cable for connection from DG Set to panel board complete with and incl the following :- (a) PRIME MOVER:- Vertical diesel engine of suitable cap water cooled (Radiator mounted), closed circuit as per BS 649 or IS 10002 direct injection type turbo charged electric starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24 hrs continuously with 10 % overloading for 01 hrs in every 12 hrs as per BS 5514/BS649. Engine shall be equipped with all standard fitting as per manufacturer recommendation and mounted on common base frame with following accessories as per manufacturer design :- (i) RPM cum Hrs meter. (ii) Battery charging ammeter. (iii) Ignition key/ starting with push button switch. (iv) Lubricating oil pressure gauge. (v) A-1 governor controlling. (vi) Oil temperature gauge. (vii) Water temperature gauge. (viii) Lubricating oil coolant heater. (ix) Flywheel housing with flywheel to suit double bearing coupled alternator.
(x) Air cleaner dry type with vaccum indicator. (xi) Lub-oil filter with filter element (xii) Radiator with fan. (xiii) Corrosion inhibitor coolant. (xiv) 12 V -02 Nos starting equipment comprising with the following :- (aa) Two Nos 12 V 180 AH maintenance free battery. Make : Exide/ Standard (ab) Battery charging alternator with inbuilt regulator. (ac) Starter motor of suitable capacity. (ad) Battery leads (copper cable) of suitable of size with brass thimbles and terminal. Make of engine:- Cummins/ Ashok Leyland/ Kirloskar Green. (b) ALTERNATOR:- Alternator rating 500KVA/400 KW, 03 phase 50 cycles, 415 Volts, 04 wires supply at NTP 0.8 PF running @ 1500 RPM self excited, self regulated mounted on a strong fabricated steel frame suitable for mounting on permanent foundation to be coupled with the above engine. The alternator shall be confirming to BS - 2613 or IS-4722. Make of Alternator:- Alstom/ Siemens/ Kirloskar Electric. (c) ACOUSTIC ENCLOSURE:- (i) DG set shall be fitted with acoustic enclosure suitable for 500 KVA as per manufacturer instruction and confirming to CP CB norms of 75 dBA @ 1 mtr at 75% load under free field condition acoustic enclosure shall compile shall revised noise limit for DG set vide GSR - 371 (E) dt 17 May 2002 and its amendments under environment (projection) act 1996 issued by Min of Environment and forest.
(viii) Digital energy meter having facility to show KWH, KW, KVA, power factor reading etc. Make: AE/ Legrand (ix) Power contactor suitable for 500 KVA DG set incl over current, earth fault protection relays, reverse power relay, alarm for high water/lub oil temp and low lub oil pressure complete with cable gland plate for cable entry etc. (e) OTHER FITTINGS:- (i) Battery charger having electric circuit consisting of triods, rectifier, capacitor and resistor etc. Note:- The battery charger should be able to charge the battery at all the time whenever electrical supply given to the battery charger through control panel are electric power point. (f) FUEL TANK:- Fuel tank of suitable capacity as per manufacturer instructions capable to store 12 hrs running of DG set, as per manufacturer design, with all pipes connecting upto fuel pumps including oil level indicating gauge in ltrs, drain and air vent plug etc. (i) The contractor shall supply 01 Years maint spare for the above Gen Set :- (aa) Fuel filter- 12 Nos. (ab) Lub oil filter - 12 Nos (ac) Element air cleaner outer - 06 Nos. (ad) Element air cleaner Inner - 06 Nos. (ae) V -Belt - 02 Sets. (af) Filter lubricant oiF21:F23l by pass 03 Nos.
(iii) Fuel/ oil required for load test shall be arranged by the contractor and cost thereof is deemed to be included in the lump sum amount quoted by the contractor. (j) PCC / RCC foundation of size 6.6 mtr x 3.0 mtr x 0.45 mtr complete as per manufacturers design. Note:- (i) Contractor will satisfactorily conduct load test of DG set for 12 hours including run on 10% overload for 1 hour at their own risk, cost and arrangement. (ii) Testing eqpt will be arranged by the contractor. (iii) Fuel/ oil required for load test shall be arranged by the contractor and cost thereof is deemed to be included in the lump sum amount quoted by the contractor. (iv) Trolly for carrying 500 KVA DG set considered uder separate item
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 500 sqmm x 3.5 core complete all as specified and directed.
Supply& fabrication DG set trolly for 500 KVA Capacity DG set of approx size 4340x1740x1975 with amin chasis of 100X50 mm MS Channel of 6 mm Thickness support channel sizes of 75X 40 MM MS channel size of wire mesh including provision of suitable door at rear side fixed by hinges and locking system and 2 nos axle of 63 mm square forged steel toe hook and axle will be fitted with leaf spring /suspension the trolly will be nos of of double planted rim and 4 nos of tyre and tube of size 7.50:16 .The trolly should be carrying of 6 ton and weight of trolly should not be more than 2000 KG.Trolly shall be painted with two coat of synthetic enamel spray painting over a coat of redoxide primer,including the following:(a) Cable reel for 500 sqmm cable approx 75 meter all as specified and directed.
Supply, fixing, connecting and testing 500 KVA step down, Trolly mounted outdoor type 11/0.433 KV, AC double wound core type, copper wound, oil immersed, air naturality cooled with external cooling tubes, transformer delta connetion of HV side and star connection on LV side in accordance with vector symbol DyN-11 (vector group 4) and having tapping of +7.5% in equal step of 2.5% change by means of auto on load tap changing arrangement. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-1 and IS-1180 the transformer should have cable box on LT side and brass bushing on HT side. The limit of temp rise after continuous full laod run as specified in SSR Part-1 and IS-1180 (level 3) shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified comprising with and including the following specifications :- i) 01 Nos Cable box on LT side consisting of 03 Nos porcelain bushing with bushing brass rods and nuts washers and cable glands of suitable for reception of cable LT 1100 Volts grade XLPE insulated heavy duty including gland joint complete. ii) HV bushing with arching horn on 11 KV side. iii) Oil conservator with filter type drain valve and oil level guage. iv) Explosion Vent.
v) Thermometer Pocket. vi) Two Earthing Terminal on tank body to facilitate fixing of 32x6 GI strips. vii) One No Thermometer Dail type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature guage : Max reading pointed terminal. viii) Rating plate with terminal marking plate. ix) Oil level guage. x) Oil drain filter valve. xi) Oil filling pot on top cover with plug. xii) Air release valve/plug. xiii) First fill of transformer oil confirming to relevant to IS and tested upto 60 KV dielectric strength. xiv) Inspection cover. xv) Lifting lugs and jack lifting pad support. xvi) Bi-directional plain / flanged rullers. xvii) Explosion vent with double diaphragm and sight glass.
Supply and fix cable jointing kit for 11 KV grade cable for out door termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 Sqmm complete all as specified and directed.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts (Earthed) grade, of size 3 core 95 sqmm complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 500 sqmm x 3.5 core complete all as specified and directed.
Supply& fabrication trolly for 500 KVA Capacity transformer of approx size 680x620x720 mm with amin chasis of 100X50 mm MS Channel of 6 mm Thickness support channel sizes of 75X 40 MM MS channel size of wire mesh including provision of suitable door at rear side fixed by hinges and locking system a24nd 2 nos axle of 63 mm square forged steel toe hook and axle will be fitted with leaf spring /suspension the trolly will be nos of of double planted rim and 4 nos of tyre and tube of size 7.50:16 .The trolly should be carrying of 2 ton and weight of trolly should not be more than 1000 KG.Trolly shall be painted with two coat of synthetic enamel spray painting over a coat of redoxide primer,including the following:(a) Cable reel for 400 sqmm cable3.5 core & HT 95 sqmm 3 core approx 100 and 50 meter respectively meter complete all as specified and directed.
SARKAR ENGINEERING CO.
M/S BENGAL ENGINEERING ENTERPRISES
MS ORIENT ENGINEERING WORKS
Shree Ram Construction
SHRI SANJAY KUMAR GUPTA
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .